Download Print deze pagina

DAB ebox Instructies Voor Installatie En Onderhoud pagina 95

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 226
8.13
System status in Kiwa mode
8.14
Setting the Ebox with dip switches
If the Ebox is provided with a display, it is recommended to use the display for configuration. Otherwise it is possible to use the dip
switches inside the panel and set them as shown in Figure 51.
8.15
Activation of the set
To activate the set it is necessary to enable the pumps. During the first configuration, for safety's sake, the pumps are
disabled and are OFF. To change to automatic mode, just briefly press the
shown in Figure 52.
The following modifications may be made during configuration:
If the expansion vessel is larger than 100 litres, set DS_A1 at OFF.
If you want the pumps to be exchanged every 24 hours and not at each restart, set DS_A2 at ON.
If you do not want protection against too rapid restarts, set DS_A3 at OFF.
If you do not want protection against lack of water, set DS_A4 at OFF.
If you want to bring the delay in switching off the pumps from 2 to 4 seconds, set DS A6 at OFF.
If you do not want to use the pump P1 set DS_A7 at ON.
If you do not want to use the pump P2 set DS_A8 at ON.
If you intend to use a set-point between 7 and 16 bar, set DS_B5 at ON.
If you intend to use pressure switches, set DS_B7 at OFF.
ENGLISH
Figure 50: System status in KIWA mode
Figure 51: Dip switches for KIWA pressure boosting
Figure 52: enabling P1 and P2
97
buttons on the pumps P1 and P2. As

Advertenties

loading