Figure 39: System status in configurations: A with only depth sensor, B: depth sensor and floats, C depth sensor and level probes
7.10
Setting the Ebox with dip switches
If the Ebox is provided with a display, it is recommended to use the display for configuration. Otherwise it is possible to use the dip
switches inside the panel and set them as shown in Figure 40 Setting dip switches for drainage.
7.11
Activation of the set
To activate the set it is necessary to enable the pumps. During the first configuration, for safety's sake, the pumps are
disabled and are OFF. To change to automatic mode, just briefly press the
shown in Figure 41.
The following modifications may be made during configuration:
If you want the pumps to be exchanged every 24 hours and not at each restart, set DS_A2 at ON.
•
If you do not want protection against too rapid restarts, set DS_A3 at OFF.
•
If you do not want to use the pump P1 set DS_A7 at ON.
•
If you do not want to use the pump P2 set DS_A8 at ON.
•
If level probes are used and not floats, set DS_B4 at ON
•
If a depth sensor is used, set DS_B7 at ON and position DS_B5 according to the desired scale.
•
7.12
Regulating the rated current of the pumps (Imax) and the pump starting and stopping levels (only with depth sensor
connected)
With a straight tip screwdriver, position the indices in the centre of the graduated scales, as shown, so that:
Imax indicates the rated current of the installed pumps, which you can find on the pump data plate.
•
ENGLISH
Figure 40: Setting the Drainage dip switches
Figure 41: Enabling P1 and P2.
91
buttons on the pumps P1 and P2. As