The following modifications may be made during configuration:
• If you want the pumps to be exchanged every 24 hours and not at each restart, set DS_A2 at ON.
• If you do not want protection against too rapid restarts, set DS_A3 at OFF.
• If you do not want to use the pump P1 set DS_A7 at ON.
• If you do not want to use the pump P2 set DS_A8 at ON.
• If level probes are used and not floats, set DS_B4 at OFF
• If a depth sensor is used, set DS_B7 at ON and position DS_B5 according to the desired scale.
6.11
Activation of the set
To activate the set it is necessary to enable the pumps. During the first configuration, for safety's sake, the pumps are
disabled and are OFF. To change to automatic mode, just briefly press the
shown in Figure 28.
6.12
Regulating the rated current of the pumps (Imax) and the pump starting and stopping levels (only with depth sensor
connected)
With a straight tip screwdriver, position the indices in the centre of the graduated scales, shown, so that:
• Imax indicates the rated current of the installed pumps, which you can find on the pump data plate.
• SP represents the maximum level in the tank (LMAX) that you want the water to reach during normal operation.
• DP represents the minimum level in the tank (LMIN) that you want the water to reach during normal operation. DP is
expressed as a percentage of SP.
Attention, SP and DP have significance only if a depth sensor is used. For their meaning, refer to Figure 30. The scale
changing label 0-3m/2-5m must be applied on SP.
ENGLISH
Figure 27: Setting the filling dip switches
Figure 28: Enabling P1 and P2.
Figure 29: Regulating the rated current SP and DP
84
buttons on the pumps P1 and P2. As