ENGLISH
Parameters with local significance
These are parameters that can be divided among the various devices and in some cases it is necessary for them to be different. For these
parameters it is not allowed to align the configuration automatically among the various devices. For example, in the case of manual assignment
of the addresses, these must absolutely be different one from the other. List of parameters with local significance for the device.
• BK Brightness
• TK Backlight switch-on time
• RI Revs/min in manual mode
• IC Reserve configuration
• RF Reset fault and warning
Sensitive parameters
These are parameters which must necessarily be aligned over the whole chain for adjustment reasons.
List of sensitive parameters:
• SP Setpoint pressure
• RP Pressure decrease to restart
• ET Max. exchange time
• AY Anticycling
• NC Number of simultaneous devices
• TB Dry run time
• T1 Switch-off time after low pressure signal
• T2 Switch-off time
• GI Integral gain
• GP Proportional gain
• OD Type of system
• PW Change password
Automatic alignment of sensitive parameters
When a multipump system is detected, the compatibility of the set parameters is checked. If the sensitive parameters are not aligned among all
the devices, a message appears on the display of each device asking whether you want to propagate the configuration of that particular device to
the whole system. If you accept, the sensitive parameters of the device on which you answered the question will be distributed to all the devices
in the chain. If there are configurations that are not compatible with the system, these devices are not allowed to propagate their configuration.
During normal operation, changing a sensitive parameter of a device results in the automatic alignment of the parameter on all the other devices
without asking for confirmation.
NOTE: The automatic alignment of the sensitive parameters has no effect on all the other types of parameters. In the particular case of inserting
a device with factory settings in the chain (a device replacing an existing one or a device on which the factory configuration has been restored), if
the present configurations with the exception of the factory configurations are compatible, the device with factory configuration automatically
assumes the sensitive parameters of the chain.
Parameters with optional alignment
These are parameters for which it is tolerated that they may not be aligned among the various devices. At each change of these parameters, when
you press SET or MODE, you are asked if you want to propagate the change to the entire communication chain. In this way, if all elements of the
chain are the same, it avoids setting the same data on all the devices.
List of parameters with optional alignment:
• LA Language
• MS Measuring system
• AE Anti-blocking
• AF Anti-Freeze
• RM Maximum speed
9.3.6 - First start of the multipump system
Make the hydraulic and electrical connections of the whole system as described in chapter 2 and in par 3.
Switch on the devices and create the associations as described in paragraph 5.5.4 - AS: Association of devices..
9.3.7 - Multipump adjustment
When a multipump system is switched on, the addresses are automatically assigned and an algorithm selects one device as the adjustment
leader. The leader decides the speed and starting order of each device in the chain. The adjustment mode is sequential (the devices start one at
a time). When starting conditions occur, the first device starts, when it has reached maximum speed the next one starts, and then the others in
sequence. The starting order is not necessarily in ascending order according to the machine address, but it depends on the working hours done,
see 5.6.8 - ET: Max. switching time.