NC-foutmeldingen | Lijst met NC-foutmeldingen
Foutnummer
237-13808
237-13809
237-1380A
237-1380B
HEIDENHAIN | TNC7 | TNCguide | 01/2022
Beschrijving
Error message
13808 UM (FS.B): Herconfiguratie van parameters (PAE) niet
mogelijk %1
Cause of error
- Safety-relevant parameters of the inverter were changed
(delayTimeSTOatSS0/SS1, delayTimeSBCatSS0/SS1 or
driveOffGroup)
Error correction
- Restart the control in order to apply the new parameters
Error message
13809 UM (FS.B): Inschakelgereedheid ontbr. %1 1:%4 2:%5
3:%6 4:%7 5:%8
Cause of error
- The conditions for the switch-on readiness of the UM are
not given:
-- Info1 = 1: No valid configuration received for this axis
-- Info2 = 1: SS0 stop reaction active for this axis
-- Info3 = 1: Self-test for this axis has not yet run without
error
-- Info4 = 1: STEST.PERMIT set as release for the UM self-
test
-- Info5 = 1: Restart prevented due to the previous SS0 and
SS1F
Error correction
Error message
1380A UM (FS.B): CRC-fout bij PAE-communicatie %1 (nom:
%4,act:%5)
Cause of error
- Checksum (CRC) in cyclic communication with PAE is
faulty.
Error correction
- Inform your service agency
Error message
1380B UM (FS.B): Telegramteller PAE-communicatie %1
nom:%4 act:%5
Cause of error
- Telegram counter in cyclic communication with PAE is
faulty.
Error correction
- Inform your service agency