Foutnummer
239-0004
239-0007
239-000A
239-000C
239-000D
2864
Beschrijving
Error message
4 CC-FSUC: spanningsfout CC%2 %1
5 MC-FSUC: spanningsfout
6 UM-FSUC: spanningsfout CC%2 %1 %10
Cause of error
Voltage monitoring reports an error.
Error correction
- Check the voltage supply of the affected units ("24 V"
status LED on the unit)
- Inform your service agency
Error message
7 CC-FSUC: temperatuurfout CC%2 %1 (temperatuur: %6,%7
°C)
8 MC-FSUC: temperatuurfout (temperatuur: %6,%7 °C)
Cause of error
Temperature monitoring reports an error.
Error correction
- Check the temperature in the electrical cabinet
- Inform your service agency
Error message
A CC-FSUC: parametrisering mislukt CC%2 %1
Cause of error
The FS microcontroller received invalid parameter data.
Error correction
- Generate the service file
- Inform your service agency
Error message
C UM-FSUC: FS-parameter inconsistent CC%2 %1 %10
Cause of error
The FS microcontroller received inconsistent parameter
data.
Error correction
- Generate the service file
- Inform your service agency
Error message
D CC-FSUC: cyclische communicatie uitgevallen CC%2 %1
Cause of error
Cyclic communication between the MC and CC FS micro-
controller failed.
Error correction
- Generate the service file
- Inform your service agency
NC-foutmeldingen | Lijst met NC-foutmeldingen
HEIDENHAIN | TNC7 | TNCguide | 01/2022