Download Print deze pagina

Sew Eurodrive MOVIDRIVE compact MCF A Technische Handleiding pagina 69

Advertenties

Par. Naam
Omschakelbare par.
parameterset 1
3__
MOTOR PARAMETERS
30_
Limits 1
300/ Start/stop speed 1
301/ Minimum speed 1
302/ Maximum speed 1
303/ Current limit 1
304
Torque limit
32_
Motor compensation 1 (asynchr.)
Automatic
320/
adjustment 1
321
Boost 1
322
IxR-compensation 1
323
Premagnetizing time 1
324
Slip compensation 1
34_
Motor protection
340
Motor protection 1
341
Cooling type 1
35_
Direction of rotation of the motor
Reversal direction of rota-
350
tion 1
360
Startup
4__
REFERENCE SIGNALS
40_
Speed reference signal
400
Speed reference value
401
Hysteresis
402
Deceleration time
403
Signal = "1" if:
41_
Speed window signal
410
Window center
411
Range width
412
Deceleration time
413
Signal = "1" if:
42_
Speed setpoint/actual value comparison
420
Hysteresis
421
Deceleration time
422
Signal = "1" if:
43_
Current reference signal
430
Current reference value
431
Hysteresis
432
Deceleration time
433
Signal = "1" if:
44_
Imax signal
440
Hysteresis
441
Deceleration time
442
Signal = "1" if:
Technische handleiding – MOVIDRIVE
Instelbereik
After
Fabrieksinstelling
startup
0...60...150 rpm
0...60...5500 rpm
0...1500...5500 rpm
0...150 % I
nom
0...150 %
ON / OFF
0...100 %
0...100 %
0...0,1...2 s
0...500 rpm
OFF / ON ASYNCHRO-
NOUS / ON SERVO
FAN COOLED /
FORCED COOLING
ON / OFF
YES / NO
0...1500...5000 rpm
0...100...500 rpm
0...1...9 s
n < n
/ n > n
ref
ref
0...1500...5000 rpm
0...5000 rpm
0...1...9 s
INSIDE / OUTSIDE
1...100...300 rpm
0...1...9 s
n <> n
/ n = n
setp
setp
0...100...150 % I
nom
0...5...30 % I
nom
0...1...9 s
I < I
/ I > I
ref
ref
0...5...50 % I
nom
0...1...9 s
I = I
/ I < I
max
max
®
compact MCF/MCV/MCS4_A
Inbedrijfstelling
Complete parameterlijst
Instelbereik
Par. Naam
Fabrieksinstelling
parameterset 2
31_ Limits 2
310 Start/stop speed 2
0...60...150 rpm
311 Minimum speed 2
0...60...5500 rpm
312 Maximum speed 2
0...1500...5500 rpm
313 Current limit 2
0...150 % I
33_ Motor compensation 2 (asynchr.)
Automatic
330
ON / OFF
adjustment 2
331 Boost 2
0...100 %
332 IxR-compensation 2
0...100 %
333 Premagnetizing time 2 0...0,1...2 s
334 Slip compensation 2
0...500 rpm
OFF / ON ASYNCHRO-
342 Motor protection 2
NOUS / ON SERVO
FAN COOLED /
343 Cooling type 2
FORCED COOLING
Reversal direction of
351
ON / OFF
rotation 2
Alleen beschikbaar in DBG11B, niet in MOVITOOLS
I
5
0 0
After
startup
nom
®
.
69

Advertenties

loading

Deze handleiding is ook geschikt voor:

Movidrive compact mcv aMovidrive compact mcs4 a