4.1.10 [10] Inputs/Outputs
All outputs are monitored for wire breaks. For this reason, operating voltage is applied to open
output with a high impedance. The function of these outputs can be checked only when they
are under load.
Haube (housing)
diverse
autost.
alarm
oilpress.
temperat.
gen. D+
ropeStart
© ehb Errors expected.
Operating Instructions
The housing input can be programmed as " NC, NO or w.out (without)." query.
If one of the SpeedHC_Pin9 or SpeedPC_Pin9 output functions is used, this
menu option must be set to "Without".
The Miscellaneous input can be programmed as " NC, NO or w.out (without)."
query.
The Autostart input can be programmed as switch, tip switch or tip switch SS.
For this purpose, the function ON or ON_15 must be set in [6] Autostart.
Switch: A plus signal at Pin 7 starts the engine. When the switch
opens, the engine stops.
Tip switch: A plus signal at Pin 7 starts the engine. When the contact
opens, the engine stops. The engine is stopped with the External Stop
input, the ignition starter switch or pressing the SET key.
Tip switch SS (current surge): A plus signal at Pin 7 starts the en-
gine. Another plus signal at Pin 7 stops the engine.
The Alarm output can be programmed as "duration", "interval" or "w.out" func-
tion.
The input for monitoring the engine oil pressure can be programmed as sen-
sor, NC, NO or w.out (without).query.
The input for monitoring the engine temperature can be programmed as sen-
sor, NC, NO or w.out (without).query.
The monitoring of the generator with the D+ signal can be programmed as
"With" or "Without" query.
The monitoring of the cable pull can be programmed as "With" or "Without"
query. The changed starting conditions in a start with cable pull compared to a
start with ignition starter switch is automatically taken into account by the con-
troller.