HMCflex
4.1.10 [10] Inputs/Outputs
All outputs are monitored for wire breaks. For this reason, operating voltage is applied to open
output with a high impedance. The function of these outputs can be checked only when they
are under load.
Haube (housing)
diverse
autost.
alarm
oilpress.
temperat.
gen. D+
ropeStart
© ehb Errors expected.
Operating Instructions
The housing input can be programmed as " NC, NO or w.out (without)." query.
If one of the SpeedHC_Pin9 or SpeedPC_Pin9 output functions is used, this
menu option must be set to "Without".
The Miscellaneous input can be programmed as " NC, NO or w.out (without)."
query.
The Autostart input can be programmed as switch, tip switch or tip switch SS.
For this purpose, the function ON or ON_15 must be set in [6] Autostart.
Switch: A plus signal at Pin 7 starts the engine. When the switch
•
opens, the engine stops.
Tip switch: A plus signal at Pin 7 starts the engine. When the contact
•
opens, the engine stops. The engine is stopped with the External Stop
input, the ignition starter switch or pressing the SET key.
Tip switch SS (current surge): A plus signal at Pin 7 starts the en-
•
gine. Another plus signal at Pin 7 stops the engine.
The Alarm output can be programmed as "duration", "interval" or "w.out" func-
tion.
The input for monitoring the engine oil pressure can be programmed as sen-
sor, NC, NO or w.out (without).query.
The input for monitoring the engine temperature can be programmed as sen-
sor, NC, NO or w.out (without).query.
The monitoring of the generator with the D+ signal can be programmed as
"With" or "Without" query.
The monitoring of the cable pull can be programmed as "With" or "Without"
query. The changed starting conditions in a start with cable pull compared to a
start with ignition starter switch is automatically taken into account by the con-
troller.