4. Explanations to the adjustable parameters
4.1 [1] Settings
Parameter
4.1.1 [1] Language
Language
4.1.2 [2] Sensors
Temperature
Oil pressure
Impulses/rotation
4.1.3 [3] High-power output
OFF
ETR-HC
ETR-PC
ETR-PC+3s
ETS-HC
ETS-PC
IG.15
Glow
Alarm
© ehb Errors expected.
Operating Instructions
Explanations
You can select between German, English and French (subject to change).
The HMCflex unit can be factory-set to standard temperature sensors. For this
purpose, the Sensor type must be selected as the temperature monitoring type
under [10] Inputs/Outputs. This menu item is not displayed for the types N.C.,
N.O. or Without.
The HMCflex unit can be factory-set to standard oil pressure sensors. For this
purpose, the Sensor type must be selected as the oil pressure monitoring type
under [10] Inputs/Outputs. This menu item is not displayed for the types N.C.,
N.O. or Without.
Enter the number of impulses per rotation from the pulse generator or the
number of pole pairs of the generator including the transmission ratio. See also
chapter 5.2 for further details.
The selected output pin of the D plug is switched off.
The selected output pin of the D plug has the function of a Operating sole-
noid ETR excitation winding: An operating solenoid (ETR – Energise To
Run) is defined as a lifting magnet releasing the fuel supply when under power.
This magnet must be switched on during engine operation.
The selected output pin of the D plug has the function of a Operating sole-
noid ETR pull-in winding: Short activation for approx. 0.5 seconds to engage
the operating solenoid.
The selected output pin of the D plug has the function of a Operating sole-
noid ETR pull-in winding: The output is activated with the starter and remains
active for another 3 seconds after the starter is switched off. Specifically for
HATZ engines
The selected output pin of the D plug has the function of a Stopping sole-
noid ETS excitation winding: A stopping solenoid (ETS - energised to stop)
is defined as a lifting magnet requiring voltage to stop the engine.
The selected output pin of the D plug has the function of a Stopping sole-
noid ETS pull-in winding: Short activation for approx. 0.5 seconds to engage
the stopping solenoid.
The selected output pin of the D plug has the function of a switched output
KL.15 of the HMCflex ignition starter switch. After an external stop signal at Pin
9, it is deactivated even when the HMCflex ignition starter switch is in position
1.
The selected output pin of the D plug has the function of a pre-glow output is
active during pre-, by- and after-glowing.
The selected output pin of the D plug has the function of an alarm output that is
Version 2.9.4