4.1.9 [9] Limit values
oil min
temp. max
disengage
min.speed
max.speed
overvolt.
24/40
Operating Instructions
suppressed by the controller. Upon expiry of the set time, the alarm pro-
grammed under [7] is triggered.
This setting specifies the time for the speed to be below minimum value to be
suppressed by the controller. Upon expiry of the set time, the alarm pro-
grammed under [7] is triggered.
This setting specifies the time for the speed to be above maximum value to be
suppressed by the controller. Upon expiry of the set time, the alarm pro-
grammed under [7] is triggered.
Is an additional fault time for the Miscellaneous input. This setting specifies the
time for a signal active at the Miscellaneous input to be suppressed by the
controller immediately after starting. Upon expiry of this time, the standard
fault time for Miscellaneous will apply. Example: Water pressure switch on
Miscellaneous. This is the time required by a water pump to draw in ground
water and to build water pressure.
This setting specifies the time for an overvoltage to be applied to the controller
before it automatically shuts down to protect itself and the engine components.
For example, a load dump triggered by a battery isolation. "error: F.Ue.Sp."
message
This setting specifies the time for the speed signal missing during automatic
start for example, before the controller shuts down and returns a fault. "error:
KlW.Riss" message
The sleep mode function is made for reducing the power consumtion of the
HMCflex. Is this function active, after sleeptime timeout Display and all outputs
are switched off.
Setting the limit value for minimum oil pressure. If the pressure drops below the
programmed value, the alarm programmed under [7] is triggered. For this pur-
pose, the Sensor type must be selected as the oil pressure monitoring type
under [10] Inputs/Outputs. This menu item is not displayed for the types NC,
NO or w.out (without).
Setting the limit value for maximum engine temperature. If the temperature
rises above the programmed value, the alarm programmed under [7] is trig-
gered. For this purpose, the Sensor type must be selected as the temperature
monitoring type under [10] Inputs/Outputs. This menu item is not displayed for
the types NC, NO or w.out (without).
Setting the limit value for start speed. If the start speed is exceeded the starter
output KL.50F is deactivated. If the starting speed cannot be reached, the
alarm programmed under [7] is triggered.
Setting a lower engine speed. If the speed drops below this value, the alarm
programmed under [7] is triggered.
Setting an upper engine speed. If the speed exceeds this value, the alarm pro-
grammed under [7] is triggered.
Setting a maximum overvoltage permitted at the controller. If this voltage is
exceeded due to, for example, a load dump caused by battery isolation, the
controller protects itself by shutting down and returns a fault.
Versoin 2.9.4
HMCflex
© ehb Errors expected.