4.1.8 [8] Fault times
oilpress.
temp. max
gen. D+
housing (Haube)
© ehb Errors expected.
Operating Instructions
The load voltage monitoring can be programmed to shut down (emergency off),
to warn (alarm), without monitoring (without) or as shut-down with run-on time
(CDown). "error: gen. D+ " message
The start speed monitoring can be programmed to shut down (emergency off),
to warn (alarm), without monitoring (without) or as shut-down with run-on time
(CDown). "error: NoSpeed" message
The underspeed monitoring can be programmed to shut down (emergency off),
to warn (alarm), without monitoring (without) or as shut-down with run-on time
(CDown). "error: lowSpeed" message
The overspeed monitoring can be programmed to shut down (emergency off),
to warn (alarm), without monitoring (without) or as shut-down with run-on time
(CDown). "error: maxSpeed" message
The Miscellaneous input monitoring can be programmed to shut down (emer-
gency off), to warn (alarm), without monitoring (without) or as shut-down with
run-on time (CDown). "error: Haube" message
The monitoring of the autostart process with number of failed attempts can be
programmed to shut down (emergency off), to warn (alarm), without monitoring
(without) or as shut-down with run-on time (CDown). "error: Autstrt" message
The monitoring of the Kl.W process with number of failed attempts can be pro-
grammed to shut down (emergency off), to warn (alarm), without monitoring
(without) or as shut-down with run-on time (CDown). "error :KlW.Riss".
The sleep mode function is made for reducing the power consumtion of the
HMCflex.
off: If the key switch is in position 1 (ignition) the display and activate outputs
are always switched on.
idle: After sleeptime timeout Display and activate outputs are switched down.
Output function KL.15* and CANbus function are still working.
pwrdn: After sleeptime timeout Display and all outputs are switched off, output
function KL.15* and CANbus too.
This setting specifies the time for an active oil pressure fault to be suppressed
by the controller. Upon expiry of the set time, the alarm programmed under [7]
is triggered.
This setting specifies the time for an active temperature fault to be suppressed
by the controller. Upon expiry of the set time, the alarm programmed under [7]
is triggered.
This setting specifies the time for an active generator fault to be suppressed by
the controller. Upon expiry of the set time, the alarm programmed under [7] is
triggered.
This setting specifies the time for a signal active at the housing input to be