HMCflex
Feed forward ETS
Feed back ETR
Feed back ETS
IG.15*
Fuel Pump
air fan
SpeedMagTime
CDownTime
4.1.4 [4] Glow times
Temp1
Temp2
Time1 (Temp1)
Time2 (Temp2)
© ehb Errors expected.
Operating Instructions
This output is inactive in the chopper function when the speed is within the
operating range. (chopper automatic = ON)
This output is active only a short time in the chopper function when the speed
drops below the lower limit. This time can be set in the Set-up menu [6] chop-
per under the "Time push" menu option.
This output is inactive for a short time in the chopper function when the speed
drops below the lower limit. This time can be set in the Set-up menu [6] chop-
per under the "Time push" menu option.
The selected output pin of the 19-pole D plug has the function of a switched
output KL.15 of the HMCflex ignition starter switch. This function remains ac-
tive after an external stop signal at Pin 9. The output is deactivated if the igni-
tion starter switch is set to Position 0 (even when the Autostart function is set to
ON!). Example: Operation of a remote control supplied by the KL_15* output.
Function on ON_15 and input Autostart as tip switch.
The selected output pin of the 19-pole D plug has the function to operate a fuel
supply pump. This output become active when the controller is switched on.
The output is switched off after a time-out of currently approx. 120 seconds
without starting and immediately after an alarm shut-down or external stop.
The selected output pin of the 19-pole D plug has the function of a fan or venti-
lation control with two temperature limit values of the temperature measured at
Pin 3. To be set with ehbTools using ...
- Parameter 169 for min. temperature between 0-255°C (default
- Parameter 170 for max. temperature between 0-255°C (default
This time affects the SpeedHC or SpeedPC output functions. After a successful
start and expiry of this speed magnet time, the two outputs are activated as
follows:
SpeedHC: The selected output pin of the D plug has the function of a speed-
adjusting solenoid excitation winding: It is automatically activated after the
SpeedMagTime has expired when the engine is running.
SpeedPC: The selected output pin of the D plug has the function of a speed-
adjusting solenoid pull-out winding: It is automatically activated for approx. 0.5
seconds after the SpeedMagTime has expired when the engine is running.
Setting for the run-on or cooling time of the engine. To be set between 0 and
15 minutes.
Specifies the hotter value for the temperature-dependent pre-glow process.
See also chapter 6.2, Temperature-dependent pre-glow.
Specifies the colder value for the temperature-dependent pre-glow process.
See also chapter 6.2, Temperature-dependent pre-glow.
Specifies the glow time for the hotter Temp1 value in seconds. See also chap-
ter 6.2, Temperature-dependent pre-glow.
Specifies the glow time for the colder Temp2 value in seconds. See also chap-
ter 6.2, Temperature-dependent pre-glow.
Version 2.9.4
85°C)
95°C)
21/40