13.1.1 Connection
961665_02
Biral AG
CH-3110 Münsingen
BIM Modbus RTU (CIM 200)
Biral interface module for communication via a Modbus RTU network.
The CIM 200 has the appropriate terminals for connection to a Modbus net-
work. The parity and stop bits used to select the transmission speed and line
termination are set using DIP switches. Two hexadecimal rotary switches are
used to set the Modbus address. The current communication status of the
CIM 200 is indicated by two LEDs. One LED is used to indicate that the pump
is correctly connected to the network and the other shows the communica-
tion status on the Modbus network.
BIM BACnet MS/TP (CIM 300)
Biral interface module for communication via a BACnet MS/TP network.
The CIM 300 has the appropriate terminals for connection to a BACnet MS/
TP network. The transmission speed and line termination as well as the cus-
tomer-specific device object instance number are set using DIP switches.
Two hexadecimal rotary switches are used to set the BACnet address. The
current communication status of the CIM 300 is indicated by two LEDs. One
LED is used to indicate that the pump is correctly connected to the network
and the other shows the communication status on the BACnet network.
A
B
10
10
Dokumentstatus:
Massstab
1:3
Freigegeben
Format:
29.03.2022
A4
Erstelldatum
29.03.2022
PDM_Nr:
212997
Zeichnungsnummer
961665
Prepare the cable according to the figure. The
cable must be connected according to the
connection diagram, see "Additional module"
operating instructions.
Remarks:
Use shielded cables with a max. cable
cross-section of 1 mm².
– Area (A) cable stripped by 10 mm
– Area (B) with heat-shrink tubing
– Area (X) = 200 mm
– Install and connect the module
– Connect and configure the required
function, if necessary
sta
– Close cover