3. Carefully lower the pump head with the rotor shaft and impeller into the pump housing.
4. Replace the hex head bolts and tighten them crosswise. M8 = 25 Nm
5. Connect the pressure sensor's capillary tubes (see Section 4.4.3 "Differential pressure sensor
handling").
P1
P2

4.4.3 Differential pressure sensor handling

The pump has a built-in PI controller and a differential pressure sensor, which enables the feed
pressure to be regulated under constant pressure and proportional pressure operating modes. The
required set value for each operating mode can be set on the Biral control panel using keys. The
sensor is already installed ex works. If the motor or the pump head is rotated, the capillary tubes
must be routed again.
Remove the capillary tubes at the connection to the frequency inverter. After aligning the pump
head, the tubes must be rerouted. Take care not to overstretch the capillary tubes.
2
4
P2
P1
Werkstoff:
VivarA-S 65-340_A71
1
IL00003808_00
Werkstoff:
VivarA-S 65-340_A71
Pumpenkopf drehen
+
+2
DC out 24V
-
4-
out
73
P1
IL00003772_00
P2
3
Massstab
1:3
1:3
Format:
Zeichnungsnummer
Biral AG
IL00003808
CH-3110 Münsingen
+
Brown +2
Yellow 4-
Out
Green 73
White
Massstab
Dokumentstatus:
1:3
1:3
in Arbeit DS
Format:
A3
English
59
|
Dokumentstatus:
in Arbeit DS
A3
Erstelldatum
08.06.2020
sta
PDM_Nr:
205848
Änd. Ind.
00
A
Vers.
Rev.

Advertenties

Hoofdstukken

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

Vivara sVivara m

Inhoudsopgave