Montage der Pumpe
The motor must never lie below the horizontal plane or face downwards.
Biral AG
CH-3110 Münsingen
The arrows on the pump housing indicate the flow direction of the medium. The pump can be in-
stalled in horizontal or vertical piping. However, the motor must not face downwards. The bleeding
screw (LV) must always face upwards; the housing lid may have to be rotated.
LV
961684_00
Ersetzt durch:
Ersatz für:
Massstab
gezeichnet 17.02.2014
1:7
geprüft
19.02.2014
Freigabe
19.02.2014
PDM_Nr
TD-0019216
Zeichnungsnummer
961684
LV
The following points must also be observed to
ensure adequate motor and electronics cool-
ing:
– The minimum distance of 50 mm between
the fan cover and another fixed object must
be maintained.
– The temperature of the cooling air must not
exceed 40 °C.
– The cooling fins and the fan blade must be
kept clean.
– To prevent condensation on the electronics,
motors which are installed outdoors must
be shielded by suitable protection (not avail-
able as Biral accessories).