Praesideo 3.5 | Installation and User Instructions | ISO7240-16: 2007
Clause / Requirement
17 Tests
Clause / Requirement
18 Test report
Changed clauses
Clause / Requirement
4.3 Power supply
Power-supply equipment shall comply with the
requirements of ISO 7240-4 and may be internal or external
to the s.s.c.i.e. cabinet.
The power supply may be shared with that of the
emergency detection system.
Clause / Requirement
8 Fault-warning condition
8.5 Reset of fault indications
8.5.2 Following the completion of the reset process, the
indication of the correct functional conditions
corresponding to any received signals shall either remain or
be re-established within 100 s.
Clause / Requirement
9 Disabled condition - Optional function
9.3 Indication of specific disablements
9.3.4 If the indication is on an alphanumeric display that
cannot simultaneously indicate all of the disablements
because of its limited capacity, at least the following shall
apply.
b
Suppressed disablement indications shall be capable
of being displayed, independently of other indications,
by means of a manual operation at access level 1 or 2,
which interrogates only the disablement indications.
Bosch Security Systems | 2011-02
Compliance
All tests as asked for in the clauses of section 17 have been
carried out by an accredited certification body for
ISO7240-16 compliancy.
The Praesideo system has been found compliant to
ISO7240-16 and received a certification of compliancy.
Compliance
The tester must take care of documenting the testing
programme and the results of the tests in a test report that
at least contains the information as listed in clause 18.
Compliance
The installer must use power supplies and battery charging
equipment in accordance with ISO7240-4, with separate
wiring for mains (230Vac) and battery backup (48Vdc) from
the power supply to the Praesideo system.
The power supply equipment must be installed in a
separate cabinet, not shared with the Praesideo system,
unless the combination of the actual power supply
equipment and Praesideo system elements in the same
cabinet has been certified.
The content of the ISO7240-16 certification is subject to
change. The most recent version of this certificate can be
found on www.boschsecurity.com.
The network controller and all amplifiers are supplied with a
mains supply and DC backup supply (48V) input. Switch
over between the both takes place automatically, without
any interruption or status change other than the power
supply related indications.
The installer must ensure that the output voltages of the
power supply equipment do not exceed the specifications
of the mains and battery inputs of the connected Praesideo
equipment.
Compliance
If any individual fault is reset while it is not actually resolved
in the system, the Praesideo system will report the fault
again within 100 seconds. If all faults are reset in one
action, all individual faults that are not actually resolved in
the system are reported again within 100 seconds.
Compliance
Praesideo does not support the optional function disabled
condition. See 9.