Commands and Accessories
If not installed, safety devices with NC contacts must be jumpered at the COM terminals, or disabled by
modifying the parameters
KEY:
N.A. (Normally Open).
N.C. (Normally Closed).
CONTACT
13 (COR)
14
13 (COR)
14
16(+LAM)
15(COM)
17(+ES)
15(COM)
18(+24V)
15(COM)
20(SC)
19(COM)
20(SC)
19(COM)
22(FT2)
21(COM)
23(FT1)
21(COM)
24(COS2)
26(COM)
25(COS1)
26(COM)
,
,
,
,
and
DESCRIPTION
Output (potential free contact) for connecting courtesy light. 230V~ 100 W - 24V~/
3).
Error alert contact only, for:
• control unit in alarm / battery supply error (low battery);
•
The COR output operating mode is managed by parameter
The voltage level of the battery can be set via parameter
Input for connecting electric lock, 12V
The function of the electric lock is determined by parameter
Vmedia=12V
, Vmax=40V
Power feed for external devices; see table "PRODUCT TECHNICAL FEATURES"
Connection for gate open indicator lamp. 24V
The function of the indicator lamp is determined by parameter
Photocell test connection
Set the parameter
to enable the test function.
Each time a command is received, the control unit switches the photocells off and on to check
that the contact changes state correctly.
Power feeds for all external devices may be connected to reduce battery consumption (if batteries
are used). Set
or
WARNING! If contact 20 (SC) is used for the photocell test function or battery saving function, a
gate open indicator lamp cannot be connected.
Input (N.C. or 8.2 kOhm) for connecting photocells FT2
The photocells FT2
–
. Photocell FT2 disabled when gate is opening.
–
. Photocell FT2 disabled when gate is closing.
–
. The gate opens when an open command is received if photocell FT2 is obstructed.
–
. NC (normally closed) incoming contact.
If the photocells are not installed, jumper the terminals 21(COM) - 22(FT2) or set the parameters
and
.
WARNING! Use R90/F4ES, G90/F4ES or T90/F4S series photocells.
Input (N.C. or 8.2 kOhm) for connecting photocells FT1
The photocells FT1
–
. Photocell triggers only during gate closure. Photocell is ignored during gate opening.
–
. Movement is reversed if the photocell is triggered during gate closure.
–
. The gate opens when an open command is received if photocell FT1 is obstructed.
–
. NC (normally closed) incoming contact.
If the photocells are not installed, jumper the terminals 23(FT1) - 21(COM) or set the parameters
and
.
WARNING! Use R90/F4ES, G90/F4ES or T90/F4S series photocells.
Input (NC or 8 kOhm) for connecting sensing edge COS2.
–
. The sensing edge COS2 (NC contact) is disabled.
If the sensing edge is not installed, jumper the terminals 24(COS2) - 26(COM) or set the parameter
.
Input (NC or 8 kOhm) for connecting sensing edge COS1
–
. If the sensing edge COS1 (NC contact) is enabled, the gate always reverses.
If the sensing edge is not installed, jumper the terminals 25(COS1) - 26(COM) or set the
parameter
.
.
(24V
- duty cycle
.
max. 15 W
; see table "PRODUCT TECHNICAL FEATURES"
.
.
.
-
.
.
,