7.3
TECHNICAL FEATURES
EN
• The chimney flue must be sealed from fumes.
• It must have a vertical run without narrowing. It must be realized with fume and condensation resistant
materials with thermal insulation and able to last against usual mechanical stresses.
• The stove must be spaced out from fuels or flammable materials with an air gap or with insulating materials.
Check the distance with the chimney manufacturer.
• The chimney entrance must be placed in the same room where the appliance is installed or otherwise in
the adjacent room and it must be provided with a solid and condensation collection chamber under the
entrance, accessible through the sealed metal gate.
• Auxiliary exhaust fans cannot be installed neither along the chimney nor on the chimney pot.
• The inner section of the chimney flue can be round (the best one) or square and the jointed sides must have
a minimum radius of 20 mm.
• The section dimension must be minimum Ø120 mm and maximum Ø180 mm.
• Made the efficiency of the chimney flue overhauled by an expert stove-repairer and if necessary cover the
chimney flue with materials in compliance with current regulations.
• The flue system must be placed on the roof.
• The chimney flue must be provided CE in accordance with EN 1443 regulation. Please find attached an
example of label:
6
LEGEND
Fig. 3 page 6
1
Height over the ridge of the roof = 0,5 mt
2
Roof inclination ≥ 10°
3
90°
4
Measured distance at 90° from the roof surface = 1,3 mt
It must be insulated to avoid condensation and to reduce fume cooling effects.
Fig. 3 - Inclined roof
Fig. 4 - Example of label
FAMILY