• Disengage the 4 screws at the corners of the panel using the
hex wrench provided with the accessory tool.
• Do not remove the screws, just disengage them from the thread
on the product body.
• Be careful not to drop the screws into the system
• Move the panel away, taking care not to pull on the signal
transmission cable
• Reposition the panel in its seat at the preferred angle taking
care not to pinch the cable.
• Tighten the 4 screws with the wrench
2.2.3 Loading Operation
Installation above head and below head
Figure 10
With reference to its position with respect to the water to be pumped, the
installation of the system may be defined "above head" or "below head". In
particular the installation is defined "above head" when the pump is placed
at a level higher than the water to be pumped (e.g. pump on the surface and
water in a well); vice versa it is "below head" when the pump is placed at a
level lower than the water to be pumped (e.g. overhead cistern and pump
below).
Installation "above head": with the aid of the accessory tool (Fig.3_point 5) or
with a screwdriver, remove the filling cap which, for the horizontal configura-
tion, is the one on Face F (Fig.1). Fill the system with clean water through the
loading door, taking care to let the air out. The quantity of water with which to
fill the system must be at least 1.5 litres. It is recommended to fit a non-return
valve at the end of the suction pipe (foot valve) so as to be able to fill it quickly
too during the loading operation. In this case the quantity of water necessary
for the loading operation will depend on the length of the suction pipe (1.5
litres + ...).
Installation "below head": if there are no check valves between the water
deposit and the system (or if they are open), it loads automatically as soon
GB
ENGLISH
Figure 11
68