Download Print deze pagina

DAB E.Sybox Gebruiks- En Onderhoudsaanwijzing pagina 96

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 226
GB
ENGLISH
When you are working with the auxiliary setpoint, to return to working with
setpoint SP, the input must not be active for at least 1 sec. The behaviour
of the function is summed up in Table 16.
When several auxiliary setpoint functions are configured at the same time
on different inputs, the system will show Pi when at least one function is
activated. For simultaneous activations, the pressure achieved will be the
lowest of those with the active input. The alarm is removed when no input
is activated.
auxiliary setpoint
Behaviour of the
Value of Para-
Input configu-
meter
ration
Ix
Active with high
signal on input
3
(NO)
Active with low
4
signal on input
(NC)
Table 16: Auxiliary setpoint
7.6.15.4 - Setting system disabling and fault reset
The signal that enables the system can be supplied to any input (for the
electrical connections refer to the control unit manual). The system
disabling function is obtained by setting the parameter Ix, relating to the
input to which the signal to be used to disable the system is connected,
on one of the values shown in Table 18.
When the function is active, the system shuts down completely and the
F3 symbol appears on the main page.
When several system disabling functions are configured at the same time
93
function depending on Ix and on the
input
Input status
Operation
i-th auxiliary
Absent
setpoint not active
i-th auxiliary
Present
setpoint active
i-th auxiliary
Absent
setpoint active
i-th auxiliary
Present
setpoint not active
on different inputs, the system will indicate F3 when at least one function
is activated and will remove the alarm when none is activated.
For the system to work with the disable function, the input must be active
for at least 1 sec.
When the system is disabled, for the function to be deactivated (re-
enabling the system), the input must not be active for at least 1 sec. The
behaviour of the function is summed up in Table 17.
When several disable functions are configured at the same time on
different inputs, the system will show F3 when at least one function is
activated. The alarm is removed when no input is activated.
This function also allows the resetting of any faults present, see table 18.
Behaviour of the system disabling and fault reset function depending on Ix
Shown on
display
Value of
Input configu-
Parameter
None
Ix
Active with high
Px
signal on input
5
Px
Active with low
None
6
signal on input
Active with high
signal on input
7
Active with low
8
signal on input
Active with high
signal on input
9
and on the input
Input status
Operation
ration
Absent
Motor enabled
(NO)
Present
Motor disabled
Absent
Motor disabled
Present
Motor enabled
(NC)
Absent
Motor enabled
Motor disabled +
(NO)
Present
fault reset
Motor disabled +
Absent
fault reset
(NC)
Present
Motor enabled
Absent
Motor enabled
(NO)
Present
Fault reset
Table 17: Disabling system restore and fault
Shown on
display
None
F3
F3
None
None
F3
F3
None
None
None

Advertenties

loading

Deze handleiding is ook geschikt voor:

E.sybox 30/50