ID
Name
CF
Configuration
bU
Bus Protocol
Ad
Unit Address
Fa
Fancoil Type
Po
Position of installation
Ambient temperature
co
compensation
bU – BUS Protocol:
Modicon Modbus" ASCII type
Ad - Unit Address:
In the event of need, it is possible to change the unit address.
The value must be entered in hexadecimal format.
The table below indicates the conversion of the first 80 numbers from decimal to hexadecimal format, for
the next numbers, please refer to the specific tables which can be consulted on the web.
Decimal
1
2
3
4
5
6
7
8
9
10
11
12
EN - 16
Description
Configure the type of control
Allows to configure the type of bus used
Allows to set/change the unit address
(insert the value in hexadecimal format)
A l l o w s t o s e l e c t t h e t y p e o f
fancoil
Allows to select where the fancoil has
been installed
Allows to choose the compensation
value to use
Baudrate = 9600
data bits = 7
stop bit = 1
equality = yes
Hexadecimal
01
02
03
04
05
06
07
08
09
0A
0B
0C
Permitted values
AU : Autonomous
rE : Remote
AS : ASCII
rt : RTU
00 -> FF (255)
_0: Without flap (200-1000)
_1: All versions
(1100-1400-1600)
_2: With flap (200-1000)
uP : roof installation
dO : floor installation
-5 : 5
Modicon Modbus RTU type
Baudrate = 9600
data bits = 8
stop bit = 1
equality = no