2.12.a - Assembly and connections for models with console and recess
Once the connection operations and possible configuration are complete, close the electric panel by means
of the previously removed screws.
Reposition the front panel taking care to connect the connector of the display.
Secure the front panel by means of the screws, then power the machine.
- When the unit is configured for remote control, the remote controller is disabled.
- It is not possible to control the flap from remote control.
- In this mode, the air probe installed on board the fan coil is ignored.
2.13 - CONNECTION WITH SIOS CONTROL
- Connect the cables coming from the "A B" connection of SIOS CONTROL
with the respective wires on the mammoth connected to the panel lid, taking
care to respect the polarity, connecting the farthest unit with the 120 Ohm
resistor supplied with the appliance.
- Enable Autonomous configuration (paragraph "2.14", configuration parameter
"CF").
- Set the protocol type ASCII if SIOS CONTROL envisages B0863 or RTU if
SIOS CONTROL does not envisage B0863 (paragraph "2.14", configuration
parameter "bU").
- Set the address, each appliance must have an address different from all the
other units connected to the same BUS (paragraph "2.14", configuration pa-
rameter "Ad").
- As regards mounting of the connections, proceed by following the indications
described in the previous paragraphs.
2.14 - BOARD SOFTWARE CONFIGURATION
Work as follows:
a. Connect power supply, then ensure that the latter is set to any mode except for stand-by.
b. On the control panel, simultaneously press the key "
until an acoustic signal is emitted.
c. The display shows the reference to the parameter
d. Scroll using the key "
e. Press the key "
CF -> ...
f. Press key "
" (T2) to access the value
g. Release and press key "
h. Press key "
" or "
i. Press key "
" (T3) to confirm the value
j. Press key "
" (T3) to exit the configuration or wait 20 seconds.
Quit and give power voltage to the system to start the unit under the new config-
uration.
" or "
" (T1) until you select the desired parameter
" or "
" (T1) to scroll the list of parameters: CF -> bU -> Ad -> Fa -> Po -> co ->
" (T2) for more than 3 seconds to change the value (Display blinking)
" (T1) to scroll the possible values of the parameters
" (T2) and "
" (T1) for at least 5 seconds,
EN - 15
Bi2 Air TR