Samenvatting van Inhoud voor Wilo Yonos GIGA2.0-I/-D
Pagina 1
Pioneering for You Wilo-Yonos GIGA2.0-I/-D de Einbau- und Betriebsanleitung Notice de montage et de mise en service en Installation and operating instructions nl Inbouw- en bedieningsvoorschriften · 2227301 • Ed.02/2023-08...
Pagina 2
Yonos GIGA2.0-I https://qr.wilo.com/276 Yonos GIGA2.0-D https://qr.wilo.com/277...
Pagina 3
Fig. I Yonos GIGA2.0-I/-D DN 32 ... DN 80 (0,37 ... 7,5 kW)
Pagina 7
Deutsch ........................... English ..........................Français ........................... Nederlands ........................
Pagina 8
12.7 Anwendung und Funktion der Analogeingänge AI1 und Technische Daten ............... 19 AI2 .................. 75 Lieferumfang ............... 21 12.8 Anwendung und Funktion der Wilo Net-Schnittstelle... 82 Zubehör ................ 21 12.9 Anwendung und Funktion der CIF-Module...... 83 5 Transport und Lagerung ............ 22 13 Display-Einstellungen .............. 83...
Pagina 9
19 Ersatzteile ................ 111 20 Entsorgung................ 111 20.1 Öle und Schmierstoffe ............ 112 20.2 Information zur Sammlung von gebrauchten Elektro- und Elektronikprodukten.......... 112 Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 10
Schadenersatz. Alle Rechte vorbehalten. Vorbehalt der Änderung Wilo behält sich vor, die genannten Daten ohne Ankündigung zu ändern und übernimmt keine Gewähr für technische Ungenauigkeiten und/oder Auslassungen. Die verwendeten Abbildungen können vom Original abweichen und dienen der exemplarischen Darstellung des Produkts.
Pagina 11
In den lokal gültigen Unfallverhütungsvorschriften unterrichtet sein. • Die Einbau- und Betriebsanleitung gelesen und verstanden ha- ben. Das Personal muss die folgenden Qualifikationen haben: • Elektrische Arbeiten: Eine Elektrofachkraft muss die elektri- schen Arbeiten ausführen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 12
• Niemals Bedienelemente entfernen. • Führen Funkwellen (Bluetooth) zu Gefährdungen (z. B. im Kran- kenhaus) müssen diese, soweit sie am Installationsort nicht ge- wünscht oder untersagt sind, ausgeschaltet oder entfernt wer- den. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 13
• Allgemeinen Verhaltensrichtlinien, die für den Umgang mit elektri- schen Geräten gelten, befolgen! • Motor nicht öffnen! • Demontage und Montage des Rotors nur durch Wilo-Kundendienst durchführen lassen! Personen, die einen Herzschrittmacher tragen, dürfen solche Arbeiten nicht durchführen! HINWEIS Von den Magneten im Inneren des Motors geht keine Gefahr aus, solange der Motor komplett montiert ist.
Pagina 14
Gefährliche Bauteile (extrem kalt, extrem heiß, drehend usw.) mit einem bauseitigen Berührungsschutz ausstatten. • Leckagen gefährlicher Fördermedien (z. B. explosiv, giftig, heiß) so abführen, dass keine Gefährdung für Personen und die Um- welt entsteht. Nationale gesetzliche Bestimmungen einhalten. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 15
Jede darüber hinausgehende Verwendung gilt als Fehlgebrauch und führt zum Verlust jegli- cher Haftungsansprüche. Fehlgebrauch Die Betriebssicherheit des gelieferten Produkts ist nur bei bestimmungsgemäßer Verwen- dung entsprechend Kapitel „Bestimmungsgemäße Verwendung“ der Betriebsanleitung ge- Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 16
Befestigungsschrauben des Elektronikmodul-Unterteils, 4x Klemmringverschraubung der Druckmessleitung (Gehäuseseite), 2x Überwurfmutter der Klemmringverschraubung (Gehäuseseite), 2x Druckmessleitung, 2x Differenzdruckgeber (DDG) Überwurfmutter der Klemmringverschraubung (DDG-seitig), 2x Befestigungsschrauben des Motors, Hauptbefestigung, 4x 2x Hilfsbefestigungsschrauben Motoradapter für Elektronikmodul Motorgehäuse Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 17
Schützt vor rotierender Motorwelle (Nur DN 100, DN 125). Fig. 1: Übersicht Pumpe ternenfenster Schnittstelle Wilo- Optionale Schnittstelle Connectivity Inter- face Differenzdruckgeber 2 ... 10 V mit Kapillarrohranschlüssen an Flanschen der Saug- und Druckseite Tab. 2: Beschreibung der Pumpe Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 18
Die Hydraulikeinheit ist aufgrund der durchgehenden Motorwelle keine einbaufertige Bau- gruppe. Sie wird bei den meisten Wartungs- und Reparaturarbeiten zerlegt. Hinweise zu Wartungs- und Reparaturarbeiten siehe Kapitel „Wartung“ [” 101]. Einstecksatz Laufrad und Laterne bilden zusammen mit dem Motor den Einstecksatz (Fig. 4). Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 19
> +60 °C auf eine Dauer min./max. von 8 Wochen begrenzt. Temperatur bei Transport -30 °C ... +70 °C > +60 °C auf eine Dauer min./max. von 8 Wochen begrenzt. Relative Luftfeuchtigkeit < 95 %, nicht kondensierend Aufstellungshöhe max. 2000 m über Meeresspiegel Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 20
Leistung im leitungsgeführten Bereich unter ungünstigen Um- ständen bei einem Einsatz im Wohnbereich (C1) zu EMV-Auffälligkeiten kommen. In die- sem Fall bitte WILO SE kontaktieren, um gemeinsam eine schnelle und geeignete Abstell- maßnahme zu finden. Yonos GIGA2.0-I/-D ist im Sinne der EN 61000-3-2 ein professionelles Gerät.
Pagina 21
Leistungsaufnahme der Pumpe. Nur Gemische mit Korrosionsschutzinhibitoren ver- wenden. Zugehörige Herstellerangaben beachten! • Das Fördermedium muss sedimentfrei sein. • Bei Verwendung anderer Medien ist die Freigabe durch Wilo erforderlich. • Gemische mit einem Glykolanteil > 10 % beeinflussen die Δp‑v-Kennlinie und die Durchflussberechnung. •...
Pagina 22
Fremdkörper in das Pumpengehäuse gelangen. Um eine Riefenbildung an den Lagern und ein Festkleben zu vermeiden, die Pumpenwelle einmal wöchentlich mit einem Steckschlüssel drehen (siehe Fig. 5). Falls ein längerer Lagerungszeitraum erforderlich ist, bei Wilo erfragen, welche Konservie- rungsmaßnahmen durchzuführen sind. WARNUNG Verletzungsgefahr durch falschen Transport! Wird die Pumpe zu einem späteren Zeitpunkt erneut transportiert, muss...
Pagina 23
• Immer geeignete Hebemittel verwenden und Teile gegen Herabfallen sichern. • Niemals unter schwebenden Lasten aufhalten. • Bei Lagerung und Transport sowie vor allen Installations- und Monta- gearbeiten für eine sichere Lage und einen sicheren Stand der Pumpe sorgen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 24
• Allgemeinen Verhaltensrichtlinien, die für den Umgang mit elektri- schen Geräten gelten, befolgen! • Motor nicht öffnen! • Demontage und Montage des Rotors nur durch Wilo-Kundendienst durchführen lassen! Personen, die einen Herzschrittmacher tragen, dürfen solche Arbeiten nicht durchführen! GEFAHR...
Pagina 25
Die Pumpe darf nicht länger als 1 Minute ohne Durchfluss laufen. Durch den Energiestau entsteht Hitze, die Welle, Laufrad und Gleitringdichtung beschädigen kann. • Sicherstellen, dass der Mindestvolumenstrom Q nicht unterschritten wird. Überschlägige Berechnung von Q = 10 % x Q x Ist-Drehzahl / Max-Drehzahl max Pumpe Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 26
Die Entlüftung der Pumpe ist optimal gewährleistet, wenn das Entlüftungsventil nach oben zeigt (Fig. 9, Pos. 1). In dieser Position (0°) kann anfallendes Kondensat gezielt über vorhandene Bohrungen, Pum- penlaterne sowie Motor (Fig. 9, Pos. 2) abgeführt werden. Fig. 9: Zulässige Einbaulagen mit horizontaler Motorwelle Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 27
Durch Lösen der Schraube (Fig. I/III, Pos. 29, Fig. II, Pos. 10) das Halteblech des Diffe- renzdruckgebers (Fig. I, Pos. 13) vom Motorflansch lösen. Differenzdruckgeber (Fig. I, Pos. 8) mit Halteblech (Fig. I, Pos. 13) an den Druckmessleitungen (Fig. I, Pos. 7) hängen lassen. Anschlusskabel des Differenzdruckgebers im Elektronikmodul gegebenenfalls abklemmen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 28
Lage biegen. Dabei die Bereiche an den Klemmverschraubun- gen nicht verformen. Um eine optimale Führung der Druckmessleitungen zu erreichen, kann der Differenzdruckge- ber vom Halteblech (Fig. I, Pos. 13) getrennt, um 180° um die Längsachse gedreht und wieder montiert werden. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 29
10. Die Schrauben (Fig. II, Pos. 10 und Pos. 10a) lösen. 11. Laterne mit Zweiarmabzieher (Universalabzieher) von der Motorzentrierung lösen und von der Welle abziehen. Die Gleitringdichtung (Fig. I, Pos. 25) wird dabei mit entfernt. Ein Verkanten der Laterne vermeiden. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 30
Transportösen Fig. I, Pos. 30 Einstecksatz zu Fig. I, Pos. 29 Gleichmäßig über Pumpengehäuse Kreuz anziehen. für DN 32 ... DN 80 Einstecksatz zu Fig. II, Pos. 29 Gleichmäßig über Pumpengehäuse Fig. III, Pos. 29 Kreuz anziehen. für DN 100 ... DN 125 Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 31
• Immer geeignete Hebemittel verwenden und Teile gegen Herabfallen sichern. • Niemals unter schwebenden Lasten aufhalten. • Bei Lagerung und Transport sowie vor allen Installations- und Monta- gearbeiten für eine sichere Lage und einen sicheren Stand der Pumpe sorgen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 32
Pumpe einbauen. VORSICHT Sachschäden durch Turbinen und Generatorbetrieb! Ein Durchströmen der Pumpe in Fließrichtung oder entgegen der Fließ- richtung kann irreparable Schäden am Antrieb verursachen. Auf der Druckseite jeder Pumpe eine Rückschlagklappe einbauen! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 33
Isolierung) entstehen. Ein Weiterdrehen der Klemmringverschraubung um 1/4 Umdre- hung behebt die Undichtigkeit. Wenn nach dieser 1/4 Drehung noch immer eine Undichtigkeit vorliegt, nicht weiterdre- hen, sondern die Verschraubung austauschen. Fig. 13: Weiterdrehen der Klemmringverschraubung um 1/4 Umdrehung Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 34
Vorzeichen von Σ F und Σ M werden in der Kompensationsgleichung nicht berück- sichtigt. Einfluss von Werkstoff und Temperatur Die maximal zulässigen Kräfte und Momente gelten für den Grundwerkstoff Grauguss und für einen Temperaturausgangswert von 20 °C. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 35
Bei Doppelpumpen im Doppelpumpengehäuse ist die in Fließrichtung lin- ke Pumpe werkseitig als Hauptpumpe konfiguriert. Der Differenzdruck- geber ist an dieser Pumpe montiert. Das Buskommunikationskabel Wilo Net ist werkseitig ebenfalls an dieser Pumpe montiert und konfiguriert. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 36
• Anschlusskabel dürfen niemals die Rohrleitung, die Pumpe oder das Motorgehäuse berühren. • Wenn Personen mit der Pumpe oder dem gepumpten Fördermedium in Berührung kommen können, die geerdete Verbindung zusätzlich mit einer Fehlerstrom-Schutzvorrichtung ausstatten. • Einbau- und Betriebsanleitungen von Zubehör beachten! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 37
Unzureichende Netzauslegung kann zu Systemausfällen und Kabelbränden durch Netzüberlastung führen! • Bei Netzauslegung in Bezug auf verwendete Kabelquerschnitte und Absicherungen berücksichtigen, dass im Mehrpumpenbetrieb kurzzei- tig gleichzeitiger Betrieb aller Pumpen auftreten kann. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 38
1 (Fig. 20) 3~380 V AC ... 3~440 V AC 1~220 V AC ... 1~240 V AC Kunststoff 2 (Fig. 19) 1~220 V AC ... 1~240 V AC 12 V DC Kunststoff 3 (Fig. 19) 1~220 V AC ... 1~240 V AC 12 V DC Fig. 19: Kabelverschraubungen/Kabeldurch- führungen Digitaleingang 1 (nur EXT. Metall mit Abschirmung 4, 5, 6 11 ... 12 AUS) (Fig. 20, Fig. 21), (24 V DC) Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 39
Kabel für EXT. AUS an Digitaleingängen • Externes Steuerkabel an Analogeingängen • Differenzdruckgeber (DDG) an Analogeingängen, wenn bauseitig installiert • Doppelpumpenkabel bei zwei Einzelpumpen im Hosenrohr (Buskommunikation) • CIF-Modul an die Gebäudeautomation (Buskommunikation) Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Fig. 21: Klemmen für Analogeingänge, Digitaleingänge und Wilo Net HINWEIS AI3 und AI4 (Klemmen 6 ... 10) sowie DI2 (Klemmen 13 und 14) sind nicht belegt. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 41
[” 30]. Ausschließlich einen kalibrierten Drehmo- mentschlüssel verwenden! Stromart und Spannung auf dem Typenschild beachten. Den elektrischen Anschluss über ein festes Anschlusskabel mit einer Steckvorrichtung oder einem allpoligen Schalter mit mindestens 3 mm Kontaktöffnungsweite herstellen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 42
Wo für den Schutz im Fall einer direkten oder indirekten Berührung eine Fehlerstrom-Schutzeinrichtung (RCD) oder ein Fehlerstrom-Überwa- chungsgerät (RCM) verwendet wird, ist auf der Stromversorgungsseite dieses Produkts nur ein RCD oder RCM vom Typ B zulässig. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 43
Kabelverschraubungen M20 und Dichtungseinsätze müssen bauseitig be- schafft werden. Fig. 25: Schirmauflage HINWEIS Wenn zwei Kabel an eine 24 V-Versorgungsklemme angeschlossen wer- den müssen, bauseits eine Lösung bereitstellen! Es darf nur ein Kabel pro Klemme an der Pumpe angeschlossen werden! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 44
Bei der Yonos GIGA2.0-D ist das Wilo Net Kabel zur Doppelpumpenkom- munikation werkseitig an beiden Elektronikmodulen montiert. Um die Wilo Net Verbindung herzustellen, müssen die drei Klemmen H, L, GND mit einer Kommunikationsleitung von Pumpe zu Pumpe verdrahtet werden. Eingehende und ausgehende Kabel werden in einer Klemme geklemmt.
Pagina 45
Pumpe 2 eingeschaltet Tab. 13: Wilo Net Verkabelung Anzahl der Wilo Net Teilnehmer: Bei Doppelpumpen besteht das Wilo Net aus zwei Teilnehmern, dabei zählt jeder einzelne Knoten als Teilnehmer. • Doppelpumpe = 2 Teilnehmer (z. B. ID 1 und 2) Weitere Beschreibungen siehe Kapitel „Anwendung und Funktion der Wilo Net Schnittstel- le“...
Pagina 46
Bei Doppelpumpen muss nur die Hauptpumpe mit einem CIF-Modul ausgerüstet werden. • Bei Pumpen in Hosenrohranwendungen, bei denen die Elektronikmodule untereinander über Wilo Net verbunden sind, benötigt ebenfalls nur die Hauptpumpe ein CIF-Modul. HINWEIS Bei Verwendung des CIF-Modul Ethernet wird die Verwendung des Zube- hörs „Anschluss M12 RJ45 CIF-Ethernet“...
Pagina 47
Systemdruck kann Fördermedium unter hohem Druck herausschießen. • Entlüftungsvorrichtung nur vorsichtig öffnen. • Elektronikmodul beim Entlüften vor austretendem Wasser schützen. Anlage sachgemäß füllen und entlüften. Zusätzlich die Entlüftungsventile (Fig. I, Pos. 28) lösen und die Pumpe entlüften. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 48
Motor anlaufen zu lassen. Bei Rücksetzung auf Werkseinstellung ist der Digitaleingang DI1 wieder aktiv. Ohne Kabel- brücke läuft die Pumpe dann nicht an. Siehe Kapitel „Anwendung und Funktion des digita- len Steuereingangs“ [” 73]. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 49
x Ist-Drehzahl / Max-Drehzahl max Pumpe 9.4.2 Einstellungen an der Pumpe Einstellungen werden durch Drehen und Drücken des Bedienknopfs vorgenommen. Mit ei- ner Links- oder Rechtsdrehung des Bedienknopfs wird durch die Menüs navigiert oder es Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 50
Bei Erstinbetriebnahme der Pumpe erscheint im Display das Ersteinstellungsmenü. Durch Drehen des Bedienknopfs erscheinen die verschiedenen Menüsprachen. Folgende Sprachen können gewählt werden: Language Sprachenkürzel Sprache Englisch Deutsch Französisch Italienisch Spanisch UNIV Universal Finnisch Fig. 28: Ersteinstellungsmenü Schwedisch Portugiesisch Norwegisch Niederländisch Dänisch Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 51
Weitere Werkseinstellungen siehe Kapitel „Werkseinstellung“ [” 94]. HINWEIS Die Werkseinstellung bei Variante ... R1 (ohne Differenzdrucksensor im Auslieferungszustand) ist die Basisregelungsart „Konstante Drehzahl“. Die im Folgenden erwähnte Werkseinstellung bezieht sich auf die Variante mit werkseitig angebautem Differenzdrucksensor. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 52
Wenn eine Doppelpumpenverbindung eingerichtet ist, wird hier der Status der Doppelpumpe angezeigt. Betriebsdaten und Anzeige aktueller Betriebsdaten und Messwerte. Die ange- Messwertebereich zeigten Betriebsdaten hängen von der eingestellten Rege- lungsart ab. Sie werden alternierend angezeigt. Tab. 17: Homescreen Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 53
Der Titel benennt ein weiteres Untermenü oder einen nachfolgenden Einstelldialog. Folgende Tabelle gibt eine Übersicht über das Hauptmenü „Einstellungen“: 9.4.7 Hauptmenü „Einstellungen“ - Menüübersicht Universal Displaytext Einstellungen Regelungseinstellung 1.1.1 Regelungsart Δp-v ∆p-v Δp-c ∆p-c PID control PID-Regelung Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 54
Menüpunkt erscheint nur, wenn Regelungsart PID eingestellt ist. Menüpunkt erscheint nur, wenn Notbetrieb auf „EIN“ eingeschaltet ist. Menüpunkt erscheint nur, wenn als Sollwertquelle Analogeingang AI2 ausgewählt wird. 9.4.8 Hauptmenü "Einstellungen" Im Menü „Einstellungen“ können verschiedene Einstellungen vorgenommen werden. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 55
Der zuvor veränderte Wert wird verworfen, da er nicht bestätigt wurde. Um eingestellte Parameter zu überprüfen, kann durch Drücken des Bedienknopfs von Pa- rameter zu Parameter gewechselt werden. Bestehende Parameter werden dabei erneut bestätigt, aber nicht geändert. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 56
Nach Beendigung des Prozesses läuft die Pumpe im eingestellten Regelbetrieb weiter. HINWEIS Ein wiederholtes oder langes Drücken der Zurück-Taste führt bei einer Fehlermeldung zur Statusanzeige „Fehler“ und nicht zurück zum Haupt- menü. Der Statusbereich ist rot markiert. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 57
Der Wirksinn der Regelung kann durch das Ein- oder Ausschalten der Regelungsinversion eingestellt werden. 10.2 Auswahl einer Regelungsart Im Menü „Einstellungen“ (Universal 1.0) können folgende Untermenüs gewählt wer- den: Universal Displaytext Regelungseinstellung Externe Schnittstellen Doppelpumpen-Management Display-Einstellungen Zusätzliche Einstellungen Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 58
Wenn die Regelungsart konstante Drehzahl n-c gewählt wird, erscheint im Menü „Rege- lungseinstellung“ das Untermenü „Sollwert n-c“. Die gewünschte Drehzahl kann als Sollwert eingestellt werden. Nach Bestätigung des Sollwerts erscheint erneut das Menü „Regelungseinstellung“. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 59
Wenn der Sollwert über den Analogeingang AI2 eingestellt wird, kann der Analogeingang im Menü „Einstellungen“ konfiguriert werden. Wenn eine externe Sollwertquelle (Analogeingang AI2 oder CIF-Modul) gewählt wird, er- scheint der Menüpunkt „Ersatzsollwert“. Hier kann ein fester Sollwert vorgegeben werden, Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 60
„Einstellungen“ kann der Motor der Pumpe ein- und ausgeschaltet werden. Da- Regelungseinstellung zu nacheinander Folgendes wählen: Universal Displaytext Sollwert n-c Einstellungen Regelungseinstellung Sollwertquelle 1.1.15 Pumpe EIN/AUS Ausgeschaltet Pumpe EIN/AUS Eingeschaltet Fig. 46: Regelungseinstellung Pumpe EIN/AUS Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 61
Minimum jede 1 h erfolgen und kann in Abstufungen bis maximal 36 h eingestellt werden. HINWEIS Auch nach Ab- und Wiedereinschalten der Netzspannung läuft die ver- bleibende Zeit bis zum nächsten Pumpentausch weiter. Die Zählung be- ginnt nicht wieder von vorne! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 62
Bei Schaltung zweier typgleicher Einzelpumpen zu einer Doppelpumpe muss Wilo Net mit Kabel zwischen den Pumpen installiert werden. Anschließend im Menü unter „Einstellungen/Externe Schnittstellen/ Einstellung Wilo Net“ die Terminierung sowie die Wilo Net Adresse einstellen. Danach im Menü „Einstel- lungen“ Untermenü „Doppelpumpen-Management“ die Einstellungen „Doppelpumpe verbinden“ vornehmen.
Pagina 63
• Pumpengehäusetyp Bei bestehender Doppelpumpenverbindung sind folgende Einstellungen möglich: • Doppelpumpe trennen. • Doppelpumpenfunktion • Pumpentausch einstellen. • Pumpengehäusetyp HINWEIS Bei einer werkseitig ausgelieferten Doppelpumpe ist die Doppelpumpen- verbindung vorkonfiguriert und aktiv. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 64
Bei beiden Pumpen der Doppelpumpe muss zuerst die Wilo Net-Adresse des Doppelpum- penpartners eingestellt werden. Doppelpumpe verbinden Beispiel: Pumpe I ist die Wilo Net-Adresse 1 zugeordnet, Pumpe II die Wilo Net-Adresse 2. Doppelpumpenpartner- In Pumpe I muss dann die Adresse 2 des Doppelpumpenpartners und in Pumpe II-Adresse 1 Adresse eingestellt werden.
Pagina 65
Haupt/Reserve 1.4.3.2 Spitzenlastbetrieb HINWEIS Fig. 53: Menü Doppelpumpenfunktion Beim Umschalten der Doppelpumpenfunktion werden verschiedene Para- meter der Pumpe grundlegend geändert. Die Pumpe wird danach automa- tisch neu gestartet. Danach erscheint wieder das Hauptmenü. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 66
Die Auswahl, an welcher Hydraulikposition ein Motorkopf montiert ist, findet unabhängig von einer Doppelpumpenverbindung statt. Doppelpumpen- Management Im Menü „Pumpengehäusetyp“ steht folgende Auswahl zu Verfügung: • Einzelpumpenhydraulik Doppelpumpenfunktion • Doppelpumpenhydraulik I (links in Flussrichtung) • Doppelpumpenhydraulik II (rechts in Flussrichtung) Pumpentausch Pumpengehäusetyp Fig. 55: Menü Doppelpumpen-Management Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 67
Im Bereich „Aktive Einflüsse“ sind im Doppelpumpenbetrieb zwei Pumpensymbole darge- stellt. Sie haben folgende Bedeutung: Fall 1 - Haupt-/Reservebetrieb: Nur Hauptpumpe läuft. Anzeige im Display der Hauptpumpe Anzeige im Display der Partnerpumpe Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 68
Der Pumpenpartner ist im Regelbetrieb aktiv. Additionsbetrieb: AUS Doppelpumpe ist im Additionsbetrieb eingestellt. Beide Pumpen sind im Regelbetrieb in- aktiv. Additionsbetrieb: Parallelbetrieb Doppelpumpe ist im Additionsbetrieb eingestellt. Beide Pumpen sind parallel im Regelbe- trieb aktiv. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 69
Wenn die Pumpe stromlos ist, ist der Kontakt NC geschlossen. • Wenn eine Störung vorliegt, ist der Kontakt an NC geöffnet. Die Brücke zu NO ist ge- schlossen. Im Menü dazu Folgendes wählen: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 70
Um alle Störungen beider Pumpen zu erfassen, müssen in beiden Antrie- ben die Kontakte belegt werden. Fig. 61: Menü Doppelpumpe SSM-Relaisfunk- Universal Displaytext tion Einstellungen Externe Schnittstellen 1.3.1 SSM-Relais 1.3.1.4 Doppelpumpe SSM-Relaisfunktion Systemmodus (SSM) Einzelpumpenmodus (ESM) Diese Untermenüs erscheinen nur bei verbundener Doppelpumpe. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 71
SBM-Relais SSM-Relais 1.3.6.3 SBM-Relaisfunktion SBM-Relais 1.3.6.3 / 1 Motor läuft 1.3.6.3 / 2 Netzspannung vorhanden Steuereingang 1.3.6.3 / 3 Betriebsbereit Erscheint nur, wenn Doppelpumpe konfiguriert ist. Fig. 63: Menü Externe Schnittstellen Mögliche Einstellungen: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 72
Anschlüsse. Im Menü dazu Folgendes wählen: Universal Displaytext Einstellungen Externe Schnittstellen 1.3.6 SBM-Relais 1.3.6.7 SBM-Relais Zwangssteuerung 1.3.6.7 / 1 Normal 1.3.6.7 / 2 Gezwungen aktiv 1.3.6.7 / 3 Gezwungen inaktiv Auswahlmöglichkeiten: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 73
Nicht verwendet Der Steuereingang ist ohne Funktion. Extern AUS Kontakt geöffnet: Pumpe ist ausgeschaltet. Werkseinstellung: Nicht verwendet Kontakt geschlossen: Pumpe ist eingeschaltet. Extern AUS Tab. 26: Funktion Steuereingang DI1 Fig. 66: Menü Funktion Digitaleingang Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 74
AUS (DI1/2) Nicht ak- OK Normaler Aktiv Betrieb Übersteuern AUS (DI1/2) Aktiv Nicht OK Normaler Übersteuern aktiv Betrieb AUS (DI1) Nicht ak- OK Normaler Nicht OK Normaler Betrieb aktiv Betrieb Tab. 28: Einzel-Modus Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 75
Analogeingang AI1 wird als Istwert-Eingabe (Sensorwert) verwendet. Analogeingang AI2 wird als Sollwert-Eingang genutzt. Eingestellte Regelungsart Funktion Analogeingang Funktion Analogeingang Δp-v Konfiguriert als Istwert-Ein- Nicht konfiguriert gabe Nutzbar als Sollwert-Einga- • Nutzungsart: Differenz- drucksensor Konfigurierbar: • Signaltyp • Sensormessbereich • Sensorposition Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 76
Analogeingang AI1 oder AI2 auf eine Nutzungsart und einen Signaltyp konfiguriert worden ist. 12.7.1 Nutzung des Analogeingangs AI1 Der Istwertgeber liefert Folgendes: als Sensor-Eingang (Istwert) • Differenzdruck-Sensorwerte für die Differenzdruckregelung • Benutzerdefinierte Sensorwerte für die PID-Regelung Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 77
Normkonforme Position Der Istwert des Differenzdrucks verläuft linear zwischen den Analogsignalen 2 V und 10 V. Dies entspricht 0 % ... 100 % des Sensormessbereichs. (Siehe Diagramm Fig. 72). Fig. 72: Verhalten Analogeingang AI 1: Sensorwert bei Signaltyp 2 ... 10 V / 4 ... 20 Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 78
„100 %“ dar. (Siehe Diagramm Fig. 72). Der Sollwert, auf den die Pumpe regelt, wird gemäß Kapitel „Regelungseinstellungen“ vorge- geben. Die Einstellung erfolgt im Menü „Regelungseinstellung“ [” 57], „Einstellen der Soll- wertquelle“ [” 59]. Es muss „Interner Sollwert“ aktiviert werden. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 79
Der Sollwert, auf den die Pumpe regelt, wird gemäß Kapitel „Regelungseinstellungen“ vorge- geben. Die Einstellung erfolgt im Menü „Regelungseinstellung“ [” 57], „Einstellen der Soll- wertquelle“ [” 59]. Es muss „Interner Sollwert“ aktiviert werden. Die Funktion „Kabelbrucherkennung“ ist nicht aktiv. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 80
Das anliegende Analogsignal von 5 V oder 10 mA stellt den Soll- wert (z. B. die Drehzahl) bei „0 %“ dar. Das anliegende Analogsignal von 10 V oder 20 mA stellt den Sollwert bei „100 %“ dar. (Siehe Diagramm Fig. 78). Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 81
10 V oder 20 mA stellt den Sollwert bei „100 %“ dar. (Siehe Diagramm Fig. 79). Fig. 79: Verhalten Analogsignal AI2: Sollwert bei Signaltyp 0 ... 10 V / 0 ... 20 mA Bei einem Analogsignal kleiner als 1 V oder 2 mA ist der Motor ausgeschaltet. Die Kabelbrucherkennung ist nicht aktiv. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 82
Die Kopplung zwischen externer Quelle und Sollwert wird sowohl im Homescreen, als auch im Sollwerteditor blau gekennzeichnet. Die Status- LED leuchtet ebenfalls blau. 12.8 Anwendung und Funktion der Wilo Wilo Net ist ein Bus-System mit dem Wilo-Produkte (Teilnehmer) miteinander kommuni- Net-Schnittstelle zieren können. Anwendung bei: •...
Pagina 83
Einstellung Wilo Net 1.3.5.2 Wilo Net-Adresse Jeder Pumpe muss eine eigene Adresse zugeordnet werden (1 ... 2) zuordnen. HINWEIS Der Einstellungsbereich für die Wilo Net-Adresse ist 1 ... 126, alle Werte im Bereich 22 ... 126 dürfen nicht genutzt werden. Fig. 82: Menü Wilo Net-Adresse Beispiel Doppelpumpe: •...
Pagina 84
Ausschalten und Neustarten des Displays kommen. Währenddessen blinkt die grüne LED. Nachdem das Display erneut gest- artet ist, erscheint die Sprachenauswahlliste mit der aktivierten neu aus- gewählten Sprache. Dieser Vorgang kann bis zu ca. 30 sec. dauern. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 85
HINWEIS Werkseitig sind die Einheiten auf m, m /h eingestellt. Die Tastensperre verhindert ein Verstellen der eingestellten Pumpenparameter durch unbe- 13.4 Tastensperre fugte Personen. Unter „Einstellungen“, „Display-Einstellungen“ kann die Tastensperre aktiviert werden. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 86
Pumpen-Kick ein- und ausgeschaltet werden. • kann das Zeitintervall für den Pumpen-Kick zwischen 2 h und 72 h eingestellt werden. (Werkseinstellung siehe Kapitel „Werkseinstellung“ [” 94]). • kann die Pumpendrehzahl, mit der der Pumpen-Kick ausgeführt wird, eingestellt werden Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 87
Wenn die Funktion „Automatische PWM-Frequenzreduzierung“ aktiviert ist, verändert sich die Schaltfrequenz ab einer kritischen Temperatur, um den geforderten hydraulischen Ar- beitspunkt weiterhin liefern zu können. HINWEIS Eine veränderte Schaltfrequenz kann zu höheren und/oder veränderten Betriebsgeräuschen der Pumpe führen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 88
Doppelpumpe Verbindungsinfo Partner paired and re- Partner verbunden und erreichbar. achable. Partner is paired. Partner ist verbunden. Partner is not reachable. Partner ist nicht erreichbar. Partner WCID: Partner WCID: Partner Address: Partneradresse: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 89
Übersicht Analogeingang (AI2) 2.1.6 Doppelpumpe Verbindungsinfo 2.1.7 Status Pumpentausch 15.2 Geräteinformation Im Menü „Diagnose und Messwerte“ können Informationen zum Produktnamen, zur Artikel- und Seriennummer sowie Soft- und Hardware-Version abgelesen werden. Dazu Folgendes wählen: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 90
Relaisfunktion: SSM Forced control: Yes Zwangssteuerung: Ja Forced control: No Zwangssteuerung: Nein Current status: Energized Aktueller Status: Unter Spannung Current status: Not ener- Aktueller Status: Keine Spannung gized Fig. 93: Übersicht der Relaisfunktion SSM Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 91
Folgende Statusinformationen liegen vor: • Nutzungsart • Signaltyp • Aktueller Messwert 15.8 Übersicht über die Doppelpum- Im Menü „Diagnose und Messwerte“ können Status Informationen zur Doppelpum- penverbindung penverbindung abgelesen werden. Dazu Folgendes wählen: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 92
Aktueller Status: Keine Pumpe läuft/beide Pumpen laufen/Hauptpumpe läuft/Pumpen- partner läuft. • Zeit bis zum nächsten Pumpentausch 15.10 Messwerte Im Menü „Diagnose und Messwerte“ können Betriebsdaten, Messwerte und Statistik- werte abgelesen werden. Dazu nacheinander Folgendes wählen: Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 93
Pumpe zurück auf Werkseinstellung gestellt werden. Dazu Folgen- des wählen: Universal Displaytext Werkseinstellung Werkseinstellung Zurück auf Werkseinstellung Zurück auf Werkseinstellung Confirm Bestätigen (Einstellungen gehen verloren!) CANCEL Abbrechen Fig. 101: Zurücksetzen auf Werkseinstellung Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 94
Englisch Englisch Einheiten m, m m, m Pumpen-Kick eingeschaltet eingeschaltet Pumpen-Kick Zeitintervall Diagnose und Messwerte Diagnose-Hilfe SSM-Zwangssteuerung (nor- inaktiv inaktiv mal, aktiv, inaktiv) SBM-Zwangssteuerung (nor- inaktiv inaktiv mal, aktiv, inaktiv) Zusätzliche Einstellungen Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 95
Fachbetrieb über- räusche. prüfen und gegebenenfalls in- stand setzen lassen. Tab. 34: Mechanische Störungen 17.2 Fehlermeldungen Anzeige einer Fehlermeldung im graphischen Display • Die Statusanzeige ist rot eingefärbt. • Fehlermeldung, Fehlercode (E...). Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 96
Dre- sich drehenden Teile im hen der Pumpenwelle. Pumpenkörper und Motor. Ablagerungen und Fremd- körper entfernen. Zusatzinformation zu Ursachen und Abhilfe: Neben Ablagerungen und Fremdkörpern im System kann auch die Pumpenwelle blockieren. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 97
Motor oder Elektronik- Motor oder Elektronik- Motor und/oder Elektronik- modul defekt. modul defekt. modul austauschen. Zusatzinformation zu Ursachen und Abhilfe: Die Pumpe kann nicht feststellen, welches der beiden Bauteile defekt ist. Service kontaktieren. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 98
Rückschlagklappen ein- Flussrichtung der bauen. Pumpe. Zusatzinformation zu Ursachen und Abhilfe: Wenn die Pumpe zu stark in entgegengesetzter Richtung durchströmt wird, kann der Motor nicht mehr starten. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 99
Angeschlossene Kabel und (binär). gang kurzgeschlossen Verbraucher an Spannungs- oder zu stark belastet. versorgung Digitaleingang auf Kurzschluss überprüfen. Zusatzinformation zu Ursachen und Abhilfe: Binäreingänge sind beeinträchtigt. Funktionen der Binäreingänge stehen nicht zur Verfügung. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 100
Display- und Bedienein- Es wurde ein Defekt an Display- und Bedieneinheit heit defekt. der Display- und Be- austauschen. dieneinheit festge- stellt. Zusatzinformation zu Ursachen und Abhilfe: Die Display- und Bedieneinheit ist als Ersatzteil verfügbar. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 101
Elektrische Arbeiten: Eine Elektrofachkraft muss die elektrischen Arbeiten ausführen. • Montage-/Demontagearbeiten: Die Fachkraft muss im Umgang mit den notwendigen Werkzeugen und erforderlichen Befestigungsmaterialien ausgebildet sein. Es wird empfohlen, die Pumpe durch den Wilo-Kundendienst warten und überprüfen zu lassen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 102
• Allgemeinen Verhaltensrichtlinien, die für den Umgang mit elektri- schen Geräten gelten, befolgen! • Motor nicht öffnen! • Demontage und Montage des Rotors nur durch Wilo-Kundendienst durchführen lassen! Personen, die einen Herzschrittmacher tragen, dürfen solche Arbeiten nicht durchführen! HINWEIS Von den Magneten im Inneren des Motors geht keine Gefahr aus, solange der Motor komplett montiert ist.
Pagina 103
18.2 Wartungsarbeiten GEFAHR Lebensgefahr durch herabfallende Teile! Durch Herabfallen der Pumpe oder einzelner Bauteile kann es zu lebens- gefährlichen Verletzungen kommen! • Pumpenbauteile bei Installationsarbeiten mit geeigneten Lastaufnah- memitteln gegen Herabfallen sichern. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 104
Eine regelmäßige Sichtkontrolle ist erforderlich. Bei deutlich erkennbarer Leckage einen Dichtungswechsel vornehmen. Weitere Informationen siehe auch Wilo-Planungshinweise Trockenläuferpumpen. Wilo bietet ein Reparatur-Set an, das die für einen Wechsel erforderlichen Teile enthält. HINWEIS Für Personen mit Herzschrittmachern geht keinerlei Gefahr von den im Motorinneren liegenden Magneten aus, solange der Motor nicht geöffnet...
Pagina 105
30. Sitzflächen der Welle und der Laterne sorgfältig säubern. ⇒ Ausführung DN 100 ... DN 125, 5,5 kW bis 7,5 kW, Fig. III 31. Einstecksatz (siehe Kapitel „Beschreibung der Pumpe“) durch Lösen der Flanschschrau- ben (Fig. I/ III, Pos. 29) vom Pumpengehäuse abnehmen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 106
14. Laternennut säubern und den neuen O-Ring (Fig. II, Pos. 19) einlegen. 15. Einstecksatz zur Absicherung mit geeigneten Hebemitteln an den Transportösen befes- tigen. Beim Befestigen eine Beschädigung der Kunststoffteile wie Lüfterrad und Oberteil des Elektronikmoduls vermeiden. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 107
28. Absperreinrichtungen vor und hinter der Pumpe öffnen. 29. Sicherung wieder einschalten. 18.2.2 Motor/Antrieb wechseln Erhöhte Lagergeräusche und ungewöhnliche Vibrationen zeigen einen Lagerverschleiß an. Lager oder Motor müssen dann gewechselt werden. Wechseln des Antriebs nur durch den Wilo-Kundendienst! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 108
Flanschschrauben (Fig. I, Pos. 29) einschrauben, aber noch nicht endgültig festzie- hen. Vor Montage des Elektronikmoduls den neuen O-Ring (Fig. I, Pos. 31) zwischen Elek- tronikmodul (Fig. I, Pos. 1) und Motoradapter (Fig. I, Pos. 11) auf den Kontaktierungs- dom aufziehen. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 109
Motorinneren liegenden Magneten aus, solange der Motor nicht geöffnet oder der Rotor demontiert wurde. Ein Wechseln des Elektronikmoduls kann ohne Gefahr durchgeführt werden. Zur Demontage des Elektronikmoduls Handlungsschritte 1 ... 5 durchführen, entspre- chend Kapitel „Gleitringdichtung wechseln" [” 104]. Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 110
Um das Modul zu demontieren, siehe Kapitel „Elektronikmodul wechseln“ und Handlungs- 18.2.4 Modullüfterwechsel schritte 1 ... 5 aus dem Kapitel „Gleitringdichtung wechseln“ [” 104] Demontage des Lüfters: Deckel des Elektronikmoduls öffnen. Fig. 105: Deckel des Elektronikmoduls öffnen Anschlusskabel des Modullüfters abziehen. Fig. 106: Anschlusskabel des Modullüfters lö- Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 111
Dadurch werden Rückfragen und Fehlbestellungen vermieden. HINWEIS Liste der Originalersatzteile: siehe Wilo-Ersatzteildokumentation (www.wilo.com). Die Positionsnummern der Explosionszeichnung (Fig. I und Fig. II) dienen der Orientierung und der Auflistung von Pumpenkom- ponenten. Diese Positionsnummern nicht für Ersatzteilbestellungen verwenden! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 112
Informationen zur ordnungsgemäßen Entsorgung bei der örtlichen Gemeinde, der nächsten Abfallentsorgungsstelle oder bei dem Händler erfragen, bei dem das Produkt gekauft wur- de. Weitere Informationen zum Recycling unter www.wilo‑recycling.com. Technische Änderungen vorbehalten! Einbau- und Betriebsanleitung • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 113
18 Maintenance ................ 205 Description of operating elements........ 153 18.1 Air supply................ 207 Pump operation.............. 153 18.2 Maintenance tasks ............ 207 10 Control settings.............. 160 19 Spare parts................ 214 10.1 Control functions ............. 160 Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 114
20 Disposal .................. 215 20.1 Oils and lubricants............ 215 20.2 Information on the collection of used electrical and elec- tronic products .............. 215 Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 115
All rights reserved. Subject to change Wilo shall reserve the right to change the listed data without notice and shall not be liable for technical inaccuracies and/or omissions. The illustrations used may differ from the ori- ginal and are intended as an exemplary representation of the product.
Pagina 116
Personnel qualifications Staff must: • be instructed about locally applicable regulations governing ac- cident prevention, • have read and understood the installation and operating in- structions. Personnel must have the following qualifications: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 117
Never remove operating elements. • If radio waves (Bluetooth) lead to hazards (e.g. in hospitals), they must be switched off or removed if they are not desired or prohibited at the installation location. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 118
• Do not open the motor! • Dismantling and installation of the rotor may only be carried out by Wilo customer service! If you have been fitted with a pacemaker, you must not carry out this kind of work! NOTICE The magnets inside the motor do not pose a danger provided the motor is completely assembled.
Pagina 119
• Remove leakages of hazardous fluids (e.g. explosive, toxic or hot) in such a way that no danger is posed to persons or the en- vironment. Comply with national statutory provisions. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 120
The operational reliability of the supplied product is only guaranteed for intended use in ac- cordance with chapter "Intended use" of the installation and operating instructions. The limit values must not fall below or exceed those values specified in the catalogue/data sheet. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 121
2x auxiliary fastening screws Motor adapter for electronic module Motor housing DPS holder Fixation thread for transport lugs on motor flange, 2x Fixation thread for transport lugs on motor housing, 2x Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 122
Observe the instructions in the “Permitted installation positions and change of the ar- rangement of components before installation” [” 130] section. • Item 4: The display can be rotated in 90° steps as required. (See “Turning the display [” 149]” section). Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 123
The pump housing can remain in the pipe. Observe “Permitted installation positions and change of the arrangement of components be- fore installation” [” 130] section and the “Maintenance” [” 205] section. Fig. 4: Motor impeller unit Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 124
Device/ Metal Oxide Varis- Protection function control SELV, galvanically isolated terminals Electromagnetic compatib- ility Interference emission in acc. EN 61800-3:2018 Residential environment with: EN 61800-3:2018 (C1) Interference immunity in Industrial environment (C2) acc. with: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 125
(C1) with low electrical power in the conducted range. In this case, please contact WILO SE so that together we can find a quick and suitable shutdown measure. Yonos GIGA2.0-I/-D is a professional device within the meaning of EN 61000-3-2.
Pagina 126
Only remove the outer packaging at the place of utilisation to ensure that the pump is not damaged during transport. Storage CAUTION Damage due to incorrect handling during transport and stor- age! Protect the product from moisture, frost and mechanical damage during transport and temporary storage. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 127
To prevent scoring at the bearings and sticking, turn the pump shaft once a week using a socket wrench (see Fig. 5). If a longer storage time is required, contact Wilo for preservation measures. WARNING Risk of injury due to incorrect transport! If the pump is transported again at a later date, it must be packaged so that it cannot be damaged during transport.
Pagina 128
Observe locally applicable accident prevention and safety regu- lations of professional and trade associations. • Provide protective equipment and ensure that the protective equipment is worn by personnel. • Observe all regulations for working with heavy loads. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 129
• Do not open the motor! • Dismantling and installation of the rotor may only be carried out by Wilo customer service! If you have been fitted with a pacemaker, you must not carry out this kind of work! DANGER...
Pagina 130
In most cases, it is enough to rotate the motor impeller unit relative to the pump housing. The possible arrangement of components is the result of the permitted installation positions. Fig. 8: Arrangement of the components upon delivery Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 131
Fig. 10: Permitted installation positions with vertical motor shaft 6.4.3 Turn of motor impeller unit The motor impeller unit consists of an impeller, lantern and motor with electronic module. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 132
(DN 100 ... DN 125) NOTICE Always make sure that the O-ring (Fig. I, Item 19) is not twisted or squeezed during installation. Insert the motor impeller unit (Fig. 4) into the pump housing in the desired position. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 133
(Fig. I, Item 13). Loosen and remove the screws (Fig. II, Item 29). NOTICE To unscrew the screws (Fig. II, Item 29), use an open-end spanner, angle spanner or socket wrench with ball head, depending on the type. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 134
(Fig. I, Item 13). Slide the holder under the head of one of the screws (Fig. II, Item 10). Finally, tighten the screw (Fig. II, Item 10). 24. Reconnect the connection cable of the differential pressure sensor. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 135
Capillary tube Fig. I, Item 9 M6x0.75 Only bright brass fitting, union brass bright nuts nut on differen- tial pressure sensor Motor adapter Fig. I, Item 4 for electronic module Table 6: Screws and tightening torques Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 136
Transport lugs mounted on the motor housing are only permitted for transporting the motor! NOTICE Simplify subsequent work on the unit! • To ensure the entire unit does not have to be emptied, install shut-off valves upstream and downstream of the pump. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 137
If the leakage persists after this 1/4 turn, do not turn any further, but replace the screwed connection. Fig. 13: Further turning the clamping ring screw connection by a 1/4 turn Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 138
Influence of material and temperature The maximum permissible forces and torques apply for the grey cast iron base material and for an initial temperature value of 20 °C. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 139
For twin-head pumps in a twin-head pump housing, the pump on the left in the direction of flow is configured as the main pump at the factory. The differential pressure sensor is mounted on this pump. The Wilo Net bus communication cable is also mounted and configured on this pump at the factory.
Pagina 140
• If it is possible for persons to come into contact with the pump or the pumped fluid, the earthed connection must also be fitted with a re- sidual current circuit breaker. • Observe the installation and operating instructions for the accessor- ies! Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 141
• When designing the mains supply with regard to the used cable cross- sections and fuses, pay special attention to the fact that, in multi- pump operation, it is possible that all pumps operate at the same time for short periods. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 142
Fig. 19: Threaded cable glands/cable bush- Digital input 1 (only EXT. OFF) Metal with shielding 4, 5, 6 11 ... 12 ings (Fig. 20, (24 V DC) Fig. 21), Bus Wilo Net Metal with shielding 4, 5, 6 15 ... 17 (bus communication) ( Fig.20, Fig. 21) Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 143
Twin-head pump cable with two single pumps in the Y-piece (bus communication) • CIF module to the building automation (bus communication) The shield is connected to the cable bushing on the electronic module. See Fig. 25. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 144
Fig. 20: Overview of terminals in the module 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Fig. 21: Terminals for analogue inputs, digital inputs and Wilo Net NOTICE AI3 and AI4 (terminals 6 ... 10) and DI2 (terminals 13 and 14) are not as- signed.
Pagina 145
Observe the current type and voltage on the rating plate. Establish the electrical connection via a fixed connection cable equipped with a con- nector device or an all-pole switch with a contact opening width of at least 3 mm. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 146
RCD or RCM of type B is permissible on the power supply side of this product. • Labelling: • Trigger current:> 30 mA Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 147
Only one cable per terminal may be connected to the pump! NOTICE The terminals of the analogue inputs, digital inputs and Wilo Net meet the “safe isolation” requirement (according to EN 61800-5-1) to the mains terminals, the terminals SBM and SSM (and vice versa).
Pagina 148
For Yonos GIGA2.0-D, the Wilo Net cable for twin-head pump commu- nication is factory-fitted to both electronic modules. In order to establish the Wilo Net connection, the three H, L, GND terminals must be wired with a communication cable from pump to pump.
Pagina 149
Pump 2 switched on Table 13: Wilo Net cabling Number of Wilo Net participants: For twin-head pumps, the Wilo Net consists of two participants, with each individual node counting as a participant. • Twin-head pump = 2 participants (e.g. ID 1 and 2) For further descriptions, see “Application and function of the Wilo Net interface”...
Pagina 150
• For pumps in Y-pipe applications in which the electronic modules are connected to each other through the Wilo Net, only the main pump also requires a CIF module. NOTICE When using CIF module Ethernet, the use of the accessory “Connection M12 RJ45 CIF-Ethernet”...
Pagina 151
• Always exercise caution when opening the venting device. • Protect the electronic module from any water escaping when venting. Fill and vent the system correctly. In addition, loosen the air vent valves (Fig. I, Item 28) and vent the pump. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 152
When the digital input DI1 is reset to the factory setting, it is active again. The pump will not start without the cable bridge. See “Application and function of the digital control in- put” [” 177] section. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 153
A green focus indicates nav- igation in the menu. A yellow focus indicates a configuration of settings. • Green focus: Navigation in menu. • Yellow focus: Change settings. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 154
Turn the operating button to display the different menu languages. The following languages can be selected: Language Language abbreviations Language English German French Italian Spanish UNIV Universal Finnish Fig. 28: Initial settings menu Swedish Portuguese Norwegian Dutch Danish Polish Hungarian Czech Romanian Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 155
The factory setting for variant ... R1 (without differential pressure sensor in delivery status) is the basic control mode “Constant speed”. The factory setting mentioned below refers to the variant with a differential pressure sensor fitted in the factory. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 156
Shows current operating data and measured values. The measurement area displayed operating data depend on the set control mode. They are displayed alternately. Table 17: Home screen Setpoints can be changed in the “Home screen” menu. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 157
Main menu “Settings” - Menu The following table gives an overview of the “Settings” main menu: overview Universal Display text Settings Control settings 1.1.1 Control mode Δp-v ∆p-v Δp-c ∆p-c PID control PID control Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 158
The menu item only opens if emergency operation is set to “ON”. The menu item only opens if analogue input AI2 is selected as the setpoint source. 9.4.8 Main menu “Settings” Different settings can be changed in the “Settings” menu Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 159
Press the Back button to discard the current adjustment and retain the previous setting. The menu changes to the previous setting or previous menu. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 160
The status area is highlighted in red. Control settings 10.1 Control functions The following control functions are available: • Differential pressure ∆p-v • Differential pressure Δp-c • Speed constant (n-const.) • PID control Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 161
Additional settings To choose a control mode, select the following in succession: Control settings Universal Display text Settings Control mode Control settings 1.1.1 Control mode Setpoint Δp-v Emergency operation Fig. 38: Control mode Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 162
After setting the desired values, the “Control setting” menu opens again. Parameter Ti Universal Display text Parameter Td Settings Control settings 1.1.1 Control mode Fig. 41: Setting PID parameters 1.1.2 PID Setpoint PID Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 163
10.4 Emergency operation In the event of a malfunction (such as failure of the required sensor) an “emergency opera- tion” can be defined. (Only adjustable for control modes Δp-v and Δp-c) Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 164
Control settings select the following in succession: Universal Display text Setpoint n-c Settings Control settings Setpoint source 1.1.15 Pump ON/OFF Switched off Pump ON/OFF Switched on Fig. 46: Control setting pump ON/OFF Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 165
Even after switching the mains voltage off and on again, the remaining time until the next pump cycling continues to run. The timer does not start again from the beginning! • SSM/ESM (collective fault signal/individual fault signal): Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 166
Wilo Net must be installed with cable between the pumps when connecting two single pumps of the same type to a twin-head pump. Then set the termination as well as the Wilo Net address in the menu under “Settings/ external interfaces/Wilo Net setting”. Then, in the “Dual pump management” submenu of the “Settings”...
Pagina 167
• Disconnect twin-head pump. • Twin-head pump function • Set pump cycling. • Pump housing type NOTICE With a factory-supplied twin-head pump, the twin-head pump connec- tion is pre-configured and active. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 168
Pump housing type 1.4.1 Connecting twin-head pump Fig. 49: Dual pump management menu The Wilo Net address of the twin-head pump partner must first be set for both pumps of the twin-head pump. Connecting twin-head pump Example: Pump I is assigned the Wilo Net address 1, pump II the Wilo Net address 2.
Pagina 169
Fig. 53: Twin-head pump function menu When switching the twin-head pump function, different parameters of the pump are fundamentally changed. The pump is then automatically restar- ted. The main menu then opens again. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 170
Twin-head pump function • Twin-head pump hydraulics I (left in flow direction) • Twin-head pump hydraulics II (right in flow direction) Pump cycling Pump housing type Fig. 55: Dual pump management menu Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 171
This is what they mean: Case 1 – main/standby operation: only the main pump is running. Indication on the display of the main pump Indication on the display of the partner pump Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 172
Twin-head pump is set in main/standby Partner pump active operation. The pump partner is active in control mode. Parallel operation: OFF Twin-head pump is set in parallel oper- ation. Both pumps are inactive in control mode. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 173
• When the pump is without power, the NC contact is closed. • If there is a fault, the contact at NC is open. The converter bridge to NO is closed. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 174
In order to detect all faults of the two pumps, the contacts must be assigned in both drives. Fig. 61: Twin-head pump SSM relay function Universal Display text menu Settings External interfaces 1.3.1 SSM relay 1.3.1.4 Twin-head pump SSM relay function System mode (SSM) Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 175
Factory setting: ready for operation. Both contacts signal the operating status of the twin-head pump in parallel (collective run signal). Depending on the configuration, the contact is set to NO or NC. To do this, select the following in the menu: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 176
An SBM relay forced control is used as function test of the SBM relay and electrical connec- tions. To do this, select the following in the menu: Universal Display text Settings Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 177
Twin-head Pump ext. OFF function 1.3.2.2 / 1 System mode 1.3.2.2 / 2 Single mode 1.3.2.2 / 3 Combined mode The submenu only opens when the twin-head pump is connected Possible settings: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 178
“EXT. OFF” is active. Each of the two pumps is individually switched by its own control in- put. If the main pump fails or the twin-head pump connection is disconnected, the control input of the partner pump is evaluated. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 179
AI1 and AI2 target and actual value specifications depends on the selected control mode. Analogue input AI1 is used as actual value input (sensor value). Analogue input AI2 is used as setpoint input. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 180
Differential pressure measuring points are located in the piping upstream and down- stream of the pump on the discharge and suction side at a distance from the pump. 24 V DC power supply at the analogue input. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 181
1.3.3.3 / 2 Standard-compliant position The actual value of the differential pressure runs linearly between the analogue signals 2 V and 10 V. This corresponds to 0 % ... 100 % of the sensor measuring range. (See diagram Fig. 72). Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 182
100 %. The value must be read from the rating plate of the differential pressure sensor. This is the only way to ensure that the pump controls correctly. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 183
The applied analogue signal of 0 V or 0 mA represents the actual value of the differential pressure at “0 %”. The applied analogue signal of 10 V or 20 mA represents the actual value of the differential pressure at “100 %”. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 184
Fig. 77: Signal types menu (AI2) point (for instance the speed) at “0 %”. The applied analogue signal of 10 V or 20 mA repres- ents the setpoint of the differential pressure at “100 %”. (See diagram Fig. 78). Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 185
Fig. 79: Behaviour of analogue signal AI2: Setpoint for signal type 0 ... 10 V / 0 ... 20 mA If the analogue signal is less than 1 V or 2 mA, the motor is switched off. The cable break detection is not active. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 186
The coupling between external source and setpoint is marked both in the home screen, and in the setpoint editor in blue. The status LED also becomes blue. Wilo Net is a bus system that Wilo products (participants) can use to communicate with 12.8 Application and function of the each other.
Pagina 187
Wilo Net address Each pump must be assigned its own address (1 ... 2). NOTICE The setting range for the Wilo Net address is 1 ... 126, all values in the range 22 ... 126 may not be used. Fig. 82: Wilo Net address menu Twin-head pump example: •...
Pagina 188
In addition to the languages, there is a neutral number code “Universal” in the display that can be selected as an alternative language. The num- ber code is listed and explained in tables next to the display texts. Factory setting: English Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 189
Simultaneously pressing (> 5 seconds) the “Back” button and the operating button de- activates the key lock. When the key lock is activated, the Home screen and warning and error messages are still Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 191
Diagnostics help is used for diagnosis and maintenance of electronics and interfaces. In ad- dition to hydraulic and electrical overviews, information on interfaces and unit information is displayed. The following table provides an overview of the menu “Diagnosis and measured val- ues”: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 192
Partner Address: Partner address: Partner Name: Partner name: 2.1.7 Pump cycling status Time-based pump cyc- Time-based pump cycling ling: | Switched ON, interval: | Switched on, interval: Switched OFF Switched off Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 193
Statistical data W electr = W electr = Operating hours = Operating hours = WICD = Wilo Communication ID (Communication address of the twin-head pump partner) 15.1 Diagnostics help There are functions for diagnosis and maintenance of electronics and interfaces in the menu “Diagnostics and measured values”, “Diagnostics help”.
Pagina 194
Fig. 93: Overview of the relay function SSM 15.6 Overview of the SBM relay status You can read the status information on the SBM relay in the menu “Diagnostics and measured values”. To do this, select the following: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 195
Current measured value 15.8 Overview of the twin-head pump You can read status information on the twin-head pump connection in the menu connection “Diagnostics and measured values”. To do this, select the following: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 196
Partner address: connection Partner Name: Partner name: WICD = Wilo Communication ID (Communication address of the twin-head pump partner) NOTICE The twin-head pump connection overview is only available if a twin-head pump connection has been previously configured (see “Dual pump man- agement” [” 165] section).
Pagina 197
. To do this, select the fol- lowing: Universal Display text Factory setting Factory setting Reset to factory setting Back to factory settings Confirm Confirm (settings will be lost!) CANCEL Cancel Fig. 101: Resetting to factory setting Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 198
Pump kick time interval 24 h 24 h Diagnostics and measured values Diagnostics help SSM forced control (normal, inactive inactive active, inactive) SBM forced control (normal, inactive inactive active, inactive) Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 199
NOTICE If the pump behaves incorrectly, check that the analogue and digital in- puts are configured correctly. If the malfunction cannot be rectified, consult a specialist technician or the nearest Wilo customer service or representative location. 17.1 Mechanical faults without error...
Pagina 200
Remove deposits and for- eign substances. Additional information on causes and remedies: In addition to deposits and foreign substances in the system, the pump shaft can also be blocked. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 201
Electronic module is de- Electronic module is Electronic module is defect- fective. defective. ive. Additional information about causes and remedy: Contact service. Table 35: Error messages 17.3 Warning messages Warning displayed: Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 202
Additional information about causes and remedy: The pump can start despite flow through. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 203
The available signal is Check input signal. logue input AI1 or AI2. significantly over the expected maximum. Additional information about causes and remedy: The signal is processed with the maximum value. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 204
BMS = Building management system NOTICE The warning W573 “Communication to the display and control unit in- terrupted”, is shown differently from all other warnings on the display. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 205
Installation/dismantling: The technician must be trained in the use of the necessary tools and fixation materials. It is recommended to have the pump serviced and checked by the Wilo customer service. DANGER Risk of fatal injury due to electrical current!
Pagina 206
Opening the motor leads to high, abruptly occurring magnetic forces. This can lead to serious cuts, crushing injuries and bruises. • Do not open the motor! • Only allow Wilo customer service to dismantle and install the motor flange and the bearing plate for maintenance and repair work! DANGER...
Pagina 207
A regular visual inspection is required. If leakage is clearly visible, replace the gasket. For further information, see also Wilo Consulting guide for glanded pumps. Wilo offers a repair kit which contains the necessary parts for replacement. NOTICE The magnets inside the motor do not pose a risk to persons with pace- makers provided that the motor is not opened and the rotor is not dis- mantled.
Pagina 208
24. Screw M10 screws with a suitable length into the threaded holes to loosen the seat. Fig. 104: Pressing off the motor impeller unit After approx. 40 mm of pressing out, the motor impeller unit will no longer be guided in via threaded holes (DN 100 ... DN 125) the pump housing. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 209
Push the new spacer (Fig. I, Item 20) onto the shaft. Push the rear retaining ring (Fig. I, Item 36b) onto the pump shaft. Fit the impeller (Fig. I, Item 21) onto the shaft. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 210
To do this, insert an Allen key through the opening in the fan cover (Fig. 5). If the shaft is difficult to move, tighten the screws altern- ately and diagonally. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 211
Replacing the motor/drive Increased bearing noises and unusual vibrations indicate bearing wear. The bearings or mo- tor must then be replaced. The drive may only be replaced by the Wilo customer service! DANGER Risk of fatal electrical shock! Generator or turbine operation...
Pagina 212
If the rotor is driven via the impeller when the pump is at a standstill, a dangerous contact voltage can occur at the motor contacts. • Close the shut-off device upstream and downstream of the pump. Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 213
To dismantle the module, see section “Replacing the electronic module” and steps 1 ... 5 in 18.2.4 Module fan replacement the section “Replacing the mechanical seal” [” 207]. Dismantling the fan Open the cover of the electronic module. Fig. 105: Open the cover of the electronic module Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 214
Spare parts Obtain genuine spare parts only from a qualified specialist or Wilo customer service. To avoid queries and order errors, please provide all pump and drive rating plate data with every order. Pump rating plate see Fig. 2, Item 1, drive rating plate see Fig. 2, Item 2.
Pagina 215
This helps prevent return queries and incorrect orders. NOTICE For a list of genuine spare parts, see the Wilo spare parts documentation (www.wilo.com). The item numbers of the exploded view drawing (Fig. I and Fig. II) are for orientation and listing of pump components.
Pagina 216
électrique lors de la première mise en service ..... 258 17.3 Messages d'avertissement.......... 309 Description des éléments de commande ..... 259 18 Entretien .................. 313 Commande de la pompe .......... 259 18.1 Arrivée d'air ................ 315 Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 217
18.2 Travaux d'entretien ............ 315 19 Pièces de rechange.............. 323 20 Élimination ................ 324 20.1 Huiles et lubrifiants............ 324 20.2 Informations sur la collecte des produits électriques et électroniques usagés............ 324 Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 218
Tous droits réservés. Réserve de modifications Wilo se réserve le droit de modifier sans préavis les données susnommées et décline toute responsabilité quant aux inexactitudes et/ou oublis techniques éventuels. Les figures utili- sées peuvent différer du produit original et sont uniquement destinées à fournir un exemple de représentation du produit.
Pagina 219
Connaître les dispositions locales en vigueur en matière de pré- vention des accidents. • Avoir lu et compris la notice de montage et de mise en service. Le personnel doit posséder les qualifications suivantes : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 220
Si les ondes radioélectriques (Bluetooth) représentent un dan- ger (p. ex. dans un hôpital), elles doivent être désactivées ou éliminées si elles ne sont pas désirées ou sont interdites sur le lieu d'installation. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 221
Respecter les procédures décrites dans la notice de montage et de mise en service pour l'arrêt du produit/de l'installation. • Débrancher le produit de l'alimentation électrique et le protéger contre toute remise en service non autorisée. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 222
La plaque signalétique et de sécurité présente sur le produit doit toujours être lisible. • Former le personnel sur le mode de fonctionnement de l'instal- lation. • Écarter tout risque d'électrocution. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 223
Protéger la pompe contre les influences climatiques comme les rayons directs du soleil, la pluie et la neige. • La pompe doit être protégée de telle sorte que les rainures d'écoulement du condensat restent exemptes de salissures. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 224
Vis de fixation de la partie supérieure du module électronique, 4x Vis de fixation de l'embase du module électronique, 4x Connexion par anneau de serrage de la conduite de mesure de pression (côté corps), 2x Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 225
Axe du clapet de pompes doubles (seulement DN 100 … DN 125) Bouchon fileté de l'alésage d'axe, 2x (seulement DN 100 … DN 125) Bague de sécurité Bague de sécurité Clavette Regard de la lanterne Tabl. 1: Affectation des composants principaux Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 226
Capteur de pression différentielle avec éléments de raccor- différentielle dement et de fixation Entraînement L'entraînement se compose du moteur et du module élec- tronique. Fig. 3: Modules fonctionnels Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 227
Q = 0 m³/h Variante avec alimentation électrique 1~230 V Puissance nominale du moteur en kW Variante, p. ex. R1 Tabl. 4: Désignation Consulter Wilo-Select ou le catalogue pour obtenir un aperçu de toutes les versions de pro- duits. Caractéristiques techniques Propriété Valeur Commentaire Raccordement électrique :...
Pagina 228
Yonos GIGA2.0-D : 32/40/50/65/80/100/125 Brides Brides PN 16 EN 1092-2 Pression de service max. ad- 16 bar (jusqu'à +120 °C) missible Température du fluide min./ -20 °C ... +120 °C En fonction du fluide max. admissible Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 229
électrique est présente dans la zone conduite lors d'une utilisation dans un environnement résidentiel (C1) et en cas de conditions défavorables. Dans ce cas, contacter WILO SE afin de trouver rapide- ment une mesure corrective adaptée.
Pagina 230
Détérioration en cas de manipulation non conforme lors du transport et du stockage ! Lors du transport et de l'entreposage, protéger le produit de l'humidité, du gel et des dommages mécaniques. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 231
Les accessoires de levage doivent être fixés sur les œillets de transport présents sur la bride du moteur. Pousser les boucles de levage, si nécessaire, sous la plaque d'adap- tation (Fig. 6/7). Sécuriser la pompe pour éviter qu'elle ne bascule. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 232
Mettre à disposition l'équipement de protection requis et s'as- surer que le personnel le porte. • Respecter l'ensemble des directives régissant le travail avec des charges lourdes. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 233
L'ouverture du moteur libère instantanément des forces magnétiques de grande intensité qui peuvent occasionner des coupures, des écrasements et des contusions graves. • Ne pas ouvrir le moteur ! Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 234
Dans la plupart des cas, il suffit de tourner le kit embrochable par rapport au corps de pompe. La disposition possible des composants se base sur les positions de montage autorisées. Fig. 8: Disposition des composants à la livrai- Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 235
6.4.3 Rotation du kit embrochable Le kit embrochable se compose de la roue, de la lanterne et du moteur avec module élec- tronique. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 236
Si le joint torique (Fig. I, pos. 19) a été retiré, humidifier le joint torique et le disposer trous taraudés (DN 100 … DN 125) dans le corps de pompe (DN 32 ... DN 80) ou dans la rainure de la lanterne (DN 100 ... DN 125). Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 237
Laisser deux œillets de transport (Fig. I, pos. 30) libres sur la bride de moteur. À l'aide d'instruments de levage appropriés, fixer l'entraînement aux œillets de trans- port pour le sécuriser. Pour empêcher l'unité de basculer, attacher une sangle autour du Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 238
18. Retirer la clé plate et remonter la tôle de protection (Fig. II, pos. 27). 19. Si le joint torique est endommagé : Nettoyer la rainure de la lanterne et poser un joint torique neuf (Fig. II, pos. 19). Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 239
AN 305-11 pompe 0° Raccord fileté Fig. I, pos. 6 M8x1 en Écrous nickelés uni- du tube capil- laiton ni- quement (CV) laire, manchon ckelé 90° Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 240
Un dispositif pour la mise en place d'un appareil de levage doit être installé au-dessus de l'emplacement de montage des pompes plus volumineuses. Poids total de la pompe : voir catalogue ou fiche technique. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 241
Fixer la tuyauterie de manière à ce que la pompe ne supporte pas le poids des tuyaux. • Nettoyer et rincer l'installation avant de raccorder les tuyauteries. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 242
Valeurs conformément à la norme ISO/DIN 5199 – classe II (2002) – annexe B Tabl. 7: Forces et couples admissibles au niveau des brides de la pompe dans une tuyauterie verticale Fig. 14: Cas de charge 16A, EN ISO 5199, an- nexe B Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 243
EN-GJL 20, EN-GJL = module d'élasticité pour la fonte grise à la température choisie t, EN-GJL = module d'élasticité pour la fonte grise à 20 °C 20, EN-GJL Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 244
Le capteur de pression différentielle est monté sur cette pompe. Le câble de communication bus Wilo Net est également monté sur cette pompe et configuré en usine. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 245
Le capteur de pression différentielle est configuré dans le menu de la pompe. Types de signal possibles au niveau des capteurs de pression différen- tielle : • 0 ... 10 V • 2 ... 10 V • 0 ... 20 mA • 4 ... 20 mA Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 246
• Ne jamais introduire d'objets (p. ex. clous, tournevis, fil) dans les ou- vertures du module électronique ! • Remonter les dispositifs de sécurité démontés (p. ex. le couvercle du module) ! Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 247
Le module électronique comporte six passe-câbles pour le compartiment des bornes. Le câble d'alimentation électrique du ventilateur électrique est monté en usine sur le module électronique. Respecter les exigences relatives à la compatibilité électromagnétique. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 248
4, 5, 6 4, 5 (Fig. 20, Fig. 21) 0 ... 10 V, 2 ... 10 V, 0 ... 20 mA, 4 ... 20 mA (générateur de valeur de consigne externe) Module CIF Métal avec blindage 4, 5, 6 (communication bus) Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 249
à la technique Push-In. Il est possible de les ouvrir à l'aide d'un tourne- vis à fente SFZ 1 - 0,6 x 0,6 mm. Longueur de dénudage La longueur de dénudage du câble pour le raccordement des bornes doit se situer entre 8,5 mm et 9,5 mm. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 250
Fig. 21: Bornes pour les entrées analogiques, les entrées numériques et Wilo Net AVIS AI3 et AI4 (bornes 6 ... 10), ainsi que DI2 (bornes 13 et 14) ne sont pas uti- lisées. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 251
Les couples de serrage des vis de serrage sont indiqués dans le tableau « Couples de serrage » [” 239]. Utiliser exclusivement une clé dynamo- métrique calibrée ! Respecter le type de courant et la tension indiqués sur la plaque signalétique. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 252
Cette pompe est équipée d'un convertisseur de fréquence. Elle ne doit donc pas être pro- tégée à l'aide d'un disjoncteur différentiel. Les convertisseurs de fréquence peuvent nuire au fonctionnement des disjoncteurs différentiels. Fig. 23: Câble de raccordement rigide Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 253
Utiliser, dans ce cas, les inserts d'étanchéité multi-passage correspon- dants. AVIS Les passe-câbles à vis M20 et les inserts d'étanchéité sont à fournir par le client. Fig. 25: Support de blindage Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 254
à double pompe. Voir le chapitre « Installation à pompe double/ tuyau en Y » [” 244]. Raccordement de Wilo Net pour la Wilo Net est un bus système Wilo servant à établir la communication entre les produits fonction pompe double Wilo : •...
Pagina 255
Pour établir la connexion Wilo Net, les trois bornes H, L, GND doivent être reliées par un câble de communication d'une pompe à l'autre. Les câbles entrants et sortants sont insérés dans une borne. Câble pour la communication Wilo Net : Afin de garantir l'immunité...
Pagina 256
Les modules CIF sont enfichés dans le module électronique (Fig. 26, pos. 4). • Pour les pompes doubles, seule la pompe principale doit être équipée d'un module CIF. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 257
• Pour des pompes dans une installation avec tuyaux en Y, sur lesquels les modules élec- troniques sont raccordés entre eux par Wilo Net, seule la pompe principale nécessite un module CIF. AVIS Il est conseillé d'utiliser l'accessoire « Connexion M12 RJ45 CIF-Ether- net »...
Pagina 258
électrique lors de la première mise en service être effectués (voir le chapitre « Réglages de la régulation » [” 267]). Simultanément, le démarrage du moteur commence. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 259
Lors de la mise en service, régler la puis- sance de la pompe (hauteur manométrique) en fonction du point de fonctionnement de l'installation. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 260
La valeur précédente n'est pas modifiée. Si la touche retour est appuyée pendant plus de 2 secondes, la page d'accueil s'affiche et la pompe peut être commandée grâce au menu principal. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 261
Norvégien Néerlandais UNIV Danois Polonais Hongrois Tchèque Roumain Slovène Fig. 29: Menu Langue Croate Slovaque Serbe Letton Lituanien Estonien Russe Ukrainien Bulgare Grec Turc Tabl. 16: Langue des menus Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 262
Fig. 30: Menu principal 9.4.5 Menu principal « Page d'accueil » La sélection de la page d'accueil s'effectue en tournant le bouton de commande jus- qu'au symbole « Maison ». Fig. 31: Page d'accueil Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 263
« Kick » de la pompe actif EXT. OFF Entrée numérique DI EXT. OFF ac- tive Fonctionnement de pompe ARRÊT Pompe désactivée manuellement Valeur de consigne ARRÊT Signal analogique ARRÊT Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 264
Valeur de consigne = 1.1.3 Kp Paramètre Kp 1.1.4 Ti Paramètre Ti 1.1.5 Td Paramètre Td 1.1.6 Inversion de la régulation Inversion ARRÊT Inversion MARCHE 1.1.7 Régime de secours Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 265
S'il n'y a pas de flèche vers la droite, il est possible d'accéder à la boîte de dialogue de réglage en appuyant sur le bouton de commande. Fig. 34: Menu de réglage Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 266
Indicateur d'avertissement : Fig. 36: Zone d'état Les messages d'avertissement sont indiqués en jaune. Lorsqu'un avertissement survient, les fonctions de la pompe sont limitées (voir le cha- pitre « Avertissements » [” 309]). Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 267
En tenant compte de la hauteur manométrique à définir selon le point de fonctionnement, la pompe adapte sa puissance au débit nécessaire. Le débit varie selon les clapets ouverts et Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 268
Régulation PID Les modes de régulation ∆p-c et ∆p-v exigent impérativement le raccordement d'un capteur de pression différentielle sur l'entrée analogique AI1. Fig. 39: Choix du mode de régulation Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 269
Texte d'affichage Réglages Fig. 41: Réglage paramètres PID Réglage de la régulation 1.1.1 Mode de régulation 1.1.2 PID Valeur de consigne PID Setpoint = Valeur de consigne = Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 270
Régime de secours En cas de défaut (défaut du capteur requis), un « régime de secours » peut être défini. (ré- glable uniquement pour les modes de régulation Δp-v et Δp-c) Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 271
Réglages Réglage de la régulation Source de la valeur de consigne 1.1.15 Pompe MARCHE/ARRÊT Désactivé Pompe MARCHE/ARRÊT Activé Fig. 46: Réglage de la régulation de la pompe MARCHE/ARRÊT Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 272
Une permutation de la pompe en service peut avoir lieu minimum toutes les heures et peut être paramétrée par intervalles de 36 h maxi- mum. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 273
Communication entre les pompes : Pour une pompe double, la communication est préconfigurée en usine. Pour le couplage de deux pompes simples de même type en une pompe double, Wilo Net doit être installé entre les pompes avec un câble. Sous « Réglages / Interfaces externes / Réglage Wilo Net », régler la terminaison ainsi que l'adresse Wilo Net.
Pagina 274
Les réglages suivants sont possibles s'il y a une connexion de pompe double : • Séparer la pompe double. • Fonction circulateur double • Régler la permutation des pompes. • Type de corps de pompe Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 275
Type de corps de pompe 1.4.1 Connecter une pompe double Fig. 49: Menu Pilotage pompes doubles Pour les deux pompes de la pompe double, l'adresse Wilo Net du partenaire de pompe double doit tout d'abord être paramétrée. Connecter une pompe double Exemple : L'adresse Wilo Net 1 est attribuée à...
Pagina 276
En permutant la fonction de pompe double, les différents paramètres de la pompe sont fondamentalement modifiés. Ensuite, la pompe redémarre au- tomatiquement. Puis le menu principal réapparaît. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 277
Hydraulique de pompe double I (à gauche dans le sens d'écoulement) • Hydraulique de pompe double II (à droite dans le sens d'écoulement) Permutation des pompes Type de corps de pompe Fig. 55: Menu Pilotage pompes doubles Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 278
Ils ont la signification suivante : Cas 1 - Mode de fonctionnement normal/secours : seule la pompe principale fonctionne. Affichage sur l'écran de la pompe principale Affichage sur l'écran de la pompe partenaire Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 279
Mode de fonctionnement normal/ La pompe double est réglée en mode secours : de fonctionnement normal/secours. pompe partenaire active La pompe partenaire est en mode de régulation actif. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 280
Texte d'affichage ternes » Réglages Interfaces externes 1.3.1 Relais SSM 1.3.2 Entrée de commande 1.3.3 Entrée analogique (AI1) 1.3.4 Entrée analogique (AI2) 1.3.5 Réglage Wilo Net 1.3.6 Relais SBM Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 281
(report de défauts individuel). Pour enregistrer l'ensemble des pannes des deux pompes, les deux contacts doivent être affectés dans les deux entraînements. Fig. 61: Menu Fonction de relais SSM pompe Universal Texte d'affichage double Réglages Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 282
Paramètre d'usine : opérationnel. Les deux contacts signalent en parallèle l'état de fonc- tionnement de la pompe double (report de marche centralisé). En fonction de la configuration, le contact se trouve sur NO ou NC. Dans le menu, sélectionner : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 283
Une commande forcée du relais SBM sert à tester le fonctionnement du relais SBM et des 12.5 Commande forcée relais SBM branchements électriques. Dans le menu, sélectionner : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 284
1.3.2.2 / 1 Mode système 1.3.2.2 / 2 Mode seul 1.3.2.2 / 3 Mode combiné Le sous-menu n'apparaît qu'en cas de connexion d'une pompe double Réglages possibles : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 285
En cas de panne de la pompe principale ou d'interruption de la connexion des pompes doubles, l'entrée de commande de la pompe partenaire est évaluée. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 286
L'alimentation électrique 24 V CC est disponible uniquement lorsque l'en- trée analogique AI1 ou AI2 a été configurée sur un type d'utilisation et un type de signal, ou lorsque l'entrée numérique DI1 est configurée. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 287
Plage du capteur de pression 1.3.3.3 Position du capteur de pression 1.3.3.3 / 1 Bride de la pompe 1.3.3.3 / 2 Position conforme à la norme 1.3.4 Entrée analogique (AI2) Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 288
Type de signal 2 … 10 V / 4 … 20 mA Réglage d'usine : L'entrée analogique AI1 est attribuée en usine au capteur de pression différentielle (pour la variante R1 : pas attribuée) et réglée sur le signal 2 … 10 V. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 289
être réglées sur l'entrée analogique AI1 (voir Fig. 69 Entrée analogique AI1). Positions possibles du capteur de pression : • Bride de la pompe • Position conforme à la norme Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 290
être réglées sur l'entrée analogique AI1 (voir Fig. 69) - Entrée analogique AI1. Posi- tions possibles du capteur de pression : • Bride de la pompe • Position conforme à la norme Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 291
AI2 a préalablement été sélectionnée dans le menu. Pour cela, sélectionner suc- consigne cessivement dans le menu : Universel Texte d'affichage Réglages Réglage de la régulation 1.1.9 Source de la valeur de consigne 1.1.9 / 2 Entrée analogique (AI2) Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 292
Une vitesse de rotation (pour le mode de régulation « Vitesse de rotation constante n-c ») • Une hauteur manométrique (pour les modes de régulation « Pression différentielle Δp-v » et « Pression différentielle Δp-c ») Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 293
Tous les autres équipements ne peuvent pas avoir de terminaison active. Une adresse individuelle (Wilo Net ID) doit être attribuée à tous les équipements du bus. Cette adresse est paramétrée dans le menu de la pompe correspondante.
Pagina 294
Adresse Wilo Net Chaque pompe doit être attribuée à une adresse propre (1 … 2). AVIS La plage de réglage de l'adresse Wilo Net est 1 … 126 ; toutes les valeurs de la plage 22 … 126 ne doivent pas être utilisées. Fig. 82: Menu Adresse Wilo Net Exemple Pompe double :...
Pagina 295
Les langues suivantes sont disponibles : Code langue Langue Anglais Allemand Français Italien Espagnol UNIV Universel Finnois Suédois Portugais Norvégien Néerlandais Danois Polonais Hongrois Tchèque Roumain Slovène Croate Slovaque Serbe Letton Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 296
Réglages Réglages de l'écran 1.5.3 Unités m, m³/h m, m kPa, m³/h kPa, m kPa, l/s kPa, l/s ft, USGPM ft, USGPM Possibilité de sélection des unités : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 297
« Kick » de la pompe : Vitesse de rotation 1.6.2 Temps de réaction 1.6.2.1 Temps de réaction : Temps de démarrage 1.6.2.2 Temps de réaction : Temps d'arrêt 1.6.4 Diminution automatique de la fréquence PWM Désactivé Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 298
La plage de valeurs réglable pour l'augmentation et la réduction se situe entre 0 s et 180 s. Pour le réglage d'usine, voir le chapitre « Réglage d'usine » [” 305]. Fig. 86: Menu Temps de réaction Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 299
Informations sur l'erreur Current status: Not ener- Statut actuel : Hors tension gized Fig. 89: Menu Aides au diagnostic 2.1.4 Aperçu entrée analogique (AI1) Type of use: Type d'utilisation : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 300
« Diagnostic et valeurs mesurées », « Aides au diagnostic » comporte des fonctions de diagnostic et d'entretien de l'électronique et des interfaces. Le tableau suivant donne un aperçu du menu « Aides au diagnostic » : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 301
à l'entretien du produit. Pour cela, sélectionner : Universal Texte d'affichage Diagnostic et valeurs mesurées Informations de service Aides au diagnostic 2.1.2 Informations de service Fig. 91: Menu Informations de service Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 302
Dans le menu « Diagnostic et valeurs mesurées », il est possible de voir les informa- AI1 et AI2 tions sur les entrées analogiques AI1 et AI2. Pour cela, sélectionner : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 303
Aperçu de l'état permutation des Dans le menu « Diagnostic et valeurs mesurées », il est possible de voir les informa- pompes tions sur l'état de permutation des pompes. Pour cela, sélectionner : Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 304
• Données statistiques n réel = 3 800/min – Puissance électrique absorbée additionnée P électr. = 6 W – Heures de service U réseau = 0 V Fig. 99: Données d'exploitation Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 305
Pompe double : connec- tée Permutation pompe double 24 h 24 h Interfaces externes Relais SSM Fonction relais SSM Erreurs seulement Erreurs seulement Retard de déclenchement Retard de réinitialisation Relais SBM Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 306
Si l'état technique le permet, une panne est surveillée en continu et si possible, un régime de secours ou le mode de régulation est rétabli. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 307
Exists since: Depuis Acknowledge needed Confirmation nécessaire For acknowlege long Pour acquitter, appuyer longuement sur la touche press knob Acknowleged, waiting for Acquitté, en attente du redémarrage restart Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 308
Informations supplémentaires sur les causes et le remède : Afin d'assurer une aération suffisante, respecter la position de montage et l'écart minimum entre les composants d'isolation et les composants de l'installation. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 309
(régime de secours). En fonction de la cause de l'avertissement, le régime de secours limite la fonction de ré- gulation jusqu'au retour à une vitesse de rotation fixe. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 310
Informations supplémentaires sur les causes et le remède : Le circulateur peut démarrer malgré l'écoulement. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 311
GTB incorrecte. La communication est coupée. Informations supplémentaires sur les causes et le remède : Les fonctions de régulation sont perturbées. Une fonction équivalente est active. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 312
Informations supplémentaires sur les causes et le remède : Le circulateur fonctionne. Si la tension continue d'augmenter, la pompe s'éteint. Des tensions trop élevées peuvent endommager la pompe. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 313
Travaux de montage/démontage : Le technicien qualifié doit être formé à l'utilisation des outils nécessaires et matériels de fixation requis. Il est recommandé de faire entretenir et contrôler la pompe par le service après-vente Wilo. DANGER Risque de blessures mortelles par électrocution ! Un comportement inapproprié...
Pagina 314
Le fonctionnement normal de la pompe n'est autorisé que lorsque le mo- dule électronique est monté. • Ne jamais raccorder ou faire fonctionner la pompe sans le module électronique monté ! Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 315
également habituelle, même lorsque la pompe fonctionne normalement. Un contrôle visuel régulier est nécessaire. Si la fuite est clairement visible, remplacer le joint d'étanchéité. Informations complémentaires, voir les Informations à destination des prescripteurs Wilo Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 316
14. Retirer la roue (Fig. II, pos. 21) de l'arbre. 15. Retirer la bague de sécurité arrière (Fig. I, pos. 36b) de l'arbre. 16. Retirer la bague entretoise (Fig. I, pos. 20) de l'arbre. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 317
33. Utiliser les deux trous taraudés adjacents (Fig. 104, pos. 1) ainsi que les vis appropriées fournies par le client (p. ex. M10 x 25 mm) pour éjecter le kit embrochable du corps de pompe. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 318
17. Lorsque le guidage de la lanterne est sensiblement engagé (environ 15 mm avant la po- sition finale), il n'y a plus de risque de basculement ou de coincement. Après avoir sécu- Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 319
• Vérifier l'absence de tension et recouvrir ou empêcher l'accès aux pièces sous tension ! • Fermer les dispositifs d'arrêt en amont et en aval de la pompe ! Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 320
Avant le montage du module électronique, monter le nouveau joint torique (Fig. I, pos. 31) entre le module électronique (Fig. I, pos. 1) et l'adaptateur moteur (Fig. I, pos. 11) sur le dôme de contact. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 321
Enfoncer le module électronique dans les contacts du moteur neuf, puis le fixer avec les vis (Fig. I, pos. 4). Restaurer la disponibilité opérationnelle de la pompe : Voir le chapitre « Remplacement de la garniture mécanique » [” 315] ; étapes 5 … 1. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 322
Fig. 105: Ouvrir le couvercle du module élec- tronique Retirer le câble de raccordement du ventilateur du module. Fig. 106: Débrancher le câble de raccorde- ment du ventilateur du module Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 323
Numéros de pièces de rechange, désignations de pièces de rechange, en- semble des données de la plaque signalétique de la pompe et de l'entraî- nement. Les demandes de précisions et les erreurs de commande sont ainsi évitées. Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 324
été acheté. Pour davantage d'informations sur le recyclage, voir le site www.wilo‑recycling.com. Sous réserve de modifications techniques ! Notice de montage et de mise en service • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 325
12.7 Toepassing en functie van de analoge ingangen AI1 en Type-aanduiding ............. 336 AI2 .................. 395 Technische gegevens............ 336 12.8 Toepassing en functie van de Wilo Net-interface .. 401 Leveringsomvang............. 338 12.9 Toepassing en functie van de CIF-module.... 402 Toebehoren............... 339 13 Displayinstellingen.............. 402 5 Transport en opslag ..............
Pagina 326
20 Afvoeren................. 430 20.1 Oliën en smeermiddelen .......... 431 20.2 Informatie over het inzamelen van gebruikte elektrische en elektronische producten ........... 431 Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 327
Alle rechten voorbehouden. Voorbehoud van wijziging Wilo behoudt zich het recht voor om de genoemde gegevens zonder aankondiging vooraf te wijzigen en is niet aansprakelijk voor technische onnauwkeurigheden en/of lacunes. De gebruikte afbeeldingen kunnen afwijken van het origineel en dienen slechts als voorbeeld- weergaven van het product.
Pagina 328
De naam van het hoofdstuk of de tabel staat tussen aanhalings- tekens „ ”. Het paginanummer volgt daarna tussen vierkante haakjes [ ]. Personeelskwalificatie Het personeel moet: • Geïnstrueerd zijn over de plaatselijk geldige ongevallenpreven- tievoorschriften. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 329
De technische voorschriften, zoals vermeld in deze inbouw- en bedieningsvoorschriften en op het typeplaatje, moeten worden opgevolgd. • Aard het product. • Als het product op elektrische schakelinstallaties wordt aange- sloten, moeten de voorschriften van de fabrikant worden opge- volgd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 330
Het is verboden om zich onder een gehesen last te bevinden. Lasten mogen niet over werkplekken worden gevoerd, waar zich personen bevinden. Montage-/demontage- • Draag een beschermingsuitrusting: werkzaamheden Veiligheidsschoenen – Veiligheidshandschoenen tegen snijwonden – Veiligheidshelm (bij toepassing van hijsmiddelen) – Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 331
Plichten van de gebrui- • Stel de inbouw- en bedieningsvoorschriften in de taal van het personeel ter beschikking. • Zorg voor de vereiste opleiding van het personeel voor de aan- gegeven werkzaamheden. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 332
De droogloperpompen van de serie Yonos GIGA2.0 zijn bestemd voor gebruik als circulatie- Toepassing pompen in de gebouwentechniek. Ze mogen worden gebruikt voor: • Warmwater-verwarmingssystemen • Koel- en koudwatercircuits • Industriële circulatie-installaties • Warmtedragercircuits Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 333
Fig. I/II en Fig. III geven een explosietekening weer van de pomp met de hoofdcomponen- ten. Hierna wordt de opbouw van de pomp in detail toegelicht. Toewijzing van de hoofdcomponenten volgens Fig. I/II en Fig. III van de tabel “Toewijzing van de hoofdcomponenten”: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 334
Compensatieschijf van de klep van de dubbelpomp (alleen DN 100…DN 125) As van de klep van de dubbelpomp (alleen DN 100…DN 125) Sluitplug voor het boorgat van de as, 2x (alleen DN 100…DN 125) Borgring Borgring Vlakke spie Lantaarnvenster Tab. 1: Toewijzing van de hoofdcomponenten Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 335
DN 32 ... DN 80: met geïntegreerde pomplantaarn DN 100 ... DN 125 tot een motorvermogen van 4,0 kW: Lan- taarnstuk van de motorflens kan worden gedemonteerd. DN 100 ... DN 125 bij motorvermogen 5,5 ... 7,5 kW; met ge- Fig. 3: Functiemodules ïntegreerde pomplantaarn. Elektronicamodule Elektronica-eenheid Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 336
3~380 V...3~440 V (±10%), Ondersteunde netsoorten: 50/60 Hz TN, TT, IT Spanningsbereik 1~220 V – 1~240 V (± 10%), Ondersteunde netsoorten: 50/60 Hz TN, TT, IT Vermogensbereik 3~ 0,55 kW ... 7,5 kW Afhankelijk van het pomp- type Vermogensbereik 1~ 0,37 kW – 1,5 kW Afhankelijk van het pomp- type Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 337
Standaarduitvoering Koel-/koud water Standaarduitvoering Water-glycol-mengsel tot 40% vol. Standaarduitvoering Water-glycol-mengsel tot 50% vol. Alleen bij speciale uitvoe- Thermische olie ring Andere vloeistof Alleen bij speciale uitvoe- ring Alleen bij speciale uitvoe- ring Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 338
EMC-onregelmatigheden optreden bij toepassing in huis- houdelijke omgevingen (C1) met een laag elektrisch vermogen in het geleide bereik. Neem in dit geval contact op met WILO SE om samen een snelle en geschikte uitschakel- functie te vinden. Yonos GIGA2.0-I/-D is in de zin van EN 61000-3-2 een professioneel apparaat.
Pagina 339
Bescherm het product bij transport en opslag tegen vocht, vorst en me- chanische beschadiging. Sticker op de leidingaansluitingen laten zitten, zodat er geen vuil of andere vreemde voor- werpen in het pomphuis terechtkomen. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 340
Draai de pompas eenmaal per week met een steeksleutel (zie Fig. 5) om de vorming van groeven op de lagers en vastkleven te voorkomen. Informeer bij Wilo welke conserveringsmaatregelen moeten worden genomen wanneer een langere opslagtijd noodzakelijk is. WAARSCHUWING Gevaar voor letsel door verkeerd transport! Indien de pomp op een later tijdstip opnieuw wordt vervoerd, moet deze op een voor het transport veilige manier worden verpakt.
Pagina 341
• Stel de beschermingsuitrusting ter beschikking en zorg ervoor dat deze door het personeel wordt gedragen. • Alle voorschriften voor het werken met zware lasten in acht ne- men. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 342
Letsel door sterke magnetische krachten! Het openen van de motor veroorzaakt grote, plotseling optredende mag- netische krachten. Deze kunnen tot ernstige verwondingen leiden door snijden, beknellen of stoten. • Motor niet openen! Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 343
In de meeste gevallen volstaat het draaien van de insteekset relatief aan het pomphuis. De mogelijke opstelling van de componenten is afhankelijk van de toegestane inbouwposities. Fig. 8: Opstelling van de componenten bij le- vering Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 344
Bij dubbelpompen kunnen de beide insteeksets niet naar elkaar toe draaien ten opzichte van de draaiassen vanwege de afmetingen van de elektronicamodule. Fig. 10: Toegestane inbouwposities met ver- ticale motoras 6.4.3 Draaien van de insteekset De insteekset bestaat uit een waaier, lantaarnstuk en motor met elektronicamodule. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 345
Fig. 11: Afdrukken van de insteekset via Als de O-ring is verwijderd, maak de O-ring (Fig. I, pos. 19) dan vochtig en leg deze in draadboringen (DN 100…DN 125) het pomphuis (DN 32…DN 80) of in het lantaarnstuk (DN 100…DN 125). Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 346
Een onbeschadigde mechanische afdichting kan opnieuw worden ge- bruikt. Laat 2 transportogen (Fig. I, pos. 30) op de motorflens zitten. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 347
(zie de tabel 'Schroeven en aandraaimomenten' [” 348]). 18. Verwijder de steeksleutel en monteer het beschermplaatje (Fig. II, pos. 27) weer. 19. Als de O-ring is beschadigd: Maak de groef van het lantaarnstuk schoon en plaats de nieuwe o-ring (Fig. II, pos. 19). Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 348
Handvast Monteren met WEI- ding capillaire ting CONLOCK buis naar het AN 305-11 pomphuis 0° Schroefverbin- Fig. I, pos. 6 M8x1 mes- Alleen vernikkelde ding capillaire sing vernik- moeren (CV) buis, wartelmoer keld 90° Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 349
(bijv. vervangen van de mechanische afdichting) of vervanging mogelijk. • Installeer boven de opstelplaats van grote pompen een voorziening voor het aanbrengen van een hijswerktuig. Totaalgewicht van de pomp: zie de catalogus of het gegevensblad. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 350
• Bevestig de leidingen zo dat het gewicht van de leidingen niet door de pomp wordt ge- dragen. • Voordat de leidingen worden aangesloten, moet de installatie worden gereinigd en ge- spoeld. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 351
1525 Waarden conform NEN-EN-ISO 5199 – klasse II (2002) – bijlage B Tab. 7: Toegestane krachten en momenten op de pompflenzen in een verticale leiding Fig. 14: Belastingsgeval 16A, EN ISO 5199, bijlage B Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 352
Voor hogere temperaturen moeten de waarden als volgt worden gecorrigeerd, afhankelijk van de verhouding van de elasticiteitsmodules: / E t, gietijzer 20, gietijzer = elasticiteitsmodule gietijzer bij de gekozen temperatuur t, GG = elasticiteitsmodule gietijzer bij 20 °C 20, GG Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 353
De verschil- druksensor is op deze pomp gemonteerd. De kabel voor de buscommuni- catie Wilo Net is af fabriek eveneens op deze pomp gemonteerd en ge- configureerd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 354
De kabelverbinding wordt op een van de analoge in- gangen aangesloten. De verschildruksensor wordt in het pompmenu geconfigureerd. Mo- gelijke signaaltypes op verschildruksensoren: • 0 ... 10 V • 2...10 V • 0 ... 20 mA • 4...20 mA Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 355
• Alle aansluitingen (ook potentiaalvrije contacten) op spanningsvrij- heid controleren! • Steek nooit voorwerpen (bijv. spijker, schroevendraaier, draad) in ope- ningen op de elektronicamodule! • Monteer gedemonteerde veiligheidsvoorzieningen (bijv. moduledek- sel) weer! Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 356
Op de elektronicamodule bevinden zich 6 kabeldoorgangen naar de klemmenkast. De kabel voor de voedingsspanning van de elektrische ventilator op de elektronicamodule is af fa- briek gemonteerd. De eisen met betrekking tot de elektromagnetische compatibiliteit moeten in acht worden genomen. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 357
0...20 mA, 4...20 mA (alleen verschildruksensor) Analoge ingang 2 Metaal met afscherming 4, 5, 6 4, 5 (Fig. 20, Fig. 21) 0...10 V, 2...10 V, 0...20 mA, 4...20 mA (Externe gewenste waarde) CIF-module Metaal met afscherming 4, 5, 6 (buscommunicatie) Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 358
Ze kunnen met een sleufschroevendraaier van het type SFZ 1 - 0,6 x 0,6 mm worden geopend. Lengte van de te verwijderen isolatie De te isoleren lengte van de kabels voor de klemaansluiting bedraagt 8,5 mm...9,5 mm. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 359
Fig. 20: Overzicht klemmen in de module 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Fig. 21: Klemmen voor analoge ingangen, digitale ingangen en Wilo Net LET OP AI3 en AI4 (klemmen 6 – 10) alsmede DI2 (klemmen 13 en 14) zijn niet be- zet.
Pagina 360
Stroomtype en spanning op het typeplaatje in acht nemen. Breng de elektrische aansluiting tot stand via een vaste aansluitkabel met een stekker of een meerpolige schakelaar met een contactopening van ten minste 3 mm breed. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 361
Wanneer een lekstroom-veiligheidsschakelaar (RCD) of lekstroom- bewakingsapparaat (RCM) wordt gebruikt ter bescherming bij direct of in- direct contact, is aan de stroomtoevoerzijde van dit product alleen een RCD of RCM van het type B toegestaan. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 362
LET OP Als er twee kabels op een 24 V-voedingsklem moeten worden aangeslo- ten, moet er niet inbegrepen een oplossing beschikbaar worden gesteld! Er mag slechts één kabel per klem op de pomp worden aangesloten! Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 363
Bij de Yonos GIGA2.0-D is de Wilo Net-kabel voor de dubbelpompcom- municatie af fabriek op beide elektronicamodules gemonteerd. Om de Wilo Net verbinding tot stand te brengen, moeten de 3 klemmen H, L, GND met een communicatieleiding van pomp tot pomp worden bedraad.
Pagina 364
Pomp 2 ingeschakeld Tab. 13: Wilo Net bekabeling Aantal Wilo Net deelnemers: Bij dubbelpompen bestaat het Wilo Net uit twee deelnemers, waarbij elke knoop als deel- nemer telt. • Dubbelpomp = 2 deelnemers (bijv. ID 1 en 2) Zie voor de overige beschrijvingen het hoofdstuk „Toepassing en functie van de Wilo Net- interface”...
Pagina 365
Bij dubbelpompen hoeft alleen de hoofdpomp met een CIF-module uitgerust te worden. • Bij pompen in Y-buistoepassingen, waarbij de elektronicamodules met elkaar zijn ver- bonden via Wilo Net, heeft ook alleen de hoofdpomp een CIF-module nodig. LET OP Bij gebruik van de CIF-module Ethernet wordt het gebruik van het toe- behoren „Aansluiting M12 RJ45 CIF-Ethernet”...
Pagina 366
Afhankelijk van de systeemdruk kan de vloeistof er onder hoge druk uitschieten. • Open de ontluchtingsvoorziening altijd heel voorzichtig. • Bescherm de elektronicamodule bij het ontluchten tegen lekkend wa- ter. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 367
Bij het resetten naar de fabrieksinstelling is de digitale ingang DI1 weer actief. Zonder ka- belbrug start de pomp niet. Zie het hoofdstuk 'Toepassing en functie van de digitale bestu- ringsingang' [” 392]. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 368
9.4.2 Instellingen op de pomp Instellingen worden uitgevoerd door draaien en drukken van de bedieningsknop. Door de bedieningsknop naar links of naar rechts te draaien wordt door de menu's genavigeerd of er Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 369
Door het draaien van de bedieningsknop verschijnen de diverse menutalen. De volgende ta- len kunnen worden geselecteerd: Language Afkorting taal Taal Engels Duits Frans Italiaans Spaans UNIV Universeel Fins Fig. 28: Menu eerste instelling Zweeds Portugees Noors Nederlands Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 370
De fabrieksinstelling bij variant ... R1 (zonder verschildruksensor bij de le- vering) is de basisregelingsmodus 'Constant toerental'. De hierna genoem- de fabrieksinstelling heeft betrekking op de variant met een af fabriek in- gebouwde verschildruksensor. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 371
Actieve invloeden Weergave van invloeden op het ingestelde regelbedrijf bijv. EXT. UIT. Er kunnen tot vier actieve invloeden worden weergegeven. Wanneer een dubbelpomp is ingesteld, wordt hier de status van de dubbelpomp weergegeven. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 372
Elk submenu bestaat uit een lijst van submenu-items. 9.4.6 Het submenu De titel benoemt een ander submenu of een volgende instellingsdialoog. De volgende tabel geeft een overzicht van het hoofdmenu 'Instellingen': 9.4.7 Hoofdmenu 'Instellingen' - menu- overzicht Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 373
'AAN'. menu-item verschijnt alleen, wanneer de analoge ingang AI2 als gewenste waardebron is geselecteerd. 9.4.8 Hoofdmenu 'Instellingen' In het menu „Instellingen” kunnen verschillende instellingen worden uitgevoerd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 374
De eerder veranderde waarde wordt verworpen, omdat hij niet werd bevestigd. Om ingestelde parameters te controleren, kan door drukken van de bedieningsknop van parameter naar parameter worden gewisseld. Bestaande parameters worden daarbij op- nieuw bevestigd, maar niet veranderd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 375
Tab. 20: Mogelijke weergaven in het statusbereik LET OP Terwijl een proces loopt, wordt een ingesteld regelbedrijf onderbroken. Na beëindiging van het proces loopt de pomp verder in het ingestelde regel- bedrijf. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 376
De werkingsrichting van de regeling kan worden ingesteld door de regelomkering in of uit te schakelen. 10.2 Selectie van de regelingsmodus In het menu 'Instellingen' (Universal 1.0) kunnen de volgende submenu's worden gese- lecteerd: Universal Displaytekst Regelingsinstelling Externe interfaces Dubbelpompmanagement Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 377
'Gewenste waarde ∆p-c'. De gewenste opvoerhoogte kan als gewens- Fig. 40: Instelling van gewenste waarde Δp-v te waarde worden ingesteld. Na bevestiging van de gewenste waarde verschijnt opnieuw het menu 'Regelingsinstelling'. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 378
De gewenste waardebron 'Interne gewenste waarde' is in te stellen in het display. De ge- wenste waardebronnen 'Analoge ingang AI2' en 'CIF-module' verwachten een gewenste CIF-module waarde van een externe bron. Fig. 42: Instellen van de gewenste waarde- bron Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 379
Instellingen toerental Regelingsinstelling 1.1.8 Noodtoerental 3800/min Menu-item verschijnt alleen, wanneer noodbedrijf is ingeschakeld op 'AAN'. Na bevestiging van de gewenste waarde voor het noodtoerental verschijnt opnieuw het me- nu 'Regelingsinstelling'. Fig. 45: Noodtoerental Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 380
Daarbij is de mogelijke pieklast beperkt door het vermogen van de afzonderlijke pomp. Het parallel bedrijf is ook met 2 enkelpompen van hetzelfde type in het dubbel- pompbedrijf in het broekstuk mogelijk. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 381
Stel vervolgens in het menu bij „Instellingen/Externe interfaces/Instelling Wilo Net” de terminering en het Wilo Net adres in. Voer daarna in het menu 'Instellingen', submenu 'Dubbelpompmanagement' de instellingen voor 'Dubbelpomp verbinden' in. LET OP Zie voor de installatie van 2 enkelpompen tot 1 dubbelpomp de hoofd-...
Pagina 382
Enkelpomp 1.4.5 / 2 Dubbelpomp (links): 1.4.5 / 3 Dubbelpomp (rechts): Bij nietbestaande dubbelpompaansluiting zijn de volgende instellingen mogelijk: • Dubbelpomp verbinden. • Pomphuistype Bij bestaande dubbelpompaansluiting zijn de volgende instellingen mogelijk: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 383
Dubbelpomp verbinden Voorbeeld: Aan pomp I is het Wilo Net-adres 1 toegewezen, aan pomp II het Wilo Net-adres 2. Dubbelpomppartner- In pomp I moet dan het adres 2 van de dubbelpomppartner en in pomp II adres 1 worden in- adres gesteld.
Pagina 384
LET OP Fig. 53: Menu dubbelpompfunctie Bij het omschakelen van de dubbelpompfunctie worden verschillende pa- rameters van de pomp fundamenteel veranderd. De pomp wordt daarna automatisch opnieuw gestart. Daarna verschijnt weer het hoofdmenu. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 385
In het menu 'Pomphuistype' is de volgende selectie ter beschikking: • Enkelpomphydrauliek Dubbelpompfunctie • Hydraulisch systeem dubbelpomp I (links in stroomrichting) • Hydraulisch systeem dubbelpomp II (rechts in stroomrichting) Pompwisseling Pomphuistype Fig. 55: Menu dubbelpompmanagement Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 386
In het bereik „Actieve invloeden” zijn tijdens het dubbelpompbedrijf 2 pompsymbolen zichtbaar. Deze hebben de volgende betekenis: Situatie 1 – hoofd-/reservebedrijf: alleen de hoofdpomp draait. Weergave op het display van de hoofdpomp Weergave op het display van de partner- pomp Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 387
Dubbelpomp is in hoofd-/reservebe- Deze pompkop is actief drijf ingesteld. Deze pompkop is in regelbedrijf actief. Hoofd-/reservebedrijf: Dubbelpomp is in hoofd-/reservebe- Partnerpomp actief drijf ingesteld. De pomppartner is in regelbedrijf ac- tief. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 389
De ESM-functie op het SSM-contact signaleert alleen storingen van de betreffende pomp (enkelstoringsmelding). Om alle storingen van beide pompen te registreren, moeten in beide aandrijvingen de contacten worden bezet. Fig. 61: Menu dubbelpomp SSM-relaisfunctie Universal Displaytekst Instellingen Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 390
(netwerkklaar) of als er geen storing actief is (bedrijfsklaar). Fabrieksinstelling: bedrijfsklaar. Beide contacten signaleren de bedrijfstoestand van de dubbelpomp parallel (verzamelbedrijfsmelding). Afhankelijk van de configuratie ligt het contact op NO of NC. In het menu het volgende selecteren: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 391
Deze submenu's verschijnen alleen bij een aangesloten dubbelpomp. Een SBM-relais geforceerde besturing dient als functietest van het SBM-relais en van de 12.5 Dwangsturing SBM-relais elektrische aansluitingen. In het menu het volgende selecteren: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 392
Wordt niet gebruikt 1.3.2.1 / 2 Extern Off 1.3.2.2 Dubbelpomp Ext. Off-functie 1.3.2.2 / 1 Systeemmodus 1.3.2.2 / 2 Enkelmodus 1.3.2.2 / 3 Combi-modus submenu verschijnt alleen bij een aangesloten dubbelpomp Mogelijke instellingen: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 393
De besturingsingang DI1 is af fabriek voorzien van een brug en de functie 'Ext. Off' is actief. Elk van beide pompen wordt apart door de eigen besturingsingang geschakeld. Als de hoofdpomp uitvalt of als de dubbelpompverbinding wordt verbroken, dan wordt de bestu- ringsingang van de partnerpomp geanalyseerd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 394
De 24 V DC-voedingsspanning is pas beschikbaar wanneer de analoge in- gang AI1 of AI2 op een soort gebruik en een signaaltype is geconfigureerd of wanneer de digitale ingang DI1 is geconfigureerd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 395
De volgende tabel geeft een overzicht van het menu 'Analoge ingang AI1 en AI2': Universal Displaytekst 1.3.3 Analoge ingang (AI1) 1.3.3.1 Signaaltype 1.3.3.2 Druksensorbereik 1.3.3.3 Druksensorpositie 1.3.3.3 / 1 Pompflens 1.3.3.3 / 2 Positie normconform 1.3.4 Analoge ingang (AI2) 1.3.4.1 Signaaltype Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 396
Signaaltype 2…10 V / 4…20 mA Fig. 70: Menu signaaltypen Fabrieksinstelling: De analoge ingang AI1 is af fabriek voorzien van de verschildruksensor (bij variant R1: niet voorzien) en op signaaltype 2 ... 10 V ingesteld. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 397
(bijv. op een pompvariant R1), moet op de analoge ingang AI1 het druksensorbereik en de druksensorpositie worden ingesteld (zie Fig. 69 Analoge ingang AI1). Mogelijke druksensor- posities: • Pompflens • Positie conform standaard Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 398
(bijv. op een pompvariant R1), moet op de analoge ingang AI1 het druksensorbereik en de druksensorpositie worden ingesteld (zie Fig. 69) – Analoge ingang AI1. Mogelijke druksen- sorposities: • Pompflens • Positie conform standaard Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 399
AI2 ervoor in het menu werd geselecteerd. Selecteer daarbij in het menu ach- tereenvolgens het volgende: Universeel Displaytekst Instellingen Regelingsinstelling 1.1.9 Gewenste waardebron 1.1.9 / 2 Analoge ingang (AI2) Via het menu 'Instellingen', 'Externe interfaces', 'Analoge ingang AI2' wordt het signaal- type ingesteld. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 400
1.1.10 Vervangende gewenste waarde Signaaltype 0…10 V / 0… 20 mA: Wanneer bij de analoge ingang AI2 een externe gewenste waarde wordt ingesteld, moet het signaaltype worden ingesteld. In dit geval 0…10 V of 0…20 mA. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 401
Alle andere deelnemers mogen geen geacti- veerde afsluiting hebben. Aan alle busdeelnemers moet een individueel adres (Wilo Net ID) worden toegewezen. Dit adres wordt in het pompmenu van de betreffende pomp ingesteld. Selecteer voor het uitvoeren van de stopzetting van de pompen het volgende:...
Pagina 402
Wanneer de pomp aan het einde van de elektrische buslijn is aangesloten, moet „In- Fig. 81: Menu Wilo Net-terminering geschakeld” worden geselecteerd. Nadat de stopzetting is uitgevoerd, wordt aan de pompen een individueel Wilo Net-adres toegewezen. Selecteer voor het toewijzen van het Wilo Net-adres het volgende: Universal...
Pagina 403
Afkorting taal Taal Engels Duits Frans Italiaans Spaans UNIV Universeel Fins Zweeds Portugees Noors Nederlands Deens Pools Hongaars Tsjechisch Roemeens Sloveens Kroatisch Slowaaks Servisch Lets Litouws Ests Russisch Verenigd Koninkrijk Oekraïens Bulgaars Grieks Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 404
• Opvoerhoogte in m kPa, m Weergave van de opvoerhoogte in kPa en van de debietstroom in m kPa, l/s Weergave van de opvoerhoogte in kPa en van de debietstroom in l/s Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 405
Om blokkeren van de pomp te voorkomen, wordt een pomp-kick op de pomp ingesteld. Na 14.1 Pomp-kick een ingesteld tijdsinterval start de pomp op en schakelt na korte tijd weer uit. Voorwaarde: Voor de functie pomp-kick mag de netspanning niet worden onderbroken. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 406
Het in te stellen waardebereik voor het opstarten en afsluiten ligt tussen 0 s en 180 s. Zie voor de fabrieksinstelling het hoofdstuk 'Fabrieksinstelling' [” 413]. Fig. 86: Menu acceleratietijden 14.3 Automatische PWM-frequentie- In het menu 'Instellingen', 'Extra instellingen' kan de functie 'Automatische PWM-fre- vermindering quentievermindering' in- en uitgeschakeld worden: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 407
Current status: Not ener- Actuele status: Geen spanning gized Fig. 89: Menu diagnosehulpmiddelen 2.1.4 Overzicht analoge ingang (AI1) Type of use: Gebruikswijze: Not used Wordt niet gebruikt Differential pressure sen- Verschildruksensor External sensor Externe sensor Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 408
'Diagnosehulpmiddelen en meetwaarden' bevinden zich functies voor dia- gnose en onderhoud van elektronica en interfaces. De volgende tabel geeft een overzicht via het menu 'Diagnosehulpmiddelen': Universal Displaytekst Diagnosehulpmiddelen 2.1.1 Apparaatgegevens 2.1.2 Service-informatie Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 409
Selecteer daarbij het volgende: Universal Displaytekst Diagnose en meetwaarden Service-informatie Diagnosehulpmiddelen 2.1.2 Service-informatie Fig. 91: Menu service-informatie 15.4 Foutdetails Universal Displaytekst Diagnose en meetwaarden Foutdetails Diagnosehulpmiddelen Fout: E420 2.1.8 Foutdetails 1: 0x10000F04 Fig. 92: Menu foutdetails Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 410
Overzicht analoge ingang (AI2) Type of use: Gebruikswijze: Not used Wordt niet gebruikt External sensor Externe sensor Setpoint input Ingang gewenste waarde Signal type: Signaaltype: Current value: : Actuele waarde: De volgende statusinformatie is aanwezig: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 411
Actuele status: Geen pomp draait/beide pompen draaien/hoofdpomp draait/pomppartner draait. • Tijd tot de volgende pompwisseling 15.10 Meetwaarde In het menu 'Diagnose en meetwaarden' kunnen bedrijfsgegevens, meetwaarden en statistische waarden worden afgelezen. Selecteer daarbij achtereenvolgens het volgende: Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 412
Selecteer daarbij het volgende: Universal Displaytekst Fabrieksinstelling Fabrieksinstelling Terug naar fabrieksinstelling Terug naar fabrieksinstelling Confirm Bevestigen (instellingen gaan verloren!) CANCEL Afbreken Fig. 101: Terug naar fabrieksinstelling zetten Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 413
Pomp-kick tijdsinterval 24 u 24 u Diagnose en meetwaarden Diagnosehulpmiddel SSM-dwangsturing (normaal, niet actief niet actief actief, niet actief) SBM-dwangsturing (normaal, niet actief niet actief actief, niet actief) Extra instellingen Pomp-kick ingeschakeld ingeschakeld Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 414
Pomp maakt geluiden. leren. Laat de pomp, indien no- dig, repareren. Tab. 34: Mechanische storingen 17.2 Foutmeldingen Weergave van een foutmelding op het grafische display • De statusaanduiding is rood ingekleurd. • Foutmelding, foutcode (E...). Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 415
Afzettingen en vreemde voorwerpen wegnemen. Extra informatie over oorzaken en oplossing: Behalve door afzettingen en vreemde voorwerpen in het systeem kan de pompas ook blokkeren. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 416
Motor en/of elektronicamo- dule defect. module defect. dule vervangen. Extra informatie over oorzaken en oplossing: De pomp kan niet vaststellen, welk van de beide onderdelen defect is. Contact opnemen met de service. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 417
Extra informatie over oorzaken en oplossing: Als de tegengestelde stroming door de pomp te groot wordt, kan de motor niet meer worden gestart. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 418
Extra informatie over oorzaken en oplossing: Binaire ingangen zijn belemmerd. Functies van de binaire ingangen zijn niet be- schikbaar. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 419
Er is een defect aan de Display- en bedieningseen- eenheid defect. display- en bedie- heid vervangen. ningseenheid vastge- steld. Extra informatie over oorzaken en oplossing: De display- en bedieneenheid is als reserveonderdeel verkrijgbaar. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 420
Installatie-/demontagewerkzaamheden: De monteur moet een opleiding hebben ge- volgd voor de omgang met de noodzakelijke gereedschappen en bevestigingsmateria- len. Het wordt aanbevolen om de pomp door de Wilo-servicedienst te laten onderhouden en controleren. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 421
• Controleer of ze spanningsvrij zijn en dek aangrenzende, onder span- ning staande onderdelen af of sluit ze af! • Sluit de afsluiters voor en achter de pomp! Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 422
Levensgevaar door vallende onderdelen! Als de pomp of afzonderlijke onderdelen vallen, kan dit tot levensgevaar- lijk letsel leiden! • Beveilig de onderdelen van de pomp bij installatiewerkzaamheden met geschikte hijswerktuigen tegen vallen. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 423
Doe regelmatig een visuele controle. Als er duidelijk sprake is van een lekkage, vervang dan de afdichting Zie voor meer informatie ook de Wilo-ontwerprichtlijnen voor droogloperpompen. Wilo biedt een reparatieset aan, die de vereiste onderdelen voor vervanging bevat. LET OP De magneet aan de binnenkant van de motor vormt geen gevaar voor personen met pacemakers, zolang de motor niet is geopend of de rotor is gedemonteerd.
Pagina 424
30. Zittingvlakken van de as en het lantaarnstuk zorgvuldig schoonmaken. ⇒ Uitvoering DN 100 ... DN 125, 5,5 kW tot 7,5 kW, Fig. III 31. Verwijder de insteekset (zie hoofdstuk „Beschrijving van de pomp”) door de flens- schroeven (Fig. I/III, pos. 29) van het pomphuis los te draaien. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 425
14. Maak de groef van het lantaarnstuk schoon en plaats de nieuwe o-ring (Fig. II, pos. 19). 15. Bevestig de insteekset ter beveiliging met geschikte hijsmiddelen aan de transportogen. Bij het bevestigen voorkomen dat de kunststofdelen zoals koelwaaier en bovenstuk van de elektronicamodule worden beschadigd. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 426
18.2.2 Motor/aandrijving vervangen Hardere lagergeluiden en ongebruikelijke vibraties duiden op slijtage van het lager. De la- gers of motor moeten dan worden vervangen. Laat de aandrijving uitsluitend door de Wilo- servicedienst vervangen! Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 427
Trek de nieuwe O-ring (Fig. I, pos. 31) tussen elektronicamodule (Fig. I, pos. 1) en mo- toradapter (Fig. I, pos. 11) op de houder met contacten, voordat u de elektronicamo- dule monteert. Druk de elektronicamodule in het contact van de nieuwe motor en bevestig deze met schroeven (Fig. I, pos. 4). Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 428
De elektronicamodule kan zonder risico's worden ver- vangen. Voer voor het demonteren van de elektronicamodule de stappen 1…5 uit volgens het hoofdstuk 'Vervangen van mechanische afdichting' [” 423]. Verwijder de schroeven (Fig. I, pos. 4) en trek de elektronicamodule van de motor. Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 429
1…5 uit het hoofdstuik 'Mechanische afdichting vervangen' [” 423] Demontage van de ventilator: Open de afdekking van de elektronicamodule. Fig. 105: Afdekking elektronicamodule ope- Trek de aansluitkabel van de moduleventilator los. Fig. 106: Aansluitkabel van de moduleventi- lator losmaken Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 430
Reserveonderdelen Schaf originele reserveonderdelen uitsluitend via de vakhandel of de Wilo-servicedienst aan. Om vragen en verkeerde bestellingen te voorkomen, dienen bij elke bestelling alle ge- gevens op het typeplaatje van de pomp een aandrijving te worden vermeld. Typeplaatje pomp zie Fig. 2, pos. 1.
Pagina 431
Vraag naar informatie over de correcte afvoer bij de gemeente, de plaatselijke afvalverwer- kingsplaats of bij de verkoper van het product. Meer informatie over recycling is te vinden op www.wilo‑recycling.com. Technische wijzigingen voorbehouden! Inbouw- en bedieningsvoorschriften • Wilo-Yonos GIGA2.0-I/-D • Ed.02/2023-08...
Pagina 436
Local contact at www.wilo.com/contact WILO SE Wilopark 1 44263 Dortmund Germany T +49 (0)231 4102-0 T +49 (0)231 4102-7363 wilo@wilo.com Pioneering for You www.wilo.com...