User settings
ACCESS
You can access the installer settings in 3 steps. From the Auto, Comfort, Eco or Frost protection mode:
1
information
display
1
1 long press
5 seconds
Diagram of the sequence of settings:
Backlight
Eco setback level
Max. duration of boost
Maximum room temperature
BACKLIGHT SETTING
1- Three modes are available:
L1 =
timed backlighting: the screen lights up when a key is
pressed.
L2 =
permanent backlighting: the screen stays on all the time.
on all the time.
L3 =
In this version, the device will operate in L1 mode.
Press the
or
button to display the desired
setting
2. To confirm and move to the next setting, press
To exit the user settings, press twice
ADJUSTMENT OF THE ECO-LOWERING LEVEL
The set-back is preset to -3.5°C in relation to the Comfort
set-point temperature. You can vary it from -1°C to - 8°C
in 0.5°C increments.
Important: Regardless of the set reduction level, the
Eco setpoint temperature will never exceed 19°C.
3- Press
or
to display the desired value.
2
2 short
presses
Frost protection setpoint
Temperature unit
.
information
display
1
Super comfort setpoint limitation
4- To confirm and move to the next setting, press
To exit the user settings, press
SETTING THE FROST PROTECTION
TEMPERATURE
The unit is preset to 7°C, you can vary the Frost Protecti-
on setpoint from 5°C to 15°C in 0.5°C increments.
5- Press
or
6- To confirm and move to the next setting, press
To exit the user settings, press
SUPER COMFORT- ACTIVATION/
DEACTIVATION
By default, Super Comfort is activated.
SCF flashes, then YES appears on the display. The
The heat and boost indicators are displayed.
7- Press
or
Comfort.
YES =
Super comfort activated.
NO =
Super comfort deactivated
8- To confirm and move automatically to the next setting,
press
. To exit
User = user
settings
Comfort setpoint
twice.
to display the desired value.
twice.
to activate or deactivate the Super
.
3
1 short press
.
.
14