Parameter
naam
VERSTER-
41 PID 2
KING
INSTEL-
INTEGRATIE
LINGEN
TIJD
DIFFERENT
TIJD
PID DIFF
FILTER
INV FOUT-
WAARDE
EENHEID
SCHALING
EENHEID
0% WAARDE
100%
WAARDE
KEUZE
SETPOINT
INTERNE
SETPNT
SETPOINT
MIN
SETPOINT
MAX
TERUGKOP
SEL
TERUGKOP
VERMEN
WERK-
WAARDE 1
WERK-
WAARDE 2
WERKW 1
MIN
WERKW 1
MAX
WERKW 2
MIN
WERKW 2
MAX
SLAAP
KEUZE
PID SLAAP
NIVO
PIDWEK
VERTR
WEK DEEL-
FACTOR
WEK VER-
TRAGING
358
ACH550-01 Gebruikershandleiding
HVAC
Toevoer-
standaard
ventilator
Par.
index
1
2
4101
2.5
1.0
4102
3.0 s
60.0 s
4103
0.0 s
0.0 s
4104
1.0 s
1.0 s
4105
NEE
NEE
4106
%
%
4107
1
1
4108
0.0%
0.0%
4109
100.0%
100.0%
4110
PANEEL
PANEEL
4111
40.0%
40.0%
4112
0.0%
0.0%
4113
100.0%
100.0%
4114
WERKW1
WERKW1
NIET
NIET
4115
GESELEC
GESELEC
4116
AI2
AI2
4117
AI2
AI2
4118
0%
0%
4119
100%
100%
4120
0%
0%
4121
100%
100%
NIET
NIET
4122
GESELEC
GESELEC
4123
0.0 Hz
0.0 Hz
4124
60.0 s
60.0 s
4125
0.0%
0.0%
4126
0.50 s
0.50 s
Lijst en beschrijvingen van parameters
Retour-
Koeltoren-
ventilator
ventilator Condensor
3
4
1.0
1.0
60.0 s
60.0 s
60.0 s
0.0 s
0.0 s
1.0 s
1.0 s
NEE
NEE
%
%
1
1
0.0%
0.0%
100.0%
100.0%
100.0%
PANEEL
PANEEL
PANEEL
40.0%
40.0%
40.0%
0.0%
0.0%
100.0%
100.0%
100.0%
WERKW1
WERKW1
WERKW1
NIET
NIET
GESELEC
GESELEC
GESELEC
AI2
AI2
AI2
AI2
0%
0%
100%
100%
0%
0%
100%
100%
NIET
NIET
GESELEC
GESELEC
GESELEC
0.0 Hz
0.0 Hz
0.0 Hz
60.0 s
60.0 s
60.0 s
0.0%
0.0%
0.50 s
0.50 s
0.50 s
Booster
pomp
5
6
1.0
1.0
60.0 s
0.0 s
0.0 s
1.0 s
1.0 s
NEE
NEE
%
%
1
1
0.0%
0.0%
100.0%
PANEEL
40.0%
0.0%
0.0%
100.0%
WERKW1
NIET
NIET
GESELEC
AI2
AI2
AI2
AI2
0%
0%
100%
100%
0%
0%
100%
100%
NIET
NIET
GESELEC
0.0 Hz
60.0 s
0.0%
0.0%
0.50 s