SET COMP#1 SPs (1)
Demand Limit=OFF
Minimum Amps=040%
Maximum Amps=100%
SET COMP SPs
(2)
StageMode =Normal
StageSequence# = 01
Max Compr ON = 01
SET COMP SPs
(3)
o
StageDeltaT = 1.0
F
Stop-Start =
03 min
Start-Start = 40 min
SET COMP SPs
(4)
Full Load = 300 sec Name
Plate RLA 085
SET COMP SPs
(5)
Nom Capacity = 0100T
HotGasBypass = 30%
SET COMP SPs
(6)
InterLokTmr= 010sec
UnloadTimer = 030 sec
SET COMP SPs
(7)
EWWD Automatic
Vane Control
(blank mask page)
SET COMP SPs
(8)
MAX KW = 76.0
Lag Start = 000Sec
Step Down = 060Sec
SET COMP SPs
(9)
Protocol =M-BUS MSTR
Ident Number= 001
Baud Rate = 19200
SET COMP SPs
(10)
Refrg Sat Pressure
Evp Offset =+00.0 psi
Cnd Offset = +00.0psi
SET COMP SPs
(11)
o
ELWT Offset = +0.0
F
D - EOMWC00905-10NL - 80/96
SET-INSTELPUNTEN
SET ALARM LMTs (1)
LowEvPrHold=33psi
LowEvPrUnld=31psi
LowEvPrStop=29psi
SET ALARM LMTs (2)
HighCondPr =140psi
o
HiDschT-Load=170
F
o
HiDschT-Stop=190
F
SET ALARM LMTs (3)
EWWD Compressor
Oilless Design
(blank mask page)
SET ALARM LMTs (4)
o
Surge Slp Str=20
F
o
Surge Tmp Run=06
F
MtrCurThrshld=10%
SET ALARM LMTs (5)
Evap Freeze= 34.0° F
Cond Freeze= 34.0°F
SET PASSWORD
Enter
Password:00000
No Access Given
SET PASSWORD (2)
Tech Password
00000 00000
No Access Given