Tabel vervolg
VIEW ALARMS
Alarm Log: 01
SET UNIT SPs
description
Unit Enable = OFF
HH:MM:SS MM/DD/YY
Unit Mode = COOL
Source = SWITCHES
Alarm Log: 02
SET UNIT SPs
description
Available Modes
HH:MM:SS MM/DD/YY
= COOL
.
Select w/Unit Off
Alarm Log: 03 to 25
SET UNIT SPs
description
Cool LWT = 44.0° F
HH:MM:SS MM/DD/YY
^
SET UNIT SPs
Leaving Water Temp
StartDelta = 3.0°F
StopDelta = 3.0°F
^
SET UNIT SPs
Rest Type = NONE
MaxResetDT =00.0
StrtResetDT = 10.0
^
SET UNIT SPs
Soft Load
BeginAmpLimit= 040%
SoftLoadRamp=05min
Alarm Log: 25
SET UNIT SPs
description
Max/Min LWT Rates
HH:MM:SS
Max =
MM/DD/YY
Min =
SET UNIT SPs
EvapRecTmr = 0.5min
EvapPump = #1 ONLY
CondPump = #1 ONLY
SET UNIT SPs
Templifier Src Water
No Start = 070
Delta Reset = 055
Ignore this menu
SET UNIT SPs
VFD
= YES
Min Speed =015%-KW
Max Kw = 076.0
Ignore this menu
SET UNIT SPs
Max Wtr Flow Rates
Evap WF=02400GPM
CondWF=03000GPM
SET UNIT SPs
Time
Day/Mon/Yr
24 hr time day of wk
SET UNIT SPs
Display Format
Units =
Lang = English
SET UNIT SPs
Protocol = MODBUS
Id #= 001
Baud Rate = 19200
SET UNIT SPs
Ex-Val Std Values
Pos 450% L76.0psi
Enthalpy Sp 85.0°F
Ignore this menu
(1)
SET COMP#1 SPs (1)
Demand Limit=OFF
Minimum Amps=040%
Maximum Amps=100%
(2)
SET COMP SPs
(2)
StageMode =Normal
StageSequence# = 01
Max Compr ON = 01
(3)
SET COMP SPs
(3)
o
StageDeltaT = 1.0
Stop-Start =
03 min
Start-Start = 40 min
(4)
SET COMP SPs
(4)
Full Load = 300 sec
Name Plate RLA 085
(5)
SET COMP SPs
(5)
o
F
Nom Capacity = 0100T
o
F
(6)
SET COMP SPs
(6)
= OFF
InterLokTmr= 010sec
UnloadTimer = 030 sec
(7)
SET COMP SPs
(7)
EWWD Automatic
o
0.5
F/min
Vane Control
o
0.1
F/min
(blank mask page)
(8)
SET COMP SPs
(8)
MAX KW = 76.0
Lag Start = 000Sec
Step Down = 060Sec
(9)
SET COMP SPs
(9)
Protocol =M-BUS
o
F
MSTR
o
F
Ident Number= 001
Baud Rate = 19200
(10)
SET COMP SPs
(10)
Refrg Sat Pressure
Evp Offset =+00.0 psi
Cnd Offset = +00.0psi
(11)
SET COMP SPs
(11)
ELWT Offset = +0.0
(12)
(13)
o
F/psi (IP)
(14)
Units =IP
(15)
SET-INSTELPUNTEN
SET COMP#2 SPs (1)
SET ALARM LMTs (1)
Demand Limit=OFF
LowEvPrHold=33psi
Minimum Amps=040%
LowEvPrUnld=31psi
Maximum Amps=100%
LowEvPrStop=29psi
SET COMP#2 SPs (2)
SET ALARM LMTs (2)
StageMode =Normal
HighCondPr =140psi
StageSequence# = 01
HiDschT-Load=170
Max Compr ON = 01
HiDschT-Stop=190
SET COMP#2 SPs (3)
SET ALARM LMTs (3)
o
F
StageDeltaT = 1.0
F
EWWD Compressor
Stop-Start =
03 min
Oilless Design
Start-Start = 40 min
(blank mask page)
SET COMP#2 SPs (4)
SET ALARM LMTs (4)
Full Load = 300 sec
Surge Slp Str=20
Surge Tmp Run=06
MtrCurThrshld=10%
SET COMP#2 SPs (5)
SET ALARM LMTs (5)
Evap Freeze= 34.0° F
Nom Capacity = 0100T
Cond Freeze= 34.0° F
SET COMP#2 SPs (6)
UnloadTimer = 060 sec
PostlubeTmr = 030 sec
SET COMP SPs
(7)
EWWD Automatic
Vane Control
(blank mask page)
SET COMP SPs
(8)
MAX KW = 76.0
Lag Start = 000Sec
Step Down = 060Sec
SET COMP SPs
(9)
Protocol =M-BUS
MSTR
Ident Number= 001
Baud Rate = 19200
SET COMP#2 SPs (10)
Refrg Sat Pressure
Evp Offset =+00.0 psi
Cnd Offset = +00.0psi
SET COMP#2 SPs (11)
o
o
F
ELWT Offset = +0.0
F
SET TOWER SPs (1)
SET PASSWORD
TowerControl=(type?)
Enter
Tower Stages=4
Password:00000
StageUP/Dn=080/020
No Access Given
SET TOWER SPs (2)
SET PASSWORD (2)
Stage ON
Tech Password
o
F
#1
#2
#3
#4
00000 00000
o
F
xxx
xxx
xxx
xxx
No Access Given
SET TOWER SPs (3)
StageDiff= (type?)
StageUp
= 02 min
StageDown=05 min
SET TOWER SPs (4)
o
F
Valve/VFD Control=
o
F
None
Valve Type=NC
SET TOWER SPs (5)
Valve Sp= (type?)
Valve DB= (type?)
SET TOWER SPs (6)
ValveStartPosition
o
Min=010% @ 060
F
o
Max=090% @ 090
F
SET TOWER SPs (7)
Valve Control Range
Min = 010%
Max = 090%
SET TOWER SPs (8
PD Control Loop
Error Gain = 25
Slope Gain = 25
D - EOMWC00905-10NL - 63/96
PASSWORD