Advertenties

operation
(cont.)
Configuration parameter lists
Sensor rating: choose the rating of the
sensors used to measure the load
currents.
Type of utility power: utility power
with or without distributed neutral.
RUN/STOP authorisation via JBUS
communication port: authorisation or
non authorisation of remote RUN and
STOP commands via the JBUS
communication port.

J-BUS communication

Parameter setting of the
communication port is described Is the
specific J-BUS communication port
manual.

Identification

RUN - STOP commands

Reserved access

This command provides access to the
centre of the system and is for MGE
UPS SYSTEMS personnel only so that
they may carry out a detailed survey of
the conditioner's internal operation.
34
Reactive compensation or no
reactive compensation:
compensation or no compensation of
the reactive energy. If this option is
confirmed the amount of reactive
energy supplied by the network can be
reduced and penalty payments in
preferential tariff contracts avoided.
Compensation is optimised increasing
the value of cos Φ to a value higher
than or equal to 0.94. Reactive energy
compensation is carried out to the
detriment of harmonic compensation
and it is therefore necessary to
oversize the conditioner if it is required
to compensate both reactive energy
and harmonics.
MAIN MENU
Language / langue
Principle measurements
Secondary measurements
Alarms
Configuration
JBUS communication
Identification
Reserved access
1 Choose the Identification option
using the
and
2 Confirm the Identification option by
pressing the ENT key.
1 Press RUN to start the device or
STOP to stop the device.
START-UP
Confirmation: ENT
Escape: ESC
This screen allows the command to be
confirmed by pressing ENT or
cancelled by pressing ESC.
installation and operation manual of SineWave™: E-51027008XT/AD
Choice of compensated harmonic
orders:
if this option is selected, the harmonic
orders to be compensated, in order to
optimise conditioner performance, can
be chosen.
Choice of application type: the choice
of application type is a parameter which
is set in the factory. It is defined in
relation to the customer's installation
configuration.
Number of parallel-connected
devices.
Utility power voltage: load supply
voltage
Derating: depending on altitude.
N° = xxxxxxxxxxxx
Is = xxxA
Fn = xxHz With neutral
Versions = xx, xx
This screen displays the device serial
number, the nominal current in amps,
the nominal voltage in volts, the
nominal frequency in Hz, the type of
network (with or without distributed
neutral) and the software versions built
keys.
into the control and monitoring board.
3 Press ESC to return to the general
menu.
IDENTIFICATION
Un = xxxV
MGE UPS SYSTEMS