installation

standard arrangements

Depending on the type of problem to be
solved, the position of the sensors and
that of the The SineWave™ harmonics
conditioner connection point may be
different from one installation to
another.
The audit carried out before installation
enables the optimum respective
positions to be determined.
The SineWave™ conditioner is
connected in parallel with the load.
The SineWave™ harmonics
conditioner will be fed from a
specific outgoing feeder. This line must
be protected by a circuit-breaker. The
SineWave™ conditioner uses this line
to send harmonics destined to
compensate the load harmonics back
onto the utility power.
MGE UPS SYSTEMS
Case of a 20 A, 30 A, 45 A or 60 A unit SineWave™ conditioner
low voltage distribution
switchboard
utility
network
Case of a 90 A or 120 A unit SineWave™ conditioner
low voltage distribution
switchboard
utility
network
installation and operation manual of SineWave™: E-51027008XT/AD
current
sensor
harmonic current
to be compensated
harmonic
compensating
SineWave™
current
active
harmonics
conditioner
current
sensor
harmonic current
to be compensated
SineWave™
active
harmonics
conditioner
load
to be
compensated
load
to be
compensated
5