energization and de-energization
The conditioner must be
energized for the first time by
qualified MGE UPS SYSTEMS
personnel who will carry out the
necessary checks to make sure that
operation of the installation is optimum.
energization
close the conditioner supply circuit-
breaker on your low voltage supply
switchboard:
general
if the load harmonic current is higher
than the SineWave™'s capacity to
eliminate harmonics, the orange
indicator lamp will flash, whether the
conditioner is running or stopped;
to access the RUN and STOP keys,
remove the protection cover located at
the bottom of the terminal;
SineWave™ starting and stopping
can be controlled manually using the
terminal keyboard or via the
communication link;
if SineWave™ conditioners are
connected in parallel, each conditioner
can be started or stopped
independently of the others.
starting the SineWave™
conditioner
Press the RUN key on the terminal to
start the SineWave™ conditioner and
then confirm the command displayed
on the terminal by pressing the ENT
key.
the SineWave™ conditioner starts
and is then operational. The red
indicator lamp goes off and the green
lamp lights up.
stopping the SineWave™
conditioner
to stop the SineWave™ conditioner
manually, press the STOP key and
confirm the displayed command be
pressing the ENT key on the terminal;
de-energization
The SineWave™ conditioner can be
de-energized whatever its state:
running or stopped.
MGE UPS SYSTEMS
the "conditioner stopped" red
indicator lamp lights up;
the terminal screen lights up;
F1
F2
F3
7
8
9
4
5
6
ESC
1
2
3
ENT
0
RUN
STOP
The SineWave™ conditioner
will be automatically restarted
when energized following
disappearance of the utility voltage
during operation of the SineWave™
conditioner. If it is not energized
following the disappearance of the
utility voltage, the SineWave™
conditioner will remain stopped.
the SineWave™ conditioner stops
and no longer carries out
compensation. The green indicator
lamp goes off and the red indicator
lamp lights up.
installation and operation manual of SineWave™: E-51027008XT/AD
after several seconds, the general
menu is displayed on the terminal
screen.
protection
cover
27