Table of strap configurations for each parallel conditioner
SineWave™ n° 1
configuration
of parallel
conditioners
Moving graphic terminal
The SineWave™ harmonics
conditioner graphic terminal can be
moved to the front panel of a switch
cubicle where a SineWave™ is
installed.
To do this, use the optional kit
reference n° 5102726400 which
contains:
a cover plate replacing the terminal
located on the SineWave™ door,
a 2.5 metre long extension lead. This
lead cannot be lengthened without this
causing a risk of abnormal operation;
Moving the graphic terminal:
disconnect the terminal ribbon cable
on the back of the door,
remove the terminal by unscrewing
the 4 fixing screws,
use these 4 screws to fix the cover
plate in place of the terminal,
connect the ribbon cable onto the
extension lead,
feed the extension lead through the
rectangular bushing at the bottom of
the SineWave™ conditioner,
fix the terminal at the required
location,
connect the extension lead to the
graphic terminal.
installing current sensors
(supplied)
Once installed, the current sensor
secondaries must be short-circuited via
the pullout terminals, or equivalent
terminals (not supplied). These pullout
terminals will remain in closed position
as long as they are not connected to
the SineWave™ conditioner.
MGE UPS SYSTEMS
SineWave™ n° 2
1
4
Cutting and fixing template for the
moved terminal
66
70
Sensor mechanical and electrical
characteristics
Closed sensors:
Important: the shape of the sensor
may be different depending on the
rating and supplier.
A
P
B2
L
installation and operation manual of SineWave™: E-51027008XT/AD