installation
(cont.)
Installation requirements
The SineWave™ active
harmonics conditioner must
be mounted vertically and away from
any source of heat (heating system,
transformer, motor, etc.).
installing a SineWave™ conditioner
alone
clearances must be provided to allow
the circulation of an air flow:
3
1000 m
per hour for 20 to 60 A
ratings
2000 m
3
per hour for 90 to 120 A
ratings.
The air is sucked in below the
conditioner and expelled via the top;
the air temperature at the inlet of
each conditioner must not exceed
40 degrees (25 °C recommended);
the power cables and fine wires
arrive via the bottom of the conditioner;
To install a 90 A or 120 A
conditioner, refer to how to
install 2 conditioners on top of each
other or side by side.
Installing 2 SineWave™ conditioners
on top of each other in a cubicle:
Installing 2 SineWave™
conditioners on top of each
other must only be done inside a
cubicle.
openings must be provided at the top
and bottom of the cubicle to help the
conditioners to cool down;
a ventilation deflector must be used
so that the thermal characteristics of
the 2 conditioners are respected. The
distance between the two cubicles is
determined by the height; the air is
sucked below each conditioner and
then expelled:
out the top for the top conditioner,
to the rear for the bottom conditioner;
the air flow required for cooling the
3
cubicle is 2000 m
per hour;
the air temperature at the inlet to
each conditioner must not exceed
40 degrees (25 °C recommended);
power cables and signal cables
arrive via the bottom of the conditioner.
8
it may be installed in a cubicle or
fixed against a wall.
m
5 0 m
m i n .
a n c e
c l e a r
installation and operation manual of SineWave™: E-51027008XT/AD
Whatever the installation
method, a 600 mm minimum
clearance must be provided in front of
the SineWave™ conditioner allowing
for the door to be completely opened.
300 mm min.
clearance for ventilation
min.
50 mm
clearance
300 mm clearance
for wiring and
ventilation
Side view
n
i l a t i o
v e n t
c t o r
d e f l e
m
5 0 m
m i n .
a n c e
c l e a r
A (*)
A = min. 80 mm : 20 to 30 A ratings
A = min. 200 mm : 45 to 120 A ratings
min.
50 mm
clearance
min. 300 mm clearance
for ventilation
min. 300 mm clearance
for ventilation