Locating measurement points
Using the main menu
Press ESC several times if
necessary to display the
general menu:
The current measurements in
the neutral are not displayed in
the case of a utility power without
distributed neutral.
Insignificant measurements
are replaced by * characters
on the terminal screen and
measurements where the capacity is
exceeded are displayed with #
characters on the terminal screen.
Displaying secondary
measurements
MGE UPS SYSTEMS
MAIN MENU
Language / langue
Principle measurements
Secondary measurements
Alarms
Configuration
JBUS communication
Identification
Reserved access
1 Choose the Principle
measurements option using the
and
keys. The choice must be
displayed in reverse video.
2 Confirm the Principle
measurements option by pressing
the ENT key.
MAINS
LOAD
I1 = xxxA
I1 = xxxA
I2 = xxxA
I2 = xxxA
I3 = xxxA
I3 = xxxA
IN = xxxA
IN = xxxA
I1, I2, I3, IN = actual root mean square
values in amps of the 3 phases and
neutral of the:
current supplied by the utility power;
current absorbed by the non-linear
load.
MAIN MENU
Language / langue
Principle measurements
Secondary measurements
Alarms
Configuration
JBUS communication
Identification
Reserved access
1 Choose the Secondary
measurements option using the
and
keys.
2 Confirm the Secondary
measurements option by pressing
the ENT key.
I1 LOAD SPECTRUM
H1 = xx%
H9 = XX%
H3 = xx%
H11 = xx%
H5 = xx%
H13 = xx%
H7 = xx%
THDI = xx%
I2
I3
H1, H3 - H13 = detailed spectrum of
first 13 harmonic orders.
THDI = total harmonic distortion rate of
the current absorbed by the load.
installation and operation manual of SineWave™: E-51027008XT/AD
3 Press the
and
keys to run over
the main measurement screens:
circular loop display.
MAINS
LOAD
THDI1=xx% THDI1=xx%
THDI2=xx% THDI2=xx%
THDI3=xx% THDI3=xx%
Umains=xxxV
THDI1, THDI2, THDI3 = distortion rates
of the 3 phases (THDI = I-harmonic/I-
basic) of the:
current supplied by the utility power;
current absorbed by the non-linear
load.
Umains = average value of the 3 utility
network phase-to-phase voltages.
LOAD LEVEL SINEWAVE
I1 / In = xxx%
I2 / In = xxx%
I3 / In = xxx%
I1/In, I2/In, I3/In = SineWave™ active
conditioner load rates on each of the
phases.
I1 = root mean square current supplied
by the conditioner on phase 1,
In = nominal root mean square current.
3 Press
and
arrows to display the
detailed spectrum of the current
supplied by the utility power.
I1 MAINS SPECTRUM
H1 = xx%
H9 = XX%
H3 = xx%
H11 = xx%
H5 = xx%
H13 = xx%
H7 = xx%
THDI = xx%
I2
I3
H1, H3 - H13 = detailed spectrum of
first 13 harmonic orders.
THDI = total harmonic distortion rate of
the current supplied by the utility power.
4 Press the function keys F2 and F3 to
display phase 2 and phase 3
currents.