Connecting dry contacts and
communication port (optional)
Determining wiring
Connection operations
Procedure:
wiring is connected via the bottom, in
front of the device.
Signal cable connections must
be mechanically fixed near the
connectors so that any mechanical
stress on the conductors is prevented
configuration of dry contact terminal
block:
2 x voltage-free changeover
switches: conditioner running/stopped,
1 x voltage-free changeover switch:
current-limiting operation;
connection to the terminal block may
be made whilst SineWave™ is operating;
these contacts comply with safe extra
low voltage insulating requirements.
10
common
9
conditioner stopped
8
conditioner
7
running
common
6
normal operation
5
limiting operation
4
common
3
conditioner stopped
2
conditioner running
1
Contact breaking capacity:
P = 2 VA, U = 30 V max.,
I = 1 A max.
MGE UPS SYSTEMS
connector
dry contact terminal
block
9 point Sub-D
NO
NC
NO
NC
configuration of 9 point Sub-D
connector for RS 422/485
communication link (optional);
NO
the communication link can be
plugged into the sub-D connector
NC
without shutting down the SineWave™;
this interface complies with safe extra
low voltage insulating requirements.
SineWave™ connector
seen from below
installation and operation manual of SineWave™: E-51027008XT/AD
cross-sectional
area
2
(mm
)
0.5 mini
2.5 max
shielded cable
(not supplied)
1 0
1
1
2
3
4
5
6
7
8
9
type of
remark
recommended
conductor
multi-core wires
removable screw terminal
(not supplied)
block (supplied)
male connector with female
contacts on SineWave™;
the shielding must be
connected at both ends.
1 0
1
1
dry contact cable
(not supplied)
removable connector
with polarization
(supplied with conditioner)
communication link (optional)
(not supplied)
Key:
pin 1: 0 volts
pin 2: RP_5V
pin 3: RC_A
pin 4: RD–(B')
pin 5: TD–(B)
pin 6: RP_0V
pin 7: RC_B
pin 8: RD+(A')
pin 9: TD+(A)