installation
(cont.)
each conditioner independently uses
current measurements from three
sensors, whatever the state of the other
conditioner; running, stopped, de-
energized;
two cables between the conditioners
allow each to know the other's state
and thus determine the share of
harmonics that it has to supply: half or
all if the other conditioner is not
running;
each power circuit remains
independent and has its own
protection;
it is possible to connect up to
4 conditioners with the same rating in
parallel to compensate the same load
or the same group of loads.
6
Case of 2 parallel 20 A, 30 A, 45 A, 60 A, 90 A or 120 A SineWave™
conditioners
Example of 2 parallel 20, 30, 45 or 60 A SineWave™ conditioners:
low voltage distribution
switchboard
utility
network
Example of 2 parallel 90 or 120 A SineWave™ conditioners:
low voltage distribution
switchboard
utility
network
installation and operation manual of SineWave™: E-51027008XT/AD
current
sensor
harmonic current
to be compensated
SineWave™
active
harmonics
conditioner
harmonic
compensating
SineWave™
current
active
harmonics
conditioner
current
sensor
harmonic current
to be compensated
SineWave™
active
harmonics
conditioner
SineWave™
active
harmonics
conditioner
load
to be
compensated
load
to be
compensated