PROBLEM
EN
Flames are weak
and orange,
pellet does not
burn properly and
the glass blackens
Heat exchanger
fan keeps turning
even when the
stove has cooled
Ash nearby the
stove
Stove running
and display
showing "WORK,
MODULAT"
Stove running and
display showing
"HOT EXHAUST"
Stove running and
display showing
"SERVICE"
36
CAUSE
SOLUTION
Check the following inscription: probable obstructions
Insufficient
for combustion air inlet from the stove back or bottom;
combustion air
obstructed holes of the burning pot grid and/or burning pot
with too ash. Have the fun blades and its screw cleaned.
The exhaust chimney is partly or fully obstructed. Contact
Obstructed
an expert stove-repairer to check the exhaust up to the
exhaust
chimney pot. Please clean it immediately.
Obstructed stove
Clean the stove inner.
Pellet can burn also thank to chimney flue depression without
Exhaust fan out of
exhaust fan. Have the exhaust fan replaced immediately.
order
It can be harmful to health to run the stove without fume
exhaust fan.
Faulty fume
temperature
Replace the fume probe.
probe
Faulty mother
Replace the mother board.
board
Faulty or broken
Replace the gaskets.
door gaskets
Contact an Autorized Stove-repairer who will seal the
Fume pipes not
gaskets with silicone at high temperature and/or will replace
sealed
the pipes with others in compliance with current regulations.
A not sealed fume outlet can cause damages to health.
Room
temperature
Stove idling. NO PROBLEM!
reached
Fume outlet limit
temperature
Stove idling. NO PROBLEM!
reached
Routine
When this flashing message appears upon start-up, it means
maintenance
that the preset operating hours have elapsed before
alert (it does not
maintenance. Contact the service centre.
block the system)
INTERVENTION
VENUS PLUS - GIOIA-2