14
IN CASE OF ANOMALY
14.1
ALARMS
ALARM
CAUSE
AL 1 - BLACK
Black out during ignition
OUT
step
Disconnected fume
probe
AL 2 - EXHAUST
PROBE
Faulty fume temperature
probe
Faulty fume probe
Faulty mother board
AL 3 - HOT
EXHAUST
The ambient exchanger
fan does not work
Pellet loading value too
high "stage 5"
AL 4 - FAN
Fume extractor out of
FAILURE
order
32
You should clean the fire door glass every day!
Before of every testing and/or intervention by the Authorized Technician, the Authorized
Technician must check that the parameters of the mother board correspond to those of
the table you own.
In case of doubts regarding the stove running, please allways contact the Authorized
Technician in order to avoid irreparable damages.
SOLUTION
Clean the fire pot and start the stove up again.
Have the stove checked.
Replace the fume probe.
Replace the fume probe.
Replace the mother board.
Replace the ambient fan.
Adjust pellet loading
The pellet can burn also thank to chimney flue depression
without the aid of the extractor. Have the fume extractor
immediately replaced. It can be harmful to health to run
the stove without extractor.
INTERVENTION
VENUS PLUS - GIOIA-2