7 Bediening
Tabel 26: Schermen voor het instellen van de motor
Scherm
ID nr.
20
Set-upselectie
21
Motorvermogen
Motor nominale spanning
22
Motorfrequentie
Nominaal motortoerental
23
Motorstroom
24
Motorstroom
Stroomgrens
138
Schermen
Motor
1,5pk
208 V
60 Hz
1704 RPM
5,48A
5,48A
110,0%
Aquavar Intelligent Pump Controller 1.1 - 90 kW INSTRUCTIEHANDLEIDING
20
Instellen motor
Selecties
[Parameters[ Instelge
_____ [kW/hp]
kW: [1-20] = eerste
invoer
_____ V
hp: [1-21] = tweede
invoer
[1-22] = tweede
invoer.
_____ Hz
[1-23] = eerste invoer.
_____ OPM
[1-25] = tweede
invoer.
[3-03] & [4-14] =
[1-23]
[22-37] = [1-23] * 0,85.
[1-80] = Coast
[1-82] = 10 Hz
[22-33] = 4.14 x 0.5
______ A
[1-24] = invoer
[3-82] = 3 s.
[1-78] = 0 Hz
[14-01] = 5 kHz
(HVAC): [14-55] =
Geen filter
• Sensor: [4-12] =
18 Hz
• Sensorloos: [4-12]
= 24 Hz
______ A
[1-24] = eerste invoer.
______%
[4-18] = tweede
invoer.
[22-39] = [1-21] *
[4-18] * 0,46,
[22-35] = [22*39] *
([22-33] / [4-14]) ^3.
Scherminformatie
gevens
Het instellen van de
motor moet volledig
worden
geconfigureerd bij het
voor de eerste keer
gebruiken van Start-
Up Genie (Smart
Setup) of na het
terugzetten naar
fabrieksinstellingen of
een initialisatie.
Ga verder naar
scherm ID #22.
• (HVAC): ga verder
naar scherm ID
#23.
• (Booster): ga verder
naar scherm ID
#24.
• (Internationaal): ga
verder naar scherm
ID #26.
• (Noord-Amerika):
ga verder naar
scherm ID #29.
Opmerking: Dit
scherm wordt alleen
weergegeven in de
HVAC-
pomptoepassing.
Ga verder naar
scherm ID #25.
Opmerking: Dit
scherm wordt alleen
weergegeven in de
boosterpomptoepassin
g.