The ventilation must be completely free and air must flow in both directions (no diaphragm valve fitted).
The vent pipe must not be connected to the vent pipe on the inlet side of a grease trap.
Connect the ventilation duct Ø ext. 75 (Sanifos® 110, Sanifos® 280 and Sanifos® 610) or Ø ext. 100 (Sanifos® 1300) verti-
cally to the vent hole using the flexible sleeve.
On Sanifos® 110, Sanifos® 280 and Sanifos® 610: 1 ventilation hole is available.
On Sanifos® 1300: 4 ventilation holes are available.
Carefully cut the end of the selected hole so that the through section is completely
clear.
Leave a part of the chamber to facilitate assembly of the fittings.
Ventilation should be at a distance of approximately 50 cm from the tank cover.
Ø 75mm
4.6 DISCHARGE HOLE
NOTICE
To prevent the risk of back-flow of water from the sewer, install the discharge pipe in a "loop" so that its
base, at the highest point, is located above the back-flow level.
NOTICE
Improper fitting of the discharge pipe.
Leaks and flooding in the installation room!
The pumping station must not be used as a support point
for piping.
Do not connect other drain pipes to the discharge pipe.
Install shut-off valves on thesupply pipes and discharge
pipes (already installed on Sanifos® 280, Sanifos® 610 and
Sanifos® 1300).
NOTICE
The supplied non-return valve must be installed (at the
inlet of the discharge pipe for Sanisub Steel and Sanisub
ZPK).
4.7 WATER INLET HOLES
Sanifos® 110
4 inputs available :
• 2 side inputs Ø ext. 40/50
• 2 side inputs Ø ext. 100/110/125
30
Ventilation hole
DN 40 (Ø ext. 50)
or DN 50 (Ø ext. 63)
depending on the model