Afbeelding 14, Lokale bedrading voor optioneel display
MODELS: WSC/WPV/WDC UNITS
REMOTE MOUNTED STARTER WITH D3
COMMUNICATION MICROTECH II
D3 BOARD
(SEE NOTE 2)
BIAS BLOCK
COMPRESSOR CONTROLLER
SERIAL CARD
(BLUE/WHITE)
(WHITE/BLUE)
NOTES:
1. CABLE IS BELDEN 9841 OR EQUIVALENT
(120 CHARACTERISTIC IMPEDANCE OHM).
MAXIMUM LENGTH IS 500 FEET.
2. INSTALL JUMPER ON JP2 ON D3 BOARD
(CONNECTS 120 OHM TERMINATION
RESISTOR).
3. USE A SHORT PIECE OF THE BELDEN 9841
CABLE TO JUMPER TO THE BIAS BLOCK AND
CLIP THE SHIELD.
D – DDWSCDDWDC – 07/10 5 – NL
MODELLEN: WSC/WPV/WDC-UNITS
OP AFSTAND GEÏNSTALLEERDE STARTER MET D3-
COMMUNICATIE MICROTECH II
D3-KAART
(ZIE OPMERKING 2)
COMPENSATIEBLOK
CONTROLLER COMPRESSOR
SERIËLE KAART
(BLAUW/WIT)
(WIT/BLAUW)
OPMERKINGEN:
1. KABEL IS BELDEN 9841 OF EQUIVALENT
(IMPEDANTIE 120 OHM). MAXIMUMLENGTE 150 M.
2. INSTALLEER JUMPER OP JP2 OP D3-KAART (VOOR
120 OHM AFSLUITWEERSTAND).
3. GEBRUIK EEN KORT STUK VAN DE BELDEN 9841
KABEL VOOR VERBINDING MET COMPENSATIEBLOK
EN KORT AFSCHERMING IN.
27