TECHNICAL FEATURES
Ta=25°C unless otherwise specified
Mains side
Description
Supply Voltage
Frequency
Absorbed Maximum Current per phase. *
Inrush Current
Power Factor
Absorbed Minimum Power
Absorbed Maximum Power
* Maximum value per model. For the effective current absorption please refer to the charger's identification label.
Battery side
Description
Output current
Maximum output current
Output current ripple
Absorbed current
Output voltage
Constant output voltage
Thermal compensation of output voltage
Operating range of Temperature Sensor
Output voltage ripple
Maximum power supplied
Output capacity
General
Description
Operating range of temperature
Maximum relative humidity
Efficiency
Maximum size
Weight
Enclosure class
AUX1 and AUX2 contact ratings
Protection and Safety
Description
Insulation
Insulation
Insulation
Leakage current (EMC Filter)
Input fuses
Output fuse
Minimum output voltage of operation (Battery
Detector)
Maximum output voltage
Reverse output polarity
Thermal protection of semiconductors
(Temperature of Thermal Alarm)
Safety Requirements (Rules)
EMC Requirements (Rules)
12
SG3 CAN Bus Interface
Symbol
Test Condition
Vin
f
If max
P = P max
-
Vin=230Veff
P = P max
cos
Pin min
End of charge - Standby
Pin max
P = P max
Symbol
Test Condition
I
I1
Phase 1
-
I = I1
I a
Equipment turned off
U
U1
On the OUT clamps with I = 90% of I1
dU1/dT
Phase 2
T
-
U = U1
U = U1, I = I1
P max
C
Symbol
Test Condition
T
RH

At each operation condition
a×b×c
Without connecting cable
-
Without connecting cable
-
-
Symbol
Test Condition
-
Mains to Battery side
-
Mains side to Earth
-
Battery side to Earth
I L
Supplied equipment
F1
Inside the equipment
F5
Inside the equipment
-
Equipment turn on
Um
Phase 3 (IUIa - IUIUo)
-
At the connection to the Battery
-
-
-
Value and/or Range
-
110 - 230 ± 10%
-
Value and/or Range
-
See curve ± 5%
See curve ± 5%
-
See curve ± 0,5%
See curve ± 0,5%
Programmable (-1÷-9),
default -5
-
from -20 to +55
-
Depend on the model
Value and/or Range
-
from -20 to +50
-
316×220×94,2
-
-
Value and/or Range
About 1.5 x I
See curve
See curve
Protection provided by
the output fuse
English
Unit
Veff
50 ÷ 60
Hz
15
Aeff
< 3
A
0.98
-
< 5
W
3.3
kW
Unit
-
A
< 5%
-
< 0,5
mA
-
V
mV/(°C·cell)
°C
< 1%
-
3000
W
mF
(>0,2)
Unit
°C
90%
-
≥90%
-
mm
6.2
kg
IP55
-
4
A
Unit
1250
V
AC
1250
V
AC
1250
V
AC
< 7
mA
20
A
A
1
V/cell
V
-
100
°C
-
-
-
-
D01911-01