Download Inhoudsopgave Inhoud Print deze pagina

Danfoss VLT AutomationDrive FC 300 Handleiding pagina 63

Verberg thumbnails Zie ook voor VLT AutomationDrive FC 300:
Inhoudsopgave

Advertenties

FC 300 Design Guide
Netvoeding 3 x 380-500 V AC (FC 302), 3 x 380-480 V AC (FC 301)
FC 301/FC 302
Hoge/normale belasting*
Max. ingangsstroom
* Hoge overbelasting = koppel van 160% gedurende 60 s, normale overbelasting = koppel van 110%
gedurende 60 s
HO
Typisch asvermo-
11
gen [kW]
Behuizing IP 21
Behuizing IP 55/66
Uitgangsstroom
Continu
24
(3 x 380-440 V) [A]
Intermitterend (60
s overbelasting)
38.4
(3 x 380-440 V) [A]
Continu
21
(3 x 440-500 V) [A]
Intermitterend (60
s overbelasting)
33.6
(3 x 440-500 V) [A]
Continu kVA
16.6
(400 V AC) [kVA]
Continu kVA
(460 V AC) [kVA]
Continu
22
(3 x 380-440 V) [A]
Intermitterend (60
s overbelasting)
35.2
(3 x 380-440 V) [A]
Continu
19
(3 x 440-500 V) [A]
Intermitterend (60
s overbelasting)
30.4
(3 x 440-500 V) [A]
Max. kabelgrootte
2
2)
[mm
/AWG]
Max. voorzekerin-
gen [A]
1)
Geschat
vermo-
gensverlies
291
bij max. belasting
4)
[W]
Gewicht,
behuizing IP 21, IP
55, IP 66 [kg]
Rendement
4)
MG.33.B9.10 – VLT
®
is een gedeponeerd handelsmerk van Danfoss
P11K
P15K
NO
HO
NO
HO
15
15
18.5
18.5
B1
B1
B1
B1
32
32
37.5
37.5
35.2
51.2
41.3
60
27
27
34
34
29.7
43.2
37.4
54.4
22.2
22.2
26
26
21.5
27.1
29
29
34
34
31.9
46.4
37.4
54.4
25
25
31
31
27.5
40
34.1
49.6
16/6
16/6
63
63
392
379
465
444
23
23
0.977
0.978
4. Elektrische gegevens
P18K
P22K
NO
HO
NO
22.0
22.0
30.0
B2
B2
B2
B2
44
44
61
48.4
70.4
67.1
40
40
52
44
64
57.2
30.5
30.5
42.3
31.9
41.4
40
40
55
44
64
60.5
36
36
47
39.6
57.6
51.7
35/2
35/2
63
80
525
547
739
27
27
0.979
0.978
4
63

Advertenties

Inhoudsopgave
loading

Inhoudsopgave