Maintenance
Cleaning the condensate receptacle
Cleaning and refilling the syphon
Inspection of combustion chamber
1
3
5
24
All manuals and user guides at all-guides.com
7
Cleaning the condensate receptacle
Disconnect the plug of the fluegas
2
temperature sensor (1);
Remove the internal fluegas pipe (2)
of the boiler in order to create access
to the condensate receptacle;
Clean the receptacle (3);
Mount the fluegas pipe back in positi-
on when the cleaning is finished;
Connect the plug of the fluegas tem-
perature sensor.
Cleaning and refilling the syphon
Remove the syphon (4) from the con-
densate connection;
Clean and fill it with fresh water;
Mount the syphon back in the original
position.
Inspection of combustion chamber
The inspection opening is positioned on
the left hand side of the boiler.
Remove the radiation panel (5) from
6
the heat exchanger;
Remove the cover (6) from the in-
spection opening;
Inspect the combustion chamber (7),
clean if necessary;
Mount the cover and radiation panel
back in original position.
4