Maintenance

Cleaning the condensate receptacle

Cleaning and refilling the syphon

Inspection of combustion chamber

1
3
5
24
All manuals and user guides at all-guides.com
7
Cleaning the condensate receptacle

Disconnect the plug of the fluegas
2
temperature sensor (1);

Remove the internal fluegas pipe (2)
of the boiler in order to create access
to the condensate receptacle;

Clean the receptacle (3);

Mount the fluegas pipe back in positi-
on when the cleaning is finished;

Connect the plug of the fluegas tem-
perature sensor.
Cleaning and refilling the syphon

Remove the syphon (4) from the con-
densate connection;

Clean and fill it with fresh water;

Mount the syphon back in the original
position.
Inspection of combustion chamber
The inspection opening is positioned on
the left hand side of the boiler.

Remove the radiation panel (5) from
6
the heat exchanger;

Remove the cover (6) from the in-
spection opening;

Inspect the combustion chamber (7),
clean if necessary;

Mount the cover and radiation panel
back in original position.