CombiPower
9.2
Overview of parameters
"Change Run Mode" menu (operating mode)
Parameter
COMBI Power On
CHR Power On
"P.S. Mode Param" menu (power sharing mode)
Parameter
Explanation
Iac setup
Power sharing level: limits the
current at the 230 V input (over-
load protection).
Power
Determines the power sharing
Sharing
mode:
Disable = deactivated
GEN. = generator function
SUPP. = support function
SHAR. = power sharing
"SHAR." enables the power
sharing function.
"SHAR. GEN." enables the
power sharing and generator
functions.
"SHAR. SUPP." enables the
power sharing and support func-
tions.
"SHAR. SUPP. GEN." enables
the power sharing, support and
generator functions.
EN
Configuring the device with the remote control
Explanation
The device acts as a charger and, if necessary, as an
inverter if there is not sufficient current at the AC input.
The device only acts as a charger. The inverter function is
deactivated.
Value range
3 A – 25 A
Disable
SHAR.
SHAR. GEN.
SHAR. SUPP.
SHAR. SUPP. GEN.
Default
3 A
Disable