_CombiPower_IA_DE-IT.book Seite 83 Freitag, 21. Oktober 2011 8:10 20
CombiPower
➤ Connect the positive terminal of the battery to the 5 A/2.5 A charger
(fig. 1 3, page 3).
Use a conductor with a cross section of at least 2.5 mm².
➤ Protect the positive terminal with a 7.5 A fuse.
➤ Connect the negative terminal of the battery to the negative terminal of the
service battery.
Connecting the 230 V connections
WARNING!
!
The 230 V connections may only be made by qualified personnel.
Observe the following instructions when connecting to the mains:
 Select a connection cable of sufficient cross section for the maximum
current:
– INV. AC OUTPUT: at least 2.5 mm²
– AC OUTPUT, AC INPUT: at least 2.5 mm²
For currents above 25 A, select an appropriate cross section.
 Use cables of the colours specified in the standards that apply in your
country.
➤ Remove the cover (fig. 1 7, page 3).
➤ Connect the required cables:
– INV. AC OUTPUT (fig. 1 4, page 3): 230 V output for inverter mode.
Connect the devices you want to operate in inverter mode here.
Protect the circuit with a two-pole circuit breaker (MCB) or a residual
current device.
– AC OUTPUT (fig. 1 5, page 3): 230 V output (max. 50 A)
Connect your 230 V devices here.
– AC INPUT (fig. 1 6, page 3): 230 V input (max. 50 A)
Connect your external 230 V power source here.
Protect the circuit with a fuse (the rating depends on the cable cross
section) and either a two-pole circuit breaker (MCB) or a residual
current device.
Connect the conductors according to fig. 9, page 6.
➤ Put the cover (fig. 1 7, page 3) back on.
EN
Connecting the device
83