2.2.1
Voedingsspanning
KHS VAV + veeretour (fi guur 686 05)
KHS CONTROL-PLUS (fi guur 138 4G)
186 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com
Aansluiting van de componenten
[4] br (BN) = L
[5] bl (BU) = N
[7] ge/gn (YE/GN) = PE
230V +/- 10% AC 50/60Hz
Zekering max. 16A
[1] br (BN)
[2]
[3] bl (BU)
[14] br (BN)
[15] bl (BU)
[17] zw (BK)
[18]
[19] gr (GY) = Pt 1000 (optioneel)
[20] wt (WH) = Pt 1000 (optioneel)
[21]
Om de temperatuurmeting via de KHS
CONTROL-PLUS te laten plaatsvinden, moet
de jumper op de printplaat van 4-draads
naar 2-draads omgewisseld worden.
Externe ingang
[6] br (BN) = L
Schakelaar
230V +/- 10% AC
50/60Hz
Zekering max. 16A
KHS VAV (fi guur 686 04)
[1] br (BN)
[2] zw (BK)
[3] bl (BU)