EN
EN
7
Status
Error
LED
Max. number of
switching cycles
exceeded.
20.000 / 50.000
Thermal disinfecti-
on limit exceeded
Set-point max.
limit exceeded
Set-point min. limit
undercut
Frost protection
limit undercut
Set-point OK
Control in standby
Flushing is running
170 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com
Description of warnings / notices
Possible reason
Warnings
The valve on the alarming
SLAVE has exceeded the
max. amount of switching
cycles (KHS quarter turn stop
valve -> 20.000; KHS Hygie-
ne Flush Box -> 50.000)
The monitored temperature
has exceeded the set limit
value.
The monitored temperature
has exceeded the set limit
value.
The monitored temperature
has undercut the set limit
value.
The monitored temperature
has undercut the set limit
value.
Notes
Notice that the monitored
temperature is in the target
range.
No flushing pending. Control
in standby.
The valve on the involved
control is flushing / is open.
Measure
Replace the quarter
turn stop valve bonnet
acc. to the maintenance
manual and reset the
operating cycles at the
MASTER.
Check to see if it needs
to be set otherwise.
Check to see if it needs
to be set otherwise.
Check to see if it needs
to be set otherwise.
Prevent danger of
valves freezing up.
No action needed!
No action needed!
No action needed!
Effect
The warning message
cannot be confirmed. SLA-
VE continues to operate
normally.
Entry in logbook.
Entry in logbook.
Entry in logbook.
Entry in logbook.
Entry in logbook.
No influence.
Entry in logbook.