Operating modes

3.1.2.4
In the „Operating modes" submenu, programs and times are added to the actuators and sensors.
Mode
Time Control
Temperature control
Volume control
Backup
Datalogging
Routine
Deactivated
Warning!
If two or more valves are simultaneously opened in a drinking water system, under certain
circumstances pressure fluctuations or a large pressure drop can occur in the system. For that
reason, make sure beforehand that the required flow pressure is continuously guaranteed
at all tapping points. You are recommended not to perform simultaneous water exchanging
measures.
Note!
If the program switch is „Activated" (see Chapter 3.1.2.6), a query is presented during
the operating modes configuration to determine the program this applies to (see right).
The two mentioned flushing programs can be switched using an external manual switch.
The electrical connection is shown in Chapter 2.2.
Description
Triggers a water exchange of defined duration at a certain point in time.
Triggers a water exchange when a predefined start temperature is reached,
until a predefined stop temperature is reached.
Triggers a water exchange with a defined flush volume at a certain point in
time.
Backs up a distribution line by means of a water sensor in a predefined time
window.
Acquires sensor values in a predefined time window with a predefined
sampling rate.
Triggers a water exchange for a predefined duration or quantity if a
temperature control has not actuated for a certain time.
Closes the KHS CoolFlow cold water regulating valve in a predefined
time window.
© www.kemper-group.com – 10.2023 / K410068602008-00 – 115 /265