Download Inhoudsopgave Inhoud Print deze pagina

Kemper KHS MASTER 2.1 Installatie- En Bedieningshandleiding

Mini-besturingssysteem
Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

DE
Montage- und Bedienungsanleitung
KHS Mini-Systemsteuerung
MASTER 2.1
SLAVE
EN
Installation and operating instructions
KHS Mini Control System
MASTER 2.1
SLAVE
NL
Installatie- en bedieningshandleiding
KHS Mini-besturingssysteem
MASTER 2.1
SLAVE
!
Figur 686 02 008
Figur 686 02 006
Figure 686 02 008
Figure 686 02 006
Figuur 686 02 008
Figuur 686 02 006
2
90
178

Advertenties

Hoofdstukken

Inhoudsopgave
loading

Samenvatting van Inhoud voor Kemper KHS MASTER 2.1

  • Pagina 1 Montage- und Bedienungsanleitung KHS Mini-Systemsteuerung MASTER 2.1 Figur 686 02 008 SLAVE Figur 686 02 006 Installation and operating instructions KHS Mini Control System MASTER 2.1 Figure 686 02 008 SLAVE Figure 686 02 006 Installatie- en bedieningshandleiding KHS Mini-besturingssysteem MASTER 2.1 Figuur 686 02 008 SLAVE...
  • Pagina 2: Inhoudsopgave

    6.4 Betriebsarten ..........................61 6.5 Übersicht............................74 6.6 Datentransfer ..........................75 Fehlerbeschreibung und Fehlerbehebung ................80 Ersatzteile ..........................83 Verkabelungshinweise für KHS Komponenten mit elektrischem Anschluss ......84 10 Anhang ..........................87 10.1 Ventiltechniken ..........................87 2 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 3: Sicherheitshinweise

    Objekten realisiert werden. Für jede einzelne Wasserwechselgruppe kann individuell der zeit- oder temperaturgesteuerte Wasserwech- sel oder nach vorgegebenem Wasservolumen parametriert werden. Haftung Keine Gewährleistung oder Haftung bei: - Nichtbeachten der Anleitung. - fehlerhaftem Einbau und/oder Gebrauch. - eigenständiger Modifikation am Produkt. - sonstiger fehlerhafter Bedienung. © www.kemper-group.com – 10.2023 / K410068602008-00 – 3 /265...
  • Pagina 4: Sicherheitshinweise Zur Montage

    Wichtige Hinweise für den Installateur Befolgen Sie bei der Installation die Anweisungen in dieser Anleitung. Auftretende Fehlfunktionen bei der Installation finden Sie in der Übersicht „Feh- lerbeschreibung / Fehlerbehebung“ auf den Seiten 80-82. 4 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 5: Technische Daten

    • Deutsch • Englisch • Niederländisch Betriebsarten • zeitgesteuerter Wasserwechsel • temperaturgesteuerter Wasserwechsel • volumengesteuerter Wasserwechsel • Routine • Datalogging • Sicherung • deaktiviert Funktion externer Eingang • Programmumschaltung • Systemsperrung / Wartungsbetrieb © www.kemper-group.com – 10.2023 / K410068602008-00 – 5 /265...
  • Pagina 6: Lieferumfang | Zubehör

    Verbindungs-Set Unterputz CAN-Bus für KHS HS2 Hygienespülung 99 3590 Modbus TCP/IP Lizenz für MASTER 2.0/2.1 689 03 007 KHS Hygienespülung PRO, mit einem Anschluss 689 03 008 KHS Hygienespülung PRO, mit zwei Anschlüssen 6 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 7: Montage

    Störraum Abb. 1 - Darstellung der Befestigungsbohrungen für die Wandmontage Warnung! Bitte achten Sie bei der Montage der Systemsteuerungen auf den Störraum. Linke Seite: Serien-Nummer der KHS Mini-Systemsteuerung Rechte Seite: USB-Slot © www.kemper-group.com – 10.2023 / K410068602008-00 – 7 /265...
  • Pagina 8: Elektrische Installation

    Elektrische Installation 8 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 9 Eingang 2 Pt1000 Eingang 2 Pt1000 Freier Ablauf / Wasserfühler (Adern tauschbar) Freier Ablauf / Wasserfühler (Adern tauschbar) Alarmrelais – Spannungseingang extern Überwachung ext. Spannung = Fehler Überwachung ext. Spannung = Betrieb © www.kemper-group.com – 10.2023 / K410068602008-00 – 9 /265...
  • Pagina 10 [17]  sw (BK) [18] [19]  gr (GY) = Pt 1000 (optional) [20]  ws (WH) = Pt 1000 (optional) [21] Erfolgt die Temperaturmessung über das CONTROL-PLUS, muss der Jumper auf der Platine von 4-Leiter auf 2-Leiter umgesteckt werden. 10 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 11 Klemmen 22 Überwachungsbeispiel: Fehler und und 23 eine Kabelbrücke Netzspannungsausfall werden gesteckt. Diese muss vor An- mit externer Spannung an die schluss des KHS Wasserfühlers Netz-Warnleuchte, das Warnhorn entfernt werden. oder an die GLT gemeldet. © www.kemper-group.com – 10.2023 / K410068602008-00 – 11 /265...
  • Pagina 12: Bus-Systemübersicht

    Länge 1 x 2 x 0,34 mm² 300 m 1 x 2 x 0,50 mm² 500 m 1 x 2 x 0,75 mm² 1000 m Abschirmung Gefl echt aus verzinnten Kupferdrähten Wellenwiderstand bei f ≥ 1Hz 120 Ω ± 15 % 12 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 13: Can-Bus-Anschluss

    Inbetriebnahme-Assistent durchzuführen! • Falls die Hygienespülung PRO im CAN-Bus-Setup nicht erkannt wird, muss diese einmal neugestartet werden. • Damit die Hygienespülung PRO im CAN-Bus-Setup erkannt wird, muss mindestens ein Magnetventil angeschlossen sein. © www.kemper-group.com – 10.2023 / K410068602008-00 – 13 /265...
  • Pagina 14: Anordnung Can-Bus-Teilnehmer

    Anordnung CAN-Bus-Teilnehmer 2.3.3 KHS Hygiene- spülung PRO KHS HS2 KHS Hygiene- spülung PRO KHS HS2 KHS Hygiene- spülung PRO KHS HS2 Hinweis! Falsche Topologie! Nur Linien-Topologie erlaubt! 14 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 15: Anschluss Can-Bus-Kabel

    Der MASTER benötigt keinen End-Widerstand. KHS Hygiene- spülung PRO Anschluss End-Widerstand 2.3.6 Hinweis! Alle SLAVE-Systemsteuerungen und CANBus-fähigen Hygienespülungen werden mit einem 120 Ω End- Widerstand ausgeliefert. Bei nicht endständigen Systemsteuerungen 120 Ω -SLAVE- oder Hygienespülungen muss der Widerstand entfernt werden! © www.kemper-group.com – 10.2023 / K410068602008-00 – 15 /265...
  • Pagina 16: Inbetriebnahme

    Betätigung der „-Taste“ am letzten Menüeintrag. Tasten Beschreibung Verlassen des Menüs / wechseln zwischen Übersicht und Hauptmenü  Rollen rückwärts Bestätigungstaste  Rollen vorwärts Die Menüführung der KHS Mini-Systemsteuerung MASTER 2.1 ist in zwei Fenstertypen unterteilt. 16 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 17: Gesamtübersicht

    Ventil schließt/geschlossen Ventil öffnet/geöffnet Ventil in Regulierstellung Ventil Initialisierung aktiv Ventil im Handbetrieb CAN-Bus der Systemsteuerung aktiv Störung erkannt Leckage-Überwachung der Systemsteuerung aktiv Durchfl usssensor angeschlossen* Zeitsteuerung eingestellt* Temperatursensor ageschlossen* P1 / P2 Aktiviertes Programm der Programm-Umschaltung Blatt 1 von 8 * Das jeweilige blinkende Symbol zeigt an welche Steuerung (Durchfl uss, Zeit, Temperatur) die aktuell laufende Spülung ausgelöst hat. © www.kemper-group.com – 10.2023 / K410068602008-00 – 17 /265...
  • Pagina 18: Detailübersicht

    Einstellung der Betriebsarten je Wasserwechselgruppe Logbuch Einsicht in das Ereignisprotokoll Programm umschalten Einstellung der Programm Umschaltung Handbetrieb Ventil Gezielter Handbetrieb bestimmter Ventile Netzwerk Setup Einstellung zur Einbindung in ein bestehendes Netzwerk 18 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 19: Systemeinstellung

    Systemeinstellung 3.1.2.1 Sprache Uhrzeit Datum S/W automatisch Alarmsummer Tastenquittierung © www.kemper-group.com – 10.2023 / K410068602008-00 – 19 /265...
  • Pagina 20: Displaybeleuchtung

    Um die Steuerung gegen Fremdein- Ist ein Passwort hinterlegt, wird vor jeder wirkungen zu schützen, kann ein Einstellung das Passwort abgefragt. Passwort konfi guriert werden. Info! Werkseitig ist das Passwort „0000“ eingestellt. Werkseinstellungen Hinweis! Alle zuvor getätigten Parametrierungen gehen verloren! MASTER neu starten 20 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 21: Can-Bus Setup

    Dem ausgewähltem SLAVE wird kein Gerät hinzugefügt Seriennummer Seriennummer KHS Mini-Systemsteuerung SLAVE 2.XX 2.XX 07/14 Ser. Nr.: XXXXXX Typ: KHS Mini Systemsteuerung SLAVE Netz: 230/1N/PE/50 Hz/max.3,15A Art.Nr.: 8210068602006-00 Ser.Nr.: XXXXXX IP 54 © www.kemper-group.com – 10.2023 / K410068602008-00 – 21 /265...
  • Pagina 22: Hauptansicht

    Endständiges Spülventil dem mehrere A-Ventile hydraulisch vorgeschaltet sind. A-Ventil Ventile die je nach Typ den Wasserwechsel des Stranges schalten oder den hydraulischen Abgleich in einer Kaltwasserzirkulation herstellen. C-Ventil Endständiges Spülventil für einen Strang. Sicherung Ventil, welches eine Verteilleitung sichert. nur Messung Slave zur Erfassung und Langzeit-Überwachung von Sensorwerten. 22 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 23: Parametrierung B-Ventil

    Bei der A-/B-Ventiltechnik sollte stets darauf geachtet werden, dass das B-Ventil als erstes konfiguriert wird. Anschließend können dem B-Ventil A-Ventile zugeordnet werden. Die Zuordnung der A-Ventile wird nachfolgend aufgezeigt. Informationen zu der Ventiltechnik siehe Kapitel 10.1. Parametrierung A-Ventil Geräteauswahl Steuerungstyp  B-Ventil  siehe weitere Einstellungen Warnung! Für den Einsatz von temperaturgesteuerten Spülsystemgruppen wird empfohlen nicht mehr als 5 A-Ventile mit einem B-Ventil zu verknüpfen. © www.kemper-group.com – 10.2023 / K410068602008-00 – 23 /265...
  • Pagina 24: Parametrierung C-Ventil

    Geräteeinstellungen 3.1.2.3 Parametrierung C-Ventil Geräteauswahl Steuerungstyp  Ventil  siehe weitere Einstellungen Parametrierung Sicherung Geräteauswahl Steuerungstyp  Ventil  siehe weitere Einstellungen 24 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 25 Geräteeinstellungen 3.1.2.3 Parametrierung Durchflussmessung Geräteauswahl Steuerungstyp  Sensor wählen siehe Parametrierung Durchflusssensor  Sensor wählen siehe Parametrierung Temperatursensor  siehe weitere Einstellungen Parametrierung Durchflusssensor Sensor wählen Hinweis! Der Messbereich des Sensors kann über einen Aufkleber der verbauten Durchflussmessar- matur ermittelt werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 25 /265...
  • Pagina 26: Parametrierung Temperatursensor

    Übersicht der Software-Version der ausgewählten System- steuerung Einstellmöglichkeit zur gleichzeitigen Öffnung zweier Ventile  in einer KHS HS. Je nach Durchfl uss gelten die folgenden Hinweise hinsichtlich des Schallschutzes und des freien Gleichzeitiges Öffnen der Ventile Auslaufes. V1/V2 bei Hygienespülung 26 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 27: Betriebsarten

    Betriebsart eine Abfrage, für welches Programm diese gültig ist (siehe rechts). Die zwei erwähnten Spülprogramme können mittels einem externen manuellen Schalter gewechselt werden. Der elektrische Anschluss ist in Kapitel 2.2 aufgezeigt. © www.kemper-group.com – 10.2023 / K410068602008-00 – 27 /265...
  • Pagina 28 Betriebsarten 3.1.2.4 Parametrierung Zeitsteuerung Parametrierung Volumensteuerung Parametrierung Temperatursteuerung 28 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 29: Parametrierung Datalogging

    Logdatei fi nden Sie eine detaillierte Aufl istung 12 Mio. Zeilen gespeichert werden. der gesamten Messdaten. Sortiert nach Datum, Routinen Wird eine Temperaturspülung parametriert, wird Grundlegend kann zwischen den folgenden automatisch eine Routine-Dauer aktiviert. Routinen gewählt werden: © www.kemper-group.com – 10.2023 / K410068602008-00 – 29 /265...
  • Pagina 30 Betriebsarten 3.1.2.4 Routine-Zeit Routine-Dauer Routine-Menge Hinweis! Nach der erfolgreichen Parametrierung Ihrer Systemsteuerungen empfi ehlt es sich, die Kon- fi guration als Sicherungsdatei zu speichern. Sollte die KHS Mini-Systemsteuerung MASTER 2.1 einen Defekt haben, kann diese schnell ausgetauscht und die Konfi guration eingelesen werden. Dadurch würde eine erneute Parametrierung erspart bleiben. 30 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 31: Logbuch

    über einen externen Schalter zwischen deaktiviert werden. Der „Externer Eingang“ bzw. zwei Spül-Programmen zu wechseln oder diese zu „Externer Schalter“ kann in diesem Untermenü sperren. Die Programme können ebenfalls im eine Programmumschaltung zugeordnet werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 31 /265...
  • Pagina 32: Handbetrieb Ventil

    Darüber hinaus können die Ventile im Version V2.23.15 möglich. Wartungsfall einzeln angesteuert werden. Hinweis Wartung! Eine Funktionsprüfung wird nach der Parametrierung des Untermenüs „Geräteeinstellungen“ empfohlen, um möglich Fehler sofort auszugrenzen. 32 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 33: Netzwerk Setup

    Nach geänderten Netzwerkeinstellungen sollte ein Neustart des Masters 2.1 durchdurchge- führt werden, damit sichergestellt wird, dass alle Einstellungen übernommen werden. Ohne Neustart des Masters 2.1 können Probleme bei der Verbindungsherstellung auftreten. © www.kemper-group.com – 10.2023 / K410068602008-00 – 33 /265...
  • Pagina 34 Gateway einstellen  Netzwerkmaske einstellen  Prim. DNS Server einstellen  Sek. DNS Server einstellen  HTTP Benutzername einstellen  Einbau- und Installationsanleitung Bedienungsanleitung Modbus TCP/IP Lizenz KHS BACnet Gateway  Test-Email auslösen www.kemper-group.com/ www.kemper-group.com/ de/khs-modbus-eba de/khs-bacnet-eba 34 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 35: Fehlerquittierung

    (siehe Kapitel 2.2). Das Alarmrelais ist im muss nachdem der Fehler beseitigt wurde, vom Normalbetrieb mit Spannung „angezogen“. Bei Benutzer quittiert werden. einem Fehler fällt die Spannung    Info! Eine detaillierte Aufl istung der Fehlermöglichkeiten und deren Behebungen fi nden Sie im Kapitel 7. © www.kemper-group.com – 10.2023 / K410068602008-00 – 35 /265...
  • Pagina 36: Usb-Schnittstelle

    Ereignisse auf dem USB-Stick Spülprotokoll auf den USB-Stick kopieren Bei der Auswahl von diesem Menüpunkt werden alle gespeicherten Spülvorgänge auf dem USB-Stick als CSV-Datei gespeichert. Konfi guration auf den USB-Stick kopieren Bei der Auswahl von diesem Menüpunkt werden gespeichert. alle Einstellungen auf dem USB-Stick als CFG-Datei 36 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 37: Konfiguration Von Dem Usb-Stick Lesen

    Update des Web-Server vom USB-Stick Bei der Auswahl von diesem Menüpunkt wird der Web-Server mit dem Ordner „KHS-Webserver“ auf dem USB-Stick aktualisiert. Hinweis! Nach einem Update ist an jeder Systemsteuerung und Hygienespülung ein Abgleich der Soft- ware-Version sowie eine Funktionskontrolle durchzuführen. Info! Die aktuelle Software-Version finden Sie unter kemper-group.com/de/geschaeftsbereiche/gebaeudetechnik/service/downloads/ © www.kemper-group.com – 10.2023 / K410068602008-00 – 37 /265...
  • Pagina 38: Web-Server

    Diese können über die in Abbildung 6.1.1 werden die von Ihnen eingegebenen Parameter aufgeführten Reiter ausgewählt werden. In den gespeichert. Möchten Sie die Änderungen nicht im einzelnen Menüoberfl ächen können Sie Grund- System hinterlegen, verwenden Sie die Schaltfl äche einstellungen, Parametrierungen und Änderungen ÄNDERUNG VERWERFEN vornehmen. Abbildung 6.1.1: Menüreiter des WEB-Servers 38 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 39 Anordnung der Eingabeoberfl ächen leicht verändert. Bei der Nutzung über ein Handy, werden die Menüreiter über einen Button sichtbar (siehe unten). Die Funktionsweisen der einzelnen Menüoberfl ächen sind jedoch unverändert, lediglich die Grafi ken der Komponenten werden nicht dargestellt. Hinweis! Werkseitig ist der Benutzername „KHS“ und das Passwort „0000“ eingestellt. © www.kemper-group.com – 10.2023 / K410068602008-00 – 39 /265...
  • Pagina 40: System-Einstellungen

    Sie einen Benutzernamen und ein geeignetes Passwort. Um die Einstellung zu speichern, „klicken“ Sie auf die Schaltfl äche IN STEUERUNG SCHREIBEN. Nachdem die Einstellungen gespeichert sind, müssen Sie sich zu jedem Start des WEB-Browsers authentifi zieren. Hierzu geben Sie den zuvor gewählten Benutzernamen und das zugehörige Passwort in den sich öffnenden Eingabedialog, wie in Abbildung 6.2.1 aufge- zeigt, ein. Die Verwendung von mehreren Benutzern ist nicht möglich. 40 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 41 Die entsprechenden Parameter zur Einbindung in Ihr Netzwerk bekommen Sie von Ihrem Systemadministrator. Folgende Parameter sind werkseitig konfi guriert: • IP-Adresse: 10.1.23.150 • Subnet: 255.255.255.0 • Gateway: 10.1.23.254 Die Netzwerkeinstellungen können nur beim Laden der Konfi guration via USB-Stick geladen werden. Beim Laden der Konfi guration über den Web-Server werden diese nicht mit übernommen. © www.kemper-group.com – 10.2023 / K410068602008-00 – 41 /265...
  • Pagina 42: Programmumschaltung

    Befi ndet sich der Button auf , ist der Alarmsummer nicht aktiv. Über Befi ndet sich der Button auf , ist der Alarmsummer nicht aktiv. Über das Dropdownmenü kann man zudem die Spracheinstellung der Steuerung anpassen. Geräteeinstellungen In der Menüoberfl äche „GERÄTE-EINSTELLUN- steuerungen mit den eingebauten Aktoren und GEN“ werden die einzelnen KHS Mini-System- Sensoren logisch miteinander verknüpft. 42 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 43: Geräteeinstellungen

    Aktoren und Sensoren zugeteilt. Sollte ein Fehler in den Systemsteuerungen auftreten, kann dieser system- weit gemeldet werden. Hierzu den Button auf stellen. Die stellen. Die restlichen Eingabemöglichkeiten der Eingabeoberfl äche werden im Folgenden erläutert. © www.kemper-group.com – 10.2023 / K410068602008-00 – 43 /265...
  • Pagina 44 Die KHS Mini-Systemsteuerung soll im gegebenen Musterprojekt ein B-Ventil steuern. Ventil wählen Die möglichen Ventile werden aus einer Drop- downliste gewählt. Die KHS Mini-Systemsteue- rung soll im gegebenen Musterprojekt ein KHS VAV-Vollstromabsperrventil mit Federrückzug und Stellantrieb ansteuern. 44 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 45 Spülmengen zu messen und zu speichern. Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl ä- che wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 45 /265...
  • Pagina 46: Parametrierung A-Ventil Für A-/B-Spültechnik

    Für eine A-/B-Spültechnik ist hier ein A-Ventil auszuwählen. Zugehöriges B-Ventil wählen Jedem A-Ventil muss ein B-Ventil zugeordnet wer- den. Die zur Auswahl stehenden KHS Mini-System- steuerungen, welche mit einem B-Ventil verknüpft sind, können in einer Dropdownliste ausgewählt werden. 46 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 47 Eine Erläuterung zu den Ventiltechniken fi nden Sie im Kapitel 10. Sensor wählen Die möglichen Sensoren werden mittels einer Dropdownliste gewählt. Die A-/B-Spültechnik soll im gegebenen Muster- projekt temperaturgesteuert spülen. Dafür soll die Temperatur mit dem KHS-Temp. PT1000 Sensor gemessen werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 47 /265...
  • Pagina 48 Mit der Ober- und Untergrenze werden die Melde- grenzen eingestellt. Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl äche wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. 48 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 49: Parametrierung A-Ventil Für Coolflow Kaltwasser-Zirkulation

    A-Ventil auszuwählen. Zugehöriges B-Ventil wählen Jedem A-Ventil muss ein B-Ventil zugeordnet wer- den. Die zur Auswahl stehenden KHS Mini-System- steuerungen, welche mit einem B-Ventil verknüpft sind, können in einer Dropdownliste ausgewählt werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 49 /265...
  • Pagina 50 Die möglichen Sensoren werden mittels einer Dropdownliste gewählt. Die CoolFlow Kaltwas- ser-Zirkulation soll im gegebenen Musterpro- jekt die Kaltwassertemperaturen messen und speichern. Dafür wird die Temperatur mit dem KHS- Temp. PT1000 Sensor gemessen. 50 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 51 Mit der Ober- und Untergrenze werden die Melde- grenzen eingestellt. Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl äche wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 51 /265...
  • Pagina 52 Die KHS Mini-Systemsteuerung soll im gegebenen Musterprojekt ein C-Ventil steuern. Ventil wählen Die möglichen Ventile werden mittels einer Dropdownliste gewählt. Die KHS Mini-Systemsteu- erung soll im gegebenen Musterprojekt ein KHS VAV-Vollstromabsperrventil mit Federrückzug und Stellantrieb ansteuern. 52 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 53 SCHREIBEN gespeichert werden. Sensor wählen Die möglichen Sensoren werden mittels einer Dropdownliste gewählt. Das C-Ventil soll im gegebenen Musterprojekt temperaturgesteuert spülen. Dafür soll die Tempe- ratur mit dem KHS-Temp. PT1000 Sensor gemessen werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 53 /265...
  • Pagina 54 Mit der Ober- und Untergrenze werden die Melde- grenzen eingestellt. Sensor wählen Die möglichen Sensoren werden mittels einer Dropdownliste gewählt. Mit dem Durchfl usssensor kann das C-Ventil eine Volumenspülung ausführen. Weiterhin wird er genutzt um die Spülmengen zu messen und zu speichern. 54 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 55: Parametrierung Sicherung

    „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. Parametrierung Sicherung Steuerungstyp wählen Die möglichen Steuerungstypen, welche von der gewählten KHS Mini-Systemsteuerung angewen- det werden können, sind aus einer Dropdownliste auszuwählen. Die KHS Mini-Systemsteuerung soll im gegebenen Musterprojekt als Sicherungsventil fungieren. © www.kemper-group.com – 10.2023 / K410068602008-00 – 55 /265...
  • Pagina 56 Die KHS Mini-Systemsteuerung soll im gegebenen Musterprojekt ein KHS VAV-Voll- stromabsperrventil mit Stellantrieb ansteuern. Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl ä- che wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. 56 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 57: Parametrierung Messung

    Dropdownliste bestimmbar. Die aufgezeigte KHS Mini-Systemsteuerung - SLAVE - soll im Beispiel als Mess-SLAVE fungieren. Sensor wählen Die möglichen Sensoren werden mittels einer Dropdownliste gewählt. Der KHS Mini-System- steuerung - SLAVE - soll ein Durchfl usssensor zugeordnet werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 57 /265...
  • Pagina 58: Parametrierung Hygienespülung

    Bezeichnung in das System über- nommen. Info! Ventil der KHS HS2 Hygienespülung (V2 = links; V1 = rechts) Ventil der KHS Hygienespülung PRO (V2 = rechts; V1 = links) 58 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 59 Steuerungstyp wählen Über die Dropdownliste wird der Hygienespülung ein Steuerungstyp (C-Ventil) zugeordnet. Sensor wählen Die möglichen Sensoren werden mittels einer Dropdownliste gewählt. Der Hygienespülung kann ein KHS Termperaturfühler PT1000 zugeordnet werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 59 /265...
  • Pagina 60 Über- bzw. Unterschreiten des Grenzwertes eine Warnmeldung ausgibt. Mit der Ober- und Untergrenze werden die Melde- grenzen eingestellt. Sensor wählen Zur Hygienespülung kann ein interner Durch- fl usssensor über eine Dropdownliste hinzugefügt werden. 60 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 61: Betriebsarten

    über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. Betriebsarten In der Menüoberfl äche „BETRIEBSARTEN“ werden TIMER defi niert je nach Steuerungstyp Spülzeiten, für die KHS Mini-Systemsteue- rungen steuerungs- Messintervalle, Sicherungszeiten, Routine- interval- spezifi sche TIMER (Programme) konfi guriert. Ein le, Temperaturspülungen, etc.. © www.kemper-group.com – 10.2023 / K410068602008-00 – 61 /265...
  • Pagina 62 TIMER bis zu 16 Zeilen Folgenden erläutert. hinzugefügt werden. Durch Betätigung des Buttons wird die jeweilige Zeile aus dem TIMER gelöscht. wird die jeweilige Zeile aus dem TIMER gelöscht. 62 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 63 ZEILE HINZUFÜGEN eingefügt wurde, wird der Zeilentyp ausgewählt. Die KHS Mini- Systemsteuerung ist im gegebenen Musterprojekt mit einem A-Ventil verbunden. Da- mit der Wasserwechsel zeitgesteuert durchgeführt wird, muss der Zeilentyp „Zeitspülung“ über eine Dropdownliste gewählt werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 63 /265...
  • Pagina 64 Über einen „Klick“ in das Käst- chen des jeweiligen Wochentags wird dieser mit einem Haken aktiviert. Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl äche wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. 64 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 65 Zeiten defi nieren Ist ein Zeilentyp gewählt, müssen die Zeiten defi niert werden. Beim Zeilentyp „Deaktiviert“ können über eine Dropdownliste die gewünschten Wochentage gewählt werden. Über einen „Klick“ in das Kästchen des jeweiligen Wochentags wird dieser mit einem Haken aktiviert. © www.kemper-group.com – 10.2023 / K410068602008-00 – 65 /265...
  • Pagina 66: Parametrierung Volumenspülung A-Ventil Khs Stellantrieb 230V

    Parametrierung Volumenspülung A-Ventil KHS Stellantrieb 230V Typ wählen Nachdem eine Zeile über ZEILE HINZUFÜGEN eingefügt wurde, wird der Zeilentyp ausgewählt. Damit der Was- serwechsel volumengesteuert durchgeführt wird, muss der Zeilentyp „Volu- menspülung“ über eine Dropdownliste gewählt werden. 66 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 67 Wochentage gewählt werden. Über einen „Klick“ in das Kästchen des jeweiligen Wochentags wird dieser mit einem Haken aktiviert. Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl ä- che wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 67 /265...
  • Pagina 68: Parametrierung Temperaturspülung A-Ventil Khs Stellantrieb 230V

    Zeilentyp „Temperaturspülung“ über eine Dropdownlist gewählt werden. Temperaturen defi nieren Ist ein Zeilentyp gewählt, müssen die Temperaturen defi niert werden. Beim Zeilentyp „Temperaturspü- lung“ muss eine Start-/Stopptemperatur und die maximale Dauer des Wasserwechsels angegeben werden. 68 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 69 Hierfür können der Betriebsart Routine-Menge Findet innerhalb eines parametrierten Intervalls Hierfür können der Betriebsart „Routine-Menge“ keine Temperaturspülung statt, wird der Wasser- das maßgebende Intervall (max. 168 h), die Menge wechsel über die Betriebsart „Routine-Menge“ und die maximale Spülzeit des Wasserwechsels gewährleistet. zugeordnet werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 69 /265...
  • Pagina 70 „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. Parametrierung einer Hygienespülung Zeitspülung wählen Nachdem eine Zeile über ZEILE HINZUFÜGEN eingefügt wurde, wird der Zeilentyp bestimmt. Über die Dropdownliste wird der Zeilentyp „Zeit- spülung“ gewählt. 70 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 71 über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. Parametrierung Sicherung Typ wählen Nachdem eine Zeile über ZEILE HINZUFÜGEN eingefügt wurde, wird der Zeilentyp ausgewählt. Über die Dropdownliste wird der Zeilentyp „Frei- gabe“ gewählt. © www.kemper-group.com – 10.2023 / K410068602008-00 – 71 /265...
  • Pagina 72: Parametrierung Messung (Datalogging)

    Zeilentyp ausgewählt. Die KHS Mini- Systemsteuerung ist im gegebenen Musterprojekt mit einer KHS Control Plus Durch- fl ussmessarmatur verbunden. Damit die Messda- ten der Durchfl ussmessarmatur mitgeschrieben werden, muss der Zeilentyp „Datalogging“ über eine Dropdownlist gewählt werden. 72 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 73 Über einen „Klick“ in das Kästchen des jeweiligen Wochentags wird dieser mit einem Haken aktiviert. Die Intervallzeit gibt die Ablagerate der Messwerte Einstellungen speichern Damit die neuen Parameter der Eingabeoberfl äche wirksam werden, müssen die Einstellungen über einen „klick“ auf den Button IN STEUERUNG SCHREIBEN gespeichert werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 73 /265...
  • Pagina 74: Übersicht

    KHS Mini-Systemsteuerung. Status Symbol Beschreibung Ventil geschlossen Ventil fährt in Spülposition, Sicherungsventil ist geöffnet Geräte- oder Systemfehler KHS CoolFlow Ventil in Regulierstellung Einstellung Automatikbetrieb / Handbetrieb Auf/Zu Ventil in Spülstellung Initialisierungsfahrt des KHS CoolFlow Ventils 74 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 75: Datentransfer

    Datentransfer In der Menüoberfl äche „DATENTRANSFER“ können und die erstellten Dateien des Datalogging geladen Konfi gurationen, Softwareupdates, Logbucheiträge werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 75 /265...
  • Pagina 76: Software-Update

    Abfrage, wie in Abbildung 6.6.2, geöffnet. Mit einem „klick“ auf die Schalt- fl äche OK wird das gewählte Setup auf die System- steuerung geladen. Abbildung 6.6.1: Auswahl Dialog „Setup-Datei hochladen“ Abbildung 6.6.2: Abfrage „Softwareupdate löschen“ Hinweis! Bitte sichern Sie zur Vorsicht Ihre Konfi guration vor einem Update. 76 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 77 Ihrem PC, speichern. Abbildung 6.6.4: Auswahl Dialog „Konfi gurations-Datei sichern“ Hinweis! Nach der erfolgreichen Parametrierung Ihrer Systemsteuerungen empfi ehlt es sich, die Konfi - guration als Sicherungsdatei auszulagern. Sollte die KHS Mini-Systemsteuerung - MASTER 2.1 - einen Defekt haben, kann diese schnell ausgetauscht und die Konfi guration eingelesen werden. Dadurch bliebe eine erneute Parametrierung erspart. © www.kemper-group.com – 10.2023 / K410068602008-00 – 77 /265...
  • Pagina 78 PC gespeichert werden. Es ist möglich, bis zu Durch einen „Klick“ auf OK wird die ausgewählte 12 Mio. Zeilen zu sichern. Durch einen „Klick“ auf Datei gelöscht. die Schaltfl äche LOGFILE ERZEUGEN wird die 78 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 79 CSV-Logdatei dargestellt. In der Logdatei fi nden den Messdaten der angeschlossenen Messarmatur. Sie eine detaillierte Aufl istung der gesamten Mess- Abbildung 6.6.8: Darstellung Ausschnitt einer CSV-Logdatei Hinweis! Die Ablagerate der Messwerte kann, wie in Kapitel 6.3 beschrieben, über die Menüoberfl äche „Betriebsarten“ eingestellt werden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 79 /265...
  • Pagina 80: Fehlerbeschreibung Und Fehlerbehebung

    Funktion kontrol- Betroffenes Ventil wird beim geschlossenen Ventil Ventil erkannt lieren. gesperrt. erkannt. „Kein Durchfluss Spülleitung und Spül- Fehlermeldung! Es wird kein Durchfluss bei trotz geöffnetem ventil auf Funktion Betroffenes Ventil wird einem Spülvorgang erkannt. Ventil erkannt“ kontrollieren. gesperrt. 80 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 81 Hygienespülung PRO Inbetriebnahme-Assistent Spülung eingestellt ist, warm Spülungen an wurde nicht mit dem durchgeführt und Trinkwasser diese jedoch warm spült, der Hygienespülung Inbetriebnahme-Assistent warm richtig zuortnen Fehler Temperaturüber- durchgeführt schreitung © www.kemper-group.com – 10.2023 / K410068602008-00 – 81 /265...
  • Pagina 82 Es steht keine Spülung an. Keine Aktion Steuerung in Standby Keinen Einfluss Steuerung in Standby erforderlich! Das Ventil an der betroffenen Keine Aktion Eintrag ins Spülung läuft Steuerung spült / ist offen. erforderlich! Logbuch. 82 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 83: Ersatzteile

    Netzwerkkabel für KHS Für MASTER  Mini-Systemsteuerung HW-Stand 2.01 MASTER 2.0/2.1 HW Stand 2.01 6860202200 microSD Karte für  Netzwerk-modul in KHS Kundendienst Kundendienst Mini-System-steuerung Anwendungstechnik MASTER 2.0/2.1 Tel. 02761 891-800 © www.kemper-group.com – 10.2023 / K410068602008-00 – 83 /265...
  • Pagina 84: Verkabelungshinweise Für Khs Komponenten Mit Elektrischem Anschluss

    Anwendungsbeispiele. Die exakte Häufung, Verlegeart, mechanische Belastung) vor Auslegung der entsprechenden Leitungen muss Ort durch den Planer erfolgen. Hinweis! * Möglicher Kabel-Typ bei fester Verlegung, Gemäß VDE 0815: Die Angaben von ohne machanische Belastung Signalübertragungsleitungen hinsichtlich ** abgeschirmte Kabelzuleitung des Durchmessers ist in mm aufgeführt. 84 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 85 Verkabelungshinweise für KHS Komponenten mit elektrischem Anschluss * Möglicher Kabel-Typ bei fester Verlegung, ohne machanische Belastung ** abgeschirmte Kabelzuleitung © www.kemper-group.com – 10.2023 / K410068602008-00 – 85 /265...
  • Pagina 86 Verkabelungshinweise für KHS Komponenten * Möglicher Kabel-Typ bei fester Verlegung, ohne machanische Belastung ** abgeschirmte Kabelzuleitung Stand: November 2022 86 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 87: Anhang

    Spült das Ventil A1, sind anstehen- de Spülvorgänge anderer Ventile gesperrt. Bei Temperaturspülungen werden diese hintereinander vom System abgearbeitet. KHS VAV Vollstrom-Ab- KHS VAV-PLUS mit Feder- sperrventil mit Stellantrieb rückzug-Stellantrieb 230V 230V AC, Figur 686 04 AC, Figur 686 05 © www.kemper-group.com – 10.2023 / K410068602008-00 – 87 /265...
  • Pagina 88 B-Ventil gemeinsam geöffnet wobei alle anderen Kaltwasser-Regulierventile absperren. Somit wird gezielt ein Wasserwechsel in dem jeweiligen Leitungsabschnitt durchgeführt. Nach einem Wasserwechsel schließt sich das B-Ventil und die Kaltwasser-Regulierventile fahren wieder in Regulierstellung. Es wird eine Wartungsabsperrung, Fig. 173, vor jedem A-Ventil empfohlen. 88 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 89 Montage- und Bedienungsanleitung KHS Mini-Systemsteuerung MASTER 2.1 Figur 686 02 008 SLAVE Figur 686 02 006 Installation and operating instructions KHS Mni Control System MASTER 2.1 Figure 686 02 008 SLAVE Figure 686 02 006 Installatie- en bedieningshandleiding KHS Mini-besturingssysteem MASTER 2.1 Figuur 686 02 008 SLAVE...
  • Pagina 90 6.6 Data transfer ..........................163 Error description and error handling .................. 168 Spare parts .......................... 171 Wiring instruction for KHS components with electrical connection ........172 10 Appendix .......................... 175 10.1 Valve technologies ........................175 90 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 91: Safety Instructions

    Thanks to the MASTER/SLAVE technology, KHS Mini Control System can be used to implement Info specific water exchanging measures to maintain Indicates additional information and drinking water hygiene. For each individual water tips. exchange group, time or temperature-controlled water exchange can be configured individually or according to a specified water volume. © www.kemper-group.com – 10.2023 / K410068602008-00 – 91 /265...
  • Pagina 92: Safety Instructions For Installation

    168-170. Disposal Local regulations on waste recycling and disposal must be followed. The product must not be disposed of with household waste but must rather be disposed of appropriately. 92 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 93: Technical Data

    • Time controlled water exchange • Temperature controlled water exchange • Volume controlled water exchange • Routine • Datalogging • Backup • Deactivated External input • Change program • System log / Maintenance operation © www.kemper-group.com – 10.2023 / K410068602008-00 – 93 /265...
  • Pagina 94: Scope Of Delivery | Accessories

    ush-mounted CAN bus for KHS HS2 hygiene fl ushing box 99 3590 Modbus TCP/IP licence for MASTER 2.0/2.1 689 03 007 KHS Flush Box PRO with one connection 689 03 008 KHS Flush Box PRO with two connections 94 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 95: Installation

    Ill. 1 - Illustration of the mounting holes for wall installation Warning! Please pay attention to the disturbance space when installing the Control System. Left-hand side: Serial number of the KHS Mini Control System Right-hand side: USB-slot © www.kemper-group.com – 10.2023 / K410068602008-00 – 95 /265...
  • Pagina 96: Electrical Installation

    Electrical installation 96 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 97 Free drain / water sensor (conductors interchangeable) Free drain / water sensor (conductors interchangeable) Alarm relay – External voltage input Monitoring of ext. voltage = Fault Monitoring of ext. voltage = Operation © www.kemper-group.com – 10.2023 / K410068602008-00 – 97 /265...
  • Pagina 98: Connection Of The Components

    [19]  gr (GY) = Pt 1000 (optional) [20]  ws (WH) = Pt 1000 (optional) [21] If the temperature is measured using the CONTROL-PLUS, the jumper on the board must be changed from 4-wire to 2-wire. 98 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 99 Terminals 22 and 23. This must and mains voltage failures are be removed before connecting reported with external voltage to the KHS water sensor. the network warning lamp, the warning horn or to the BMS. © www.kemper-group.com – 10.2023 / K410068602008-00 – 99 /265...
  • Pagina 100: Bus System Overview

    1 x 2 x 0,34 mm² 300 m 1 x 2 x 0,50 mm² 500 m 1 x 2 x 0,75 mm² 1000 m Shielding Braiding of tinned copper wires Impedance at f ≥ 1Hz 120 Ω ± 15 % 100 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 101: Can Bus Connection

    KHS Hygiene flushing box with two connections Info! If hot water exchanges at a KHS Hygiene Flush Box PRO are programmed via KHS Master 2.1, the commissioning wizard must be executed at each Hygiene Flush Box PRO prior program- ming.
  • Pagina 102: Can Bus Subscriber Arrangement

    CAN bus subscriber arrangement 2.3.3 KHS Flush Box PRO KHS HS2 KHS Flush Box PRO KHS HS2 KHS Flush Box PRO KHS HS2 Note! Wrong topology! Only line topology allowed! 102 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 103: Can Bus Cable Connection

    2.3.6 Note! All SLAVE system controls and all CANBus-capable hygiene fl ushing boxes are supplied with a 120 Ω end resistor. For non-terminal SLAVE or hygiene fl ushing box 120 Ω system controls, the resistor must be removed! © www.kemper-group.com – 10.2023 / K410068602008-00 – 103 /265...
  • Pagina 104: Commissioning

    Danger of fatal electric shock. Note! To simplify confi guration and to guarantee correct installation, fi ll in the system commissio- ning overview of the KHS Mini Control System (see https://www.kemper-group.com/uk-en/ building-technology/service/downloads/) before making the settings. It is mandatory to fi ll in the form to be able to take advantage of the optional factory support.
  • Pagina 105 Leakage monitoring of Control System active Flow sensor connected* Time control set* Temperature sensor connected* P1 / P2 Activated program for the program switchover Sheet 1 of 8 * The fl ashing icon indicates which control (fl ow rate, time, temperature) has triggered the current fl ushing operation. © www.kemper-group.com – 10.2023 / K410068602008-00 – 105 /265...
  • Pagina 106 Setting the operating modes for each water exchange group Logbook Access to the event log Program switchover Settings for the program switchover Manual valve operation Specifi c manual operation of certain valves Network setup Settings for integration into an existing network 106 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 107: System Settings

    System settings 3.1.2.1 Language Time Date S/W automatic Alarm buzzer Key press signal © www.kemper-group.com – 10.2023 / K410068602008-00 – 107 /265...
  • Pagina 108: Display Contrast

    If a password has been stored, the password will nal influences, a password can be configured. be queried before every setting. Info! The password „0000“ is the factory default setting. Note! All previous configurations will be lost! Factory settings Reboot the MASTER 108 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 109: Can Bus Setup

    No device is added to the selected SLAVE Serial number Serial number KHS Mini Control System SLAVE 2.XX 2.XX 07/14 Ser. Nr.: XXXXXX Typ: KHS Mini Systemsteuerung SLAVE Netz: 230/1N/PE/50 Hz/max.3,15A Art.Nr.: 8210068602006-00 Ser.Nr.: XXXXXX IP 54 © www.kemper-group.com – 10.2023 / K410068602008-00 – 109 /265...
  • Pagina 110: Device Settings

    C valve Terminal fl ushing valve for one line. Safety device Valve which protects a distribution line. Only measurement Slave for the acquisition and long-term monitoring of sensor values. 110 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 111 Confi guration of the A Valve Device selection Control type  B-Valve  see Miscellaneous settings Warning! You are recommended not to link more than 5 A valves to one B valve. © www.kemper-group.com – 10.2023 / K410068602008-00 – 111 /265...
  • Pagina 112 Device settings 3.1.2.3 Confi guration C-Valve Device selection Control type  Valve  see Miscellaneous settings Confi guration of the safety device Device selection Control type  Valve  see Miscellaneous settings 112 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 113: Configuration Of Flow Measurement

     see Miscellaneous settings Configuration of volume flow sensor Select sensor Note! The measuring range of the sensor can be determined by means of a sticker on the installed flow measurement valve. © www.kemper-group.com – 10.2023 / K410068602008-00 – 113 /265...
  • Pagina 114: Miscellaneous Settings

    Setting for the simultaneous opening of two valves in a KHS  HS2. Depending on the fl ow rate, the following instructions apply with regard to sound protection and free discharge. Simultaneous opening of valves V1/V2 during hygiene fl ushing 114 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 115: Operating Modes

    You are recommended not to perform simultaneous water exchanging measures. Note! If the program switch is „Activated“ (see Chapter 3.1.2.6), a query is presented during the operating modes configuration to determine the program this applies to (see right). The two mentioned flushing programs can be switched using an external manual switch. The electrical connection is shown in Chapter 2.2. © www.kemper-group.com – 10.2023 / K410068602008-00 – 115 /265...
  • Pagina 116 Operating modes 3.1.2.4 Confi guration of time control Confi guration of volume control Confi guration of temperature control 116 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 117: Confi Guration Of Datalogging

    Up to 12 million lines can be saved. Routines If temperature fl ushing is confi gured, a routine Generally speaking, it is possible to choose bet- duration is automatically activated. ween the following routines: © www.kemper-group.com – 10.2023 / K410068602008-00 – 117 /265...
  • Pagina 118 Operating modes 3.1.2.4 Routine time Routine Duration Routine Volume Note! After your Control System have been successfully configured, you are recommended to save the configuration as a backup file. If the KHS Mini Control System MASTER 2.1 is defective it can be quickly replaced and the configuration can be read in. This saves having to configure everything again. 118 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 119: Logbook

    „External switch“ can be assigned to a or to block them using an external switch. The program switch in this submenu. programs can also be activated or deactivated in © www.kemper-group.com – 10.2023 / K410068602008-00 – 119 /265...
  • Pagina 120: Valve Manual Mode

    „Valve manual mode“ submenu. Furthermore, CoolFlow cold water regulating valve is possible the valves can be individually addressed during with the software version V2.23.15. Note Maintenance! A function test is recommended after confi guring the „Device settings“ submenu to rule out possible errors immediately. 120 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 121: Network Setup

    The Master 2.1 should be restarted after changing the network settings to ensure that all settings are adopted. Without restarting the master 2.1, problems may occur when establis- hing the network connection. © www.kemper-group.com – 10.2023 / K410068602008-00 – 121 /265...
  • Pagina 122 Setting the sec. DNS server  Setting the http user name Installation and  Installation instructions operating instructions for Modbus TCP/IP for KHS BACnet licence gateway  Tiggering a test email www.kemper-group.com/ www.kemper-group. de/khs-modbus-eba com/de/khs-bacnet-eba 122 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 123: Acknowledge Error

    („pulled“) with voltage. mal-function has been repaired.    Info! A detailed list of possible errors and their corrections is given in chapter 7. © www.kemper-group.com – 10.2023 / K410068602008-00 – 123 /265...
  • Pagina 124: Usb Interface

    Max. storage capacity of the USB stick 16 GB • File system FAT32 Copy logbook to USB stick When this menu item is selected, all saved events are stored on the USB stick as a CSV file. Copy flushing log to USB stick When this menu item is selected, all saved flushing processes are stored on the USB stick as a CSV file. Copy configuration to USB stick When this menu item is selected, all settings are stored on the USB stick as a CFG file. 124 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 125: Copy Configuration To Usb Stick

    When this menu item is selected, the web server is updated with the „KHS Webserver“ folder on the USB stick. Note! After an update, the software version must be adjusted and a function check carried out on each system control and hygiene flushing box. Info! You can find the current software version at kemper-group.com/de/geschaeftsbereiche/gebaeudetechnik/service/ downloads/ © www.kemper-group.com – 10.2023 / K410068602008-00 – 125 /265...
  • Pagina 126: Web-Server

    If you do not want to Fig. 6.1.1. In the individual menu interfaces, you store the changes in the system, use the can make the basic settings, the confi gurations DISCARD CHANGES button. Ill. 6.1.1: Menu tab of the web browser 126 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 127 (see below). The modes of functioning of the individual menu interfaces remain unchanged; merely the graphics of the components are not displayed. Note! The username “KHS” and password „0000“ is the factory default. © www.kemper-group.com – 10.2023 / K410068602008-00 – 127 /265...
  • Pagina 128: System Settings

    To do this, enter the user name you have just chosen and the relevant password in the input dialogue that then opens, as shown in Fig. 6.2.1. Use by several users is not possible. 128 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 129 You can obtain the appropriate parameters for integration into your network from your system administrator The following parameters are confi gured as factory defaults:  IP-address: 10.1.23.150  Subnet: 255.255.255.0  Gateway: 10.1.23.254 The network settings can only be loaded when the confi guration is loaded using a USB stick. They are not imported when the confi guration is loaded using the web server. © www.kemper-group.com – 10.2023 / K410068602008-00 – 129 /265...
  • Pagina 130: Other Settings

    Using the drop-down menu you can also customise the language setting of the control. Device settings In the „DEVICE SETTINGS“ menu interface, integrated actuators and sensors are logically the individual KHS Mini Control System with linked to each other. 130 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 131 Control System, it can be reported across the entire system. To do this, set the button to . The remaining input options of the input box are explained in the following. © www.kemper-group.com – 10.2023 / K410068602008-00 – 131 /265...
  • Pagina 132: Device Settings - Adding Devices

    Select valve The possible valves are selected from a drop-down list. In this sample project, the KHS Mini Control System should actuate a KHS VAV maximum fl ow isolating ball valve with spring reset and servo drive. 132 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 133 ushing with the B-valve. It is also used to measure and log the fl ushing volume. Save settings To allow the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. © www.kemper-group.com – 10.2023 / K410068602008-00 – 133 /265...
  • Pagina 134 Select the relevant B valve Each A valve must be assigned to a B valve. The available KHS Mini Control System that are linked to a B valve can be selected from a drop-down list. 134 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 135 Select sensor The possible sensors are selected from a drop- down list. The A/B fl ushing technology will be temperature controlled in the sample project given. The temperature will be measured with the KHS Temp. PT1000 sensor. © www.kemper-group.com – 10.2023 / K410068602008-00 – 135 /265...
  • Pagina 136 The upper and lower limits are used to set the messaging limits. Save settings For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. 136 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 137 Select the relevant B valve Each A valve must be assigned to a B valve. The available KHS Mini Control System that are linked to a B valve can be selected from a drop-down list. © www.kemper-group.com – 10.2023 / K410068602008-00 – 137 /265...
  • Pagina 138 The CoolFlow cold water circulation will measure and log the cold water temperatures in the sample project given. The temperature will be measured with the KHS Temp. PT1000 sensor. 138 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 139 The upper and lower limits are used to set the messaging limits. Save settings For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. © www.kemper-group.com – 10.2023 / K410068602008-00 – 139 /265...
  • Pagina 140 Select valve The possible valves are selected from a drop-down list. In this sample project, the KHS Mini Control System should actuate a KHS VAV maximum fl ow isolating ball valve with spring reset and servo drive. 140 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 141 Select sensor The possible sensors are selected from a drop- down list. The C-valve will perform temperature- controlled fl ushing in the sample project given. The temperature will be measured with the KHS Temp. PT1000 sensor. © www.kemper-group.com – 10.2023 / K410068602008-00 – 141 /265...
  • Pagina 142 The upper and lower limits are used to set the messaging limits. Select sensor The possible sensors are selected from a drop- down list. The fl ow sensor can be used to perform volume fl ushing with the C-valve. It is also used to measure and log the fl ushing volume. 142 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 143 Choose the available control types that can be used by the selected KHS Mini Control System from a drop-down list. In this sample project, the KHS Mini Control System should function as a safety valve. © www.kemper-group.com – 10.2023 / K410068602008-00 – 143 /265...
  • Pagina 144 Save settings For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. 144 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 145 The KHS Mini Control System -SLAVE- in this example should act as a measurement SLAVE. Select sensor The possible sensors are selected from a drop- down list. A fl ow sensor must be assigned to the KHS Mini Control System -SLAVE-. © www.kemper-group.com – 10.2023 / K410068602008-00 – 145 /265...
  • Pagina 146 Confi guring the Hygiene Flush Box Use the APPLY NAME button to transmit the selected system name. Info! Valve of the KHS HS 2 hygiene fl ushing box (V2=left; V1=right) Valve of the KHS Flush Box PRO (V2=right; V1=left) 146 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 147 A control type (C valve) is assigned to the hygiene fl ushing box by means of a drop-down list. Select sensor The possible sensors are selected from a drop- down list. A KHS temperaturesensor PT1000 can be assigned to the hygiene fl ushing box. © www.kemper-group.com – 10.2023 / K410068602008-00 – 147 /265...
  • Pagina 148 The upper and lower limits are used to set the messaging limits. Select sensor An internal volume fl ow sensor can be added to the hygiene fl ushing box by means of a drop-down list. 148 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 149: Operating Modes

    In the „OPERATING MODES“ menu interface, the control type, a TIMER defi nes fl ushing times, control-specifi c TIMERS (programs) are confi gured measurement intervals, backup times, routine for the KHS Mini Control System. Depending on the intervals, temperature fl ushing, etc. © www.kemper-group.com – 10.2023 / K410068602008-00 – 149 /265...
  • Pagina 150 The remaining input options in the lines are to add up to 16 lines to the TIMER. Press the explained below. button to delete the line in question from the 150 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 151 Note! To simplify confi guration and to guarantee correct installation, fi ll in the system commissio- ning overview of the KHS Mini Control System (see https://www.kemper-group.com/oc/busi- ness-units/building-technology/service/downloads/) before making the settings. It is mandatory to fi ll in the form to be able to take advantage of the optional factory support.
  • Pagina 152 Save settings For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. 152 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 153 With the “Deactivated” line type, the desi- red weekdays can be selected from a drop-down list. Click the box of the weekday in question to activate it with a check mark. © www.kemper-group.com – 10.2023 / K410068602008-00 – 153 /265...
  • Pagina 154 Select type After a line has been added using ADD LINE the line type is selected. To volume control the water exchange, the „Volume fl ushing“ line type has to be selected from a drop-down list. 154 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 155 Save settings For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. © www.kemper-group.com – 10.2023 / K410068602008-00 – 155 /265...
  • Pagina 156 Defi ning temperatures Once a line type has been selected, defi ne the temperatures. With the “Temperature fl ushing” line type, a start/stop temperature must be given, together with the maximum duration of the water exchange. 156 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 157 ushing time of the fi gured interval, the water exchange is guaranteed water exchange can be assigned to the „Routine through the „Routine volume“ operating mode. To volume“ operating mode. accomplish this, the decisive interval (max. 168 h), © www.kemper-group.com – 10.2023 / K410068602008-00 – 157 /265...
  • Pagina 158 Confi guration of a Hygiene fl ushing box Select time fl ushing After a line has been added using LINE, the line type is selected. The „Time fl ushing“ line type is selected from the drop-down list. 158 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 159 Confi guration of the safety device Select type After a line has been added using ADD LINE the line type is selected. The „Release“ line type is selected from the drop- down list. © www.kemper-group.com – 10.2023 / K410068602008-00 – 159 /265...
  • Pagina 160: Confi Guration Of Measurement (Datalogging)

    The KHS Mini Control Sys- tem in this sample project is connected to a KHS Control Plus fl ow measurement valve. To record the fl ow measurement valve measurement data at the same time, the „Datalogging“ line type must be selected from a drop-down list. 160 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 161 Save settings For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO CONTROL button. © www.kemper-group.com – 10.2023 / K410068602008-00 – 161 /265...
  • Pagina 162: Overview

    Valve closed Valve moves to fl ushing position, safety valve is open Device or system error KHS CoolFlow valve in regulation position Setting Automatic mode / Manual mode Open/Close Valve in fl ush position Initialization run of the KHS CoolFlow valve 162 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 163: Data Transfer

    Data transfer You can use the „DATA TRANSFER“ menu interface entries and the created datalogging fi les. to load confi gurations, software updates, logbook © www.kemper-group.com – 10.2023 / K410068602008-00 – 163 /265...
  • Pagina 164: Software-Update

    LOAD UPDATE button has been pressed, a confi rmation appears as shown in Fig. 6.6.2. Click the OK button to load the selected setup into the Control System. Ill.: 6.6.1: Selection dialogue „Upload setup fi le“ Ill.: 6.6.2: „Delete software update“ confi rmation Note! As a precautionary measure, please backup your confi guration before making an update. 164 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 165 In this window, see Fig. 6.6.4, you can back up the CFG fi le to the desired folder on your PC. Ill.: 6.6.4: Selection dialogue „Back up confi guration fi le“ Note! After successfully confi guring your Control System, you are recommended to save the confi guration as a backup fi le. If the KHS Mini Control System -MASTER 2.1- is defective, it can be quickly replaced and the confi guration can be read in. This saves having to confi gure everything again. © www.kemper-group.com – 10.2023 / K410068602008-00 – 165 /265...
  • Pagina 166 Use the button to open a form of a CSV fi le on the PC. Up to 12 million query as shown in Fig. 6.6.7. Click OK to delete the selected fi le. 166 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 167 Ill.: 6.6.8: Illustration of an extract of a CSV log fi le Note! As described in Chapter 6.3, the sampling interval of the measured values can be set using the „OPERATING MODES“ menu interface. © www.kemper-group.com – 10.2023 / K410068602008-00 – 167 /265...
  • Pagina 168: Error Description And Error Handling

    „No flow de- No flow is detected du- Check the flushing line Error message! The involved tected despite ring a flushing process. and the flushing valve. valve will be blocked. open valve“ 168 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 169 Hygienespülung PRO water was flushed during hot water flushes with the commissioning as- wurde nicht mit dem a programmed cold water at the Hygiene sistant and correctly allocate Inbetriebnahme-Assistent flush. Error: temperature Flush Box PRO hot water durchgeführt exceeded © www.kemper-group.com – 10.2023 / K410068602008-00 – 169 /265...
  • Pagina 170: Description Of Warnings / Notices

    No action needed! Entry in logbook. range. No flushing pending. Control Control in standby No action needed! No influence. in standby. The valve on the involved Flushing is running No action needed! Entry in logbook. control is flushing / is open. 170 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 171: Spare Parts

    2.01 6860202200 Micro SD card for net-  work module in KHS Service de- Service de- Mini Control System partment - applica- MASTER 2.0/2.1 tion technology Tel. +49 2761 891-800 © www.kemper-group.com – 10.2023 / K410068602008-00 – 171 /265...
  • Pagina 172: Wiring Instruction For Khs Components With Electrical Connection

    Note! * Possible cable type for fixed routing, According to VDE 0815: The specification without mechanical load of signal transmission cables with res- ** Shielded cable lead pect to the diameter is specified in mm. 172 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 173 Wiring instruction for KHS components with electrical connection * Possible cable type for fixed routing, without mechanical load ** Shielded cable lead © www.kemper-group.com – 10.2023 / K410068602008-00 – 173 /265...
  • Pagina 174 Wiring instruction for KHS components with electrical connection * Possible cable type for fixed routing, without mechanical load Issue: November 2022 ** Shielded cable lead 174 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 175: Appendix

    KHS maximum fl ow KHS PLUS maximum isolation ball valve fl ow isolation ball valve with servo drive 230V with servo drive and AC, Figure 686 04 spring reset 230V AC, Figure 686 05 © www.kemper-group.com – 10.2023 / K410068602008-00 – 175 /265...
  • Pagina 176 B valve closes and the cold water regulating valves return to the regulating position. It is recommended to place a maintenance cut-off, fi gure 173, in front of each A-Valve. 176 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 177 Installatie- en bedieningshandleiding KHS Mini-besturingssysteem MASTER 2.1 Figuur 686 02 008 SLAVE Figuur 686 02 006 D R I V I N G P R O G R E S S © www.kemper-group.com – 10.2023 / K410068602008-00 – 177 /265...
  • Pagina 178 6.5 Overzicht ............................ 250 6.6 Gegevensoverdracht ........................251 Beschrijving en opheffen van storingen ................256 Reserveonderdelen......................259 Bekabelingsinstructies voor KHS componenten met elektrische aansluiting ..... 260 10 Bijlage .......................... 263 10.1 Afsluitertechnieken ........................263 178 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 179: Veiligheidsinstructies

    Info water-systemen in gebouwen worden uitgevoerd Kenmerkt extra informatie en tips. voor de instandhouding van de drinkwaterhygiëne. Voor iedere spoelgroep kunnen afzonderlijke tijd-, temperatuur- of volumegestuurde spoelmaatrege- len worden ingesteld. © www.kemper-group.com – 10.2023 / K410068602008-00 – 179 /265...
  • Pagina 180: Afvalverwijdering

    Belangrijke informatie voor de installateur Leef tijdens de installatie de instructies in deze handleiding na. Een overzicht van mogelijk voor- komende storingsmeldingen en hun oplossingen vindt u op pagina 256-258. 180 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 181: Technische Gegevens

    • Engels • Nederlands Bedrijfsmodi • Tijdgestuurde spoelmaatregel • Temperatuurgestuurde spoelmaatregel • Volumegestuurde spoelmaatregel • Routine • Datalogging • Beveiliging • Gedeactiveerd Functie externe ingang • Programma omschakeling • Systeemblokkering / Onderhoudsbedrijf © www.kemper-group.com – 10.2023 / K410068602008-00 – 181 /265...
  • Pagina 182: Leveringsomvang | Toebehoren

    Aansluitset voor inbouwmontage CAN-bus voor KHS HS2 hygiënespoeler 99 3590 Modbus TCP/IP licentie voor MASTER 2.0/2.1 689 03 007 KHS Flush Box PRO, met een aansluiting 689 03 008 KHS Flush Box PRO, met twee aansluitingen 182 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 183: Montage

    Afb. 1 - Weergave van de bevestigingsboringen voor de wandmontage Waarschuwing! Let bij de montage van de besturingsunits op de interferentie ruimte. Linker kant: Serienummer van de KHS Mini besturingsunit Rechter kant: USB-poort © www.kemper-group.com – 10.2023 / K410068602008-00 – 183 /265...
  • Pagina 184: Elektrische Installatie

    Elektrische installatie 184 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 185: Aansluiting Van De Componenten

    Ingang 2 Pt1000 Ingang 2 Pt1000 Vrije uitloop / vlotterschakelaar (bedrading verwisselbaar) Vrije uitloop / vlotterschakelaar (bedrading verwisselbaar) Alarmrelais – spanningsingang extern Bewaking ext. spanning = storing Bewaking ext. spanning = bedrijf © www.kemper-group.com – 10.2023 / K410068602008-00 – 185 /265...
  • Pagina 186 [20]  wt (WH) = Pt 1000 (optioneel) [21] Om de temperatuurmeting via de KHS CONTROL-PLUS te laten plaatsvinden, moet de jumper op de printplaat van 4-draads naar 2-draads omgewisseld worden. 186 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 187 Deze moet vóór met externe spanning aan de waar- de aansluiting van de KHS water schuwingsampen, de waar-schu- sensor verwijderd worden. wingshoorn of aan het GBS gemeld. © www.kemper-group.com – 10.2023 / K410068602008-00 – 187 /265...
  • Pagina 188: Bus-Systeemoverzicht

    1 x 2 x 0,34 mm² 300 m 1 x 2 x 0,50 mm² 500 m 1 x 2 x 0,75 mm² 1000 m Afscherming Vlechtwerk van vertinde koperdraden Weerstand bij f ≥ 1Hz 120 Ω ± 15 % 188 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 189: Can-Bus-Aansluiting

    - Als de PRO-Hygiene Flush Box niet wordt herkend in de CAN-bus setup, moet deze eenmalig opnieuw worden gestart. - Er moet ten minste één magneetventiel worden aangesloten, zodat de PRO-Hygiene Flush Box wordt herkend in de CAN-bus setup. © www.kemper-group.com – 10.2023 / K410068602008-00 – 189 /265...
  • Pagina 190: Rangschikking Can-Bus-Deelnemers

    2.3.3 Rangschikking CAN-Bus-deelnemers KHS Flush Box PRO KHS HS 2 KHS Flush Box PRO KHS HS 2 KHS Flush Box PRO KHS HS 2 Aanwijzing! Foute rangschikking! Alleen seriële aansluiting toegestaan! 190 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 191: Aansluiting Can-Bus-Kabel

    Alle systeembesturingen -SLAVE- en alle CAN bus- compatibele hygiënespoelers worden geleverd met een 120Ω- eindweer-stand. Bij niet aan het einde gelegen systeem- 120 Ω besturingen -SLAVE- of hygiënespoelers moet de weerstand verwijderd worden! © www.kemper-group.com – 10.2023 / K410068602008-00 – 191 /265...
  • Pagina 192: Inbedrijfstelling

    Verlaten van het menu – wisselen tussen overzicht en hoofdmenu  Terug scrollen Bevestigingstoets  Vooruit scrollen De menubediening van de KHS Mini besturingsunit MASTER 2.1 is in twee venstertypes onderverdeeld. 192 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 193 CAN-Bus van het besturingssysteem actief Storing gesignaleerd Lekdetectie van het besturingssysteem actief Flowsensor aangesloten* Tijdgestuurd spoelen ingesteld* Temperatuursensor aangesloten* P1 / P2 Actieve programma Pagina 1 van 8 * Het telkens knipperende symbool geeft aan, welke besturing (fl ow, tijd, temperatuur de actueel actieve spoeling heeft geactiveerd. © www.kemper-group.com – 10.2023 / K410068602008-00 – 193 /265...
  • Pagina 194 Instelling van de bedrijfsmodi per spoelgroep Logboek Inzage in de resultaten van de spoelmaatregelen Programmakeuze Instellen van de programma´s Handbed. afsluiter Handmatige bediening bepaalde afsluiters Netwerk Setup Instellingen voor integratie in een bestaand netwerk 194 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 195: Systeeminstelling

    Systeeminstelling 3.1.2.1 Taal Tijd Datum Z/W automatisch Alarmsignaal Alarm opheffen © www.kemper-group.com – 10.2023 / K410068602008-00 – 195 /265...
  • Pagina 196 gureerd worden. Als opgevraagd. Info! Af fabriek is het wachtwoord ingesteld op „0000“. Fabrieksinstellingen Aanwijzing! Alle ingestelde waarden gaan verloren! MASTER opnieuw starten 196 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 197: Can-Bus Setup

    Er is geen apparaat aan de geselecteerde SLAVE toegewezen Seriennummer Serienummer KHS Mini besturingsunit SLAVE 2.XX 2.XX 07/14 Ser. Nr.: XXXXXX Typ: KHS Mini Systemsteuerung SLAVE Netz: 230/1N/PE/50 Hz/max.3,15A Art.Nr.: 8210068602006-00 Ser.Nr.: XXXXXX IP 54 © www.kemper-group.com – 10.2023 / K410068602008-00 – 197 /265...
  • Pagina 198: Hoofdscherm

    C-afsluiter Spoelafsluiter aan het eind van een enkele strang. Beveiliging Afsluiter, die een verdeelleiding beveiligt. Alleen meten Slave voor het opslaan en de controle op langere termijn van sensorwaarden. 198 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 199 De toewijzing van de afsluiters wordt hierna getoond. Voor informatie over de afsluitertechniek zie hoofdstuk 10.1. Instellen A-afsluiter Selectie besturingsunit besturingstype  B-afsluiter  Zie verdere instellingen Waarschuwing! Aanbevolen wordt niet meer dan 5 A-afsluiters op een B-afsluiter aan te sluiten. © www.kemper-group.com – 10.2023 / K410068602008-00 – 199 /265...
  • Pagina 200 Apparaatinstellingen 3.1.2.3 Instellen C-afsluiter Selectie besturingsunit besturingstype  Afsluiter  Zie verdere instellingen Instellen beveiliging Selectie besturingsunit besturingstype  Afsluiter  Zie verdere instellingen 200 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 201: Instellen Flowmeting

    3.1.2.3 Instellen flowmeting Selectie besturingsunit besturingstype  Selectie sensor Zie instellen flowsensor  Selectie sensor Zie instellen temperatuur- sensor  Zie verdere instellingen Instellen flowsensor Selectie sensor Aanwijzing! Het meetbereik van de sensor kan van een sticker op de ingebouwde flowsensor afgelezen worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 201 /265...
  • Pagina 202 Overzicht van de softwareversie van de gekozen besturings- unit. Instelmogelijkheid om twee afsluiters van een KHS HS  gelijktijdig te laten openen. Afhankelijk van de fl ow gelden volgende richtlijnen t.a.v. geluidsisolatie en vrije uitloop. Gelijktijdig openen van de afsluiters V1/V2 tijdens hygiënespoeling 202 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 203: Bedrijfsmodi

    Aanwijzing! ls de programma-omschakeling „Geactiveerd“ is (zie hoofdstuk 3.1.2.6), dan wordt bij het instellen van de bedrijfsmodus gevraagd voor welk programma dit geldt (zie rechts). Er kan tussen de twee genoemde spoelprogramma´s geschakeld worden met behulp van een externe handmatige schakelaar. De elektrische aansluiting wordt in hoofdstuk 2.2 uitgelegd. © www.kemper-group.com – 10.2023 / K410068602008-00 – 203 /265...
  • Pagina 204 Bedrijfsmodi 3.1.2.4 Instellen tijdgestuurd spoelen Instellen volumegestuurd spoelen Instellen temperatuurgestuurd spoelen 204 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 205: Instellen Beveiliging

    Gesorteerd op datum, tijd, index, naam en de Routine-spoeling Als er een temperatuurspoeling wordt ingesteld, geactiveerd. In principe kan een van de volgende wordt er automatisch een routine-duur routines geselecteerd worden: © www.kemper-group.com – 10.2023 / K410068602008-00 – 205 /265...
  • Pagina 206 Bedrijfsmodi 3.1.2.4 Routine-tijd Routine-duur Routine-volume Aanwijzing! Geadviseerd wordt om na het succesvol instellen van het besturings-systeem, de configuratie als reservebestand op te slaan. Mocht de KHS Mini-besturingsunit MASTER 2.1 een defect hebben, kan hij snel vervangen en de configuratie ingelezen worden. Dan hoeft het systeem dan niet helemaal opnieuw ingesteld te worden. 206 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 207: Parametrering Gedeactiveerd

    Met de KHS Mini-systeembesturing MASTER 2.1 is submenu „Programma omschakelen“ geactiveerd het mogelijk om via een externe schakelaar tussen en gedeactiveerd worden. De „Externe ingang“ tussen twee spoelprogramma‘s te wisselen of deze c.q. „Externe schakelaar“ kan in dit submenu aan te blokkeren. De programma‘s kunnen ook in het een programmaomschakeling toegewezen worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 207 /265...
  • Pagina 208: Handmatige Bediening Afsluiter

    De functies worden in de afbeelding hieronder via het submenu „Handbed. afsluiter“ uit te getoond. De handmatige modus voor de voeren. Bovendien kunnen de afsluiters in CoolFlow koudwater-regelafsluiter is mogelijk met softwareversie V2.23.15. Aanwijzing Onderhoud! Aanbevolen wordt om na het maken van de instellingen in het submenu „Apparaatinstellin- gen“ een functietest uit te voeren, om eventuele fouten meteen uit te sluiten. 208 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 209: Netwerk-Setup

    Na het wijzigen van de netwerkinstellingen moet de master 2.1 opnieuw worden opgestart om er zeker van te zijn dat alle instellingen zijn overgenomen. Zonder een herstart van de Master 2.1 kunnen er problemen optreden bij het tot stand brengen van de verbinding. © www.kemper-group.com – 10.2023 / K410068602008-00 – 209 /265...
  • Pagina 210 Net mask instellen  Prim. DNS-server instellen  Sec. DNS-server instellen  http-gebruikersnaam instellen  Inbouw- en Installatiehandleiding bedieningshandleiding Modbus TCP/IP-licentie KHS BACnet Gateway  Test-e-mail versturen www.kemper-group. www.kemper-group. com/de/khs-modbus-eba com/de/khs-bacnet-eba 210 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 211: Fout Bevestigen

       Info! Een gedetailleerde lijst van mogelijke fouten en hun oplossingen is te vinden in hoofdstuk 7. © www.kemper-group.com – 10.2023 / K410068602008-00 – 211 /265...
  • Pagina 212: Usb-Poort

    Bij de keuze van dit menupunt worden alle opgeslagen spoelprocessen als CSV-bestand op de USB-stick opgeslagen. Configuratie kopiëren naar de USB-stick Bij de keuze van dit menupunt worden alle opgeslagen instellingen als CFG-als CFG-Datei bestand op de USB-stick opgeslagen. 212 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 213: Configuratie Lezen Vanaf De Usb-Stick

    Bij de keuze van dit menupunt wordt de webserver met de map ‚KHS Webserver‘ op de USB-stick geactualiseerd. Aanwijzing! Na een update moet aan iedere systeembesturing en hygiënespoeler een vergelijking van de softwareversie en een functiecontrole worden uitgevoerd. Info! De actuele softwareversie vindt u onder kemper-group.com/de/geschaeftsbereiche/gebaeudetechnik/service/ downloads/ © www.kemper-group.com – 10.2023 / K410068602008-00 – 213 /265...
  • Pagina 214: Web-Server

    Als u de wijzigingen niet in het erd worden. In de afzonderlijke menu-tabs kunt u systeem wilt opslaan, gebruik dan de schermknop basisgegevens, instellingen en wijzigingen WIJZIGINGEN ANNULEREN. Afb. 6.1.1 Menutabblad van de WEB-browser 214 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 215 Bij het gebruik via een mobiele telefoon worden de menubladen via een button zichtbaar (zie hieronder). De werking van de afzonder- lijke menu´s is echter gelijk, enkel de grafi eken van de componenten worden niet weergegeven. Aanwijzing! Af fabriek de gebruikers-naam is ingesteld op „KHS“ en het wacht-woord op „0000“. © www.kemper-group.com – 10.2023 / K410068602008-00 – 215 /265...
  • Pagina 216: Systeeminstellingen

    OPSLAAN. Nadat de instellingen zijn opgeslagen, moet u zich bij iedere start van de WEB-browser identifi ceren. Hiervoor voert u de gekozen gebruikers- naam en het bijbehorende wachtwoord in het automatisch geopende venster in, zoals in afbeelding 6.2.1 getoond. Het gebruik door meerdere gebruikers is niet mogelijk. 216 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 217  Gateway: 10.1.23.254 De netwerkinstellingen kunnen alleen bij het opladen van de instellingen via een USB-stick geladen worden. Bij het opladen van de instellingen via de Web-server worden deze niet mee overgenomen. © www.kemper-group.com – 10.2023 / K410068602008-00 – 217 /265...
  • Pagina 218: Overige Instellingen

    Verder kan via een drop-down menu de taal veranderd worden. Apparaatinstellingen In het menu „APPARAATINSTELLINGEN“ worden ingebouwde afsluiters en sensoren logisch met de afzonderlijke KHS Mini-besturingsunits met de elkaar verbonden. 218 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 219 Mocht er een fout in de besturingsunits optreden, dan kan deze in het hele systeem gemeld worden. Hiervoor de button op zetten. De overige invoermogelijkheden van het invoervenster worden hieronder toegelicht. © www.kemper-group.com – 10.2023 / K410068602008-00 – 219 /265...
  • Pagina 220: Apparaatinstellingen - Apparaten Toevoegen

    De KHS Mini besturingsunit moet in dit voorbeeld een B-afsluiter aansturen. Afsluiter kiezen De mogelijke afsluiters worden uit een drop-down lijst gekozen. De KHS Mini-besturingsunit moet in dit voorbeeld een KHS afsluiter met servomotor met veerretour aansturen. 220 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 221 Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. © www.kemper-group.com – 10.2023 / K410068602008-00 – 221 /265...
  • Pagina 222 A-afsluiter worden geselecteerd. Bijbehorende B-afsluiter kiezen Iedere A-afsluiter moet op een B-afsluiter aangesloten worden. De ter beschikking staande KHS Mini besturingsunits die op een B-afsluiter aangesloten zijn, kunnen uit een drop-downlijst gekozen worden. 222 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 223 Sensor kiezen De mogelijke sensoren worden uit een drop-down lijst gekozen. De A-/B-afsluitertechniek moet in het aangegeven voorbeeldproject temperatuur- gestuurd spoelen. Daarvoor moet de temperatuur worden gemeten met de KHS temperatuursensor Pt1000. © www.kemper-group.com – 10.2023 / K410068602008-00 – 223 /265...
  • Pagina 224 Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. 224 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 225 A-afsluiter worden geselecteerd. Bijbehorende B-afsluiter kiezen Iedere A-afsluiter moet op een B-afsluiter aangesloten worden. De ter beschikking staande KHS Mini-besturingsunits die op een B-afsluiter aangesloten zijn, kunnen uit een drop-downlijst gekozen worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 225 /265...
  • Pagina 226 De mogelijke sensoren worden uit een drop-down lijst gekozen. In het aangegeven voorbeeldpro- ject met CoolFlow koudwatercirculatie moeten de drinkwatertemperaturen worden gemeten en opgeslagen. Daarvoor wordt de temperatuur gemeten met de KHS temperatuursensor Pt1000. 226 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 227 Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. © www.kemper-group.com – 10.2023 / K410068602008-00 – 227 /265...
  • Pagina 228 KHS Mini-besturingsunit moet in dit voorbeeld een C-afsluiter aansturen.. Afsluiter kiezen De mogelijke afsluiters worden uit een drop-down lijst gekozen. De KHS Mini-besturingsunit moet in dit voorbeeld een KHS afsluiter met servomotor met veerretour aansturen. 228 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 229 Sensor kiezen De mogelijke sensoren worden uit een drop-down lijst gekozen. De C-afsluiter moet in het aange- geven voorbeeldproject temperatuurgestuurd spoelen. Daarvoor moet de temperatuur worden gemeten met de KHS temperatuursensor Pt1000. © www.kemper-group.com – 10.2023 / K410068602008-00 – 229 /265...
  • Pagina 230 Select sensor De mogelijke sensoren worden uit een drop-down lijst gekozen. Met de fl owsensor kan de C-afslui- ter een volumespoeling uitvoeren. Hij wordt ook gebruikt om het spoelvolume te meten en op te slaan. 230 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 231: Instellen Beveiliging

    Besturingstype kiezen De mogelijke besturingstypes, die door de gekozen KHS Mini-besturingsunit gebruikt kunnen worden, kunnen uit een drop-down lijst gekozen worden. De KHS Mini besturingsunit moet in dit voorbeeld als beveiligings-afsluiter fungeren. © www.kemper-group.com – 10.2023 / K410068602008-00 – 231 /265...
  • Pagina 232 KHS afsluiter met servomotor aansturen. Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. 232 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 233: Instellen Meting

    De getoonde KHS Mini-besturingsunit - SLAVE - moet in dit voorbeeld als meetsysteem fungeren. Sensor kiezen De mogelijke sensoren worden uit een drop-down lijst gekozen. De KHS Mini-systeembesturing -SLA- VE- moet worden toegewezen aan een fl owsensor. © www.kemper-group.com – 10.2023 / K410068602008-00 – 233 /265...
  • Pagina 234: Instelling Hygiënespoeler

    Door op de button NAAM OVERNEMEN te klikken, wordt de ingevoerde naam aan het systeem toegewezen. Info! Afsluiter van de KHS HS2 hygiënespoeler (V2=links; V1=rechts) Afsluiter van de KHS Flush Box PRO (V2=rechts; V1=links) 234 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 235 Met behulp van de drop-downlijst wordt een besturingstype (C-afsluiter) aan de hygiënespoeler toegewezen. Sensor kiezen De mogelijke sensoren worden uit een drop-down lijst gekozen. Op de hygiënespoeler kan een KHS termperatuursensor PT1000 aangesloten worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 235 /265...
  • Pagina 236 Met de boven- en ondergrens worden de grenswaarden voor de melding ingesteld. Sensor kiezen Via een drop-downlijst kan een interne fl owsensor aan de hygiënespoeler toegevoegd worden. 236 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 237: Bedrijfsmodi

    IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. Bedrijfsmodi In het menu „BEDRIJFSMODI“ worden voor de KHS afhankelijk van het besturingstype spoeltijden, Mini-besturingsunits besturings-specifi eke TIMERS meetintervallen, back-up-tijden, routine-intervallen, (programma‘s) ingesteld. Met een TIMER worden temperatuurspoelingen, etc. gedefi nieerd. © www.kemper-group.com – 10.2023 / K410068602008-00 – 237 /265...
  • Pagina 238 , worden schermknop REGELS TOEVOEGEN kunnen max. 16 alle gedeactiveerde regels gewist en lege regels regels aan de TIMER worden toegevoegd. Door te naar onderen verschoven. De invoermogelijkheden worden hieronder toegelicht. 238 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 239 Nadat er een regel via REGELS TOEVOEGEN ingevoegd, wordt het regeltype geselecteerd. De KHS Mini-besturingsunit is in dit voorbeeldproject op een A-afsluiter aangesloten. Om te zorgen dat er een tijdgestuurde spoelmaatregel plaatsvindt, moet in de drop-downlijst het regeltype „Tijdspoe- ling“ gekozen worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 239 /265...
  • Pagina 240 Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. 240 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 241: Instelling Deactiveert A-Afsluiter Khs Coolflow Afsluiter

    Als een regeltype gekozen is, moeten de tijden gedefi nieerd worden. Bij het regeltype ‚Gedeacti- veerd‘ kunnen via een drop-down lijst de gewenste weekdagen worden geselecteerd. Door een ‚klik‘ in het vakje van de betreffende weekdag wordt deze met een vinkje geactiveerd. © www.kemper-group.com – 10.2023 / K410068602008-00 – 241 /265...
  • Pagina 242 Type spoelmaatregel kiezen Nadat er een regel via REGELS TOEVOEGEN ingevoegd, wordt het regeltype geselecteerd. Om te zorgen dat er een volumegestuurde spoelmaa- tregel plaatsvindt, moet in de drop-downlijst het regeltype „Volumespoeling“ gekozen worden. 242 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 243 Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. © www.kemper-group.com – 10.2023 / K410068602008-00 – 243 /265...
  • Pagina 244 Temperaturen defi niëren Als een regeltype geselecteerd is, moeten de tem- peraturen worden gedefi nieerd. Bij het regeltype ‚Temperatuurspoeling‘ moet een start-/stoptem- peratuur en de maximale duur van de spoeling worden aangegeven. 244 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 245 Als er binnen een ingestelde interval geen tempe- „Routine- volume“ het gewenste interval (max. ratuurspoeling plaatsvindt, wordt de spoelmaatre- 168 uur), de hoeveelheid en de maximale spoeltijd gel via de bedrijfsmodus „Routinevolume“ gega- van de spoelmaatregel worden opgenomen. randeerd. Hiervoor kunnen in de bedrijfsmodus © www.kemper-group.com – 10.2023 / K410068602008-00 – 245 /265...
  • Pagina 246 Instellen van een hygiënespoeler Tijdspoeling kiezen Nadat er een regel via REGELS TOEVOEGEN ingevoegd, wordt het regeltype geselecteerd. Om te zorgen dat er een tijdgestuurde spoelmaatregel plaatsvindt, moet in de drop-downlijst het regelty- pe „Tijdspoeling“ gekozen worden. 246 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 247 Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. Instellen beveiliging Type kiezen Nadat er een regel via REGELS TOEVOEGEN ingevoegd, wordt het regeltype geselecteerd. Uit de drop-downlijst wordt het regeltype „Vrijga- ve“ geselecteerd. © www.kemper-group.com – 10.2023 / K410068602008-00 – 247 /265...
  • Pagina 248: Instellen Meten (Datalogging)

    Nadat er een regel via REGELS TOEVOEGEN ingevoegd, wordt het regeltype geselecteerd. In dit voorbeeld is de KHS Mini-besturingsunit op een KHS Control Plus fl owsensor aangesloten. Om te zorgen dat de meetgegevens van de fl owsensor opgeslagen worden, moet uit een drop-downlijst het regeltype „Datalogging“ geselecteerd worden. 248 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 249 De intervaltijd geeft aan met welke tussenpozen de meetgegevens worden opgeslagen. Instellingen opslaan De nieuwe instellingen moeten opgeslagen worden voordat ze in werking treden. Klik op de button IN BESTURINGSUNIT OPSLAAN om de instellingen op te slaan. © www.kemper-group.com – 10.2023 / K410068602008-00 – 249 /265...
  • Pagina 250: Overzicht

    Afsluiter gesloten A-afsluiter stuurt naar de spoelstand, B-afsluiter is geopend Apparaat- of systeemstoring KHS CoolFlow afsluiter in regelstand Instelling automatisch bedrijf/handmatig bedrijf open/dicht Afsluiter in spoelstand Initialisatie-run van de KHS CoolFlow afsluiter 250 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 251: Gegevensoverdracht

    Gegevensoverdracht In het tabblad „GEGEVENSOVERDRACHT“ kunnen en de gecreëerde datalog-bestanden geladen confi guraties, software-updates, logboekgegevens worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 251 /265...
  • Pagina 252 6.6.1, het UPE-bestand. Klik op de schermknop LOAD UPDATE. Vervolgens opent zich een bevestigingsvenster, zoals in afbeelding 6.6.2. „Klik“ op de button OK en de geselecteerde setup wordt in het besturingssysteem geladen. Afb.: 6.6.1: Keuzevenster„Setup-bestand opladen“ Afb.: 6.7.2: Bevestigingsvenster „Softwareupdate“ Aanwijzing! Sla voor de zekerheid uw confi guratie op vóór het opladen van een update. 252 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 253 Aanbevolen wordt op na het succesvol instellen van uw besturingssysteem, de confi guratie als reservebestand extern op te slaan. Mocht de KHS Mini-besturings- unit -MASTER 2.1- defect zijn of raken, dan kan hij snel vervangen worden en kan de confi guratie eenvoudig ingelezen worden. U hoeft hem dan niet helemaal opnieuw in te stellen. © www.kemper-group.com – 10.2023 / K410068602008-00 – 253 /265...
  • Pagina 254: Logboek En Spoelprotocol

    Het is Via de button gaat er een venster open zoals in mogelijk max. 12 miljoen regels op te slaan. Door afbeelding 6.6.7 getoond. Door een „klik“ op OK een „klik“ op de schermknop LOGBESTAND GENE wordt het geselecteerde. 254 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 255 Afb.: 6.6.8: Weergave fragment van een CSV-logbestand Aanwijzing! De tussenpozen waarmee de meetwaarden worden opgeslagen, kunnen, zoals beschreven in hoofdstuk 6.3. via het menu „BEDRIJFSMODI“ ingesteld worden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 255 /265...
  • Pagina 256: Beschrijving En Opheffen Van Storingen

    Tijd & datum contro- Gegevens Alle op tijd gebaseerde Gegevens in de klok zijn leren, evt. opnieuw realtime-klok gebeurtenissen vinden op een niet consistent. instellen. Batterij cont- inconsistent verkeerde tijd/datum plaats. roleren/ evt. vervangen. 256 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 257 PRO-Hygiene inbedrijfstelling assistent. warmwater water, temperatuur fout Flush Box. overschreden. © www.kemper-group.com – 10.2023 / K410068602008-00 – 257 /265...
  • Pagina 258 Er is geen spoeling actief. Geen actie Geen invloed stand-by Besturing in stand-by. noodzakelijk! De afsluiter op de desbe- Geen actie Invoer in het Spoeling loopt treffende besturing spoelt / noodzakelijk! logboek. is open. 258 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 259: Reserveonderdelen

    Voor Master  Mini-besturingssysteem hardware MASTER 2.0/2.1 Hard- stand 2.01 ware stand 2.01 6860202200 microSD kaart voor  netwerk module in KHS Klantenservice Klantenservice Mini-besturingssysteem toepassingstechniek MASTER 2.0/2.1 Tel. +49 2761 891-800 © www.kemper-group.com – 10.2023 / K410068602008-00 – 259 /265...
  • Pagina 260: Bekabelingsinstructies Voor Khs Componenten Met Elektrische Aansluiting

    Aanwijzing! * Mogelijk kabeltype bij vaste aansluiting, Conform VDE 0815: De diameter van zonder mechanische belasting de bekabeling is in mm aangegeven. ** afgeschermde kabeltoevoer 260 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 261 Bekabelingsinstructies voor KHS componenten met elektrische aansluiting * Mogelijk kabeltype bij vaste aansluiting, zonder mechanische belasting ** afgeschermde kabeltoevoer © www.kemper-group.com – 10.2023 / K410068602008-00 – 261 /265...
  • Pagina 262 Bekabelingsinstructies voor KHS componenten met elektrische aansluiting * Mogelijk kabeltype bij vaste aansluiting, zonder mechanische belasting Stand: November 2022 ** afgeschermde kabeltoevoer 262 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 263: Bijlage

    KHS afsluiter met KHS afsluiter met servomo- gelen worden deze na elkaar door het servomotor 230V AC tor met veerretour 230V AC systeem uitgevoerd. Figuur 686 04 Figuur 686 05 © www.kemper-group.com – 10.2023 / K410068602008-00 – 263 /265...
  • Pagina 264: Coolflow Koudwatercirculatie

    Op deze wijze wordt in de betreffende leidingtrajecten een doelgerichte wa- terverversing uitgevoerd. Na een waterverversing sluit de B-afsluiter en de koudwater-regelafsluiters sturen weer naar de regelstand. Aanbevolen wordt een onderhouds- afsluiter, fi g. 173, voor iedere A-afsluiter te installeren. 264 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com...
  • Pagina 265 Gebr. Kemper GmbH + Co. KG Service-Hotline +49 2761 891-800 Harkortstraße 5 www.kemper-group.com D-57462 Olpe info@kemper-group.com © www.kemper-group.com – 10.2023 / K410068602008-00 – 265 /265...

Deze handleiding is ook geschikt voor:

Khs slave686 02 008686 02 006

Inhoudsopgave