7
Status
Error
LED
Backwater in
drain
Backwater in
drain
Temperature
flushing swit-
ched off during
runtime
Volume flus-
hing switched
off during
runtime
Pt 1000 value
too high
Pt 1000 value
too low
Leak on sensor
Real-time
clock data
inconsistent
Flow detected
with valve
closed
„No flow de-
tected despite
open valve"
168 /265 – K410068602008-00 / 10.2023 – © www.kemper-group.com

Error description and error handling

Possible reason
General error
Drain is clogged or can-
not accept the flushing
volume.
Float switch on the drain
has a cable break.
Medium did not reach the
switch-off temperature in
the set time.
Set volume not reached.
Sensor defective / No
sensor available
Sensor defective / No
sensor available
Pipe failure, moisture on
the sensor
Data in the clock are not
consistent
Flow is detected by the
flow measurement valve
when the valve is closed.
No flow is detected du-
ring a flushing process.
Measure
Check the drain channel,
channel acceptance
capacity.
Replace cable / switch.
Check the installation
setup and the maximum
flushing time.
Check the installation
setup and the maximum
flushing time.
Replace sensor / Check
inputs on the MASTER.
Replace sensor / Check
inputs on the MASTER.
Check the local area and
remove the moisture.
Check the time & date
and adjust if necessary.
Check battery/replace if
applicable.
Check the function of the
flushing valve.
Check the flushing line
and the flushing valve.
Effect
Error message!
Defective control will be com-
pletely blocked.
Error message!
Defective control will be com-
pletely blocked.
Error message!
Temperature operating mode is
blocked in the defective control.
Error message!
Volume operating mode is blo-
cked in the defective control.
Error message!
Temperature flushing operating
mode is blocked in the defecti-
ve control.
Error message!
Temperature flushing operating
mode is blocked in the defecti-
ve control.
The safety valve is blocking the
system.
All time-based services are
running on incorrect time/date.
Error message! The involved
valve will be blocked.
Error message! The involved
valve will be blocked.